dupsOutputSource
DeltaUPS-MIB ·
.1.3.6.1.4.1.2254.2.4.5.1
Object
scalar
mandatory
Enumeration
The present source of output power. The enumeration none(7) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.
Context
- MIB
- DeltaUPS-MIB
- OID
.1.3.6.1.4.1.2254.2.4.5.1- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- dupsOutput
- Siblings
- 14
Syntax
Enumeration
Values & Constraints
Enumerated Values
0 | normal |
1 | battery |
2 | bypass |
3 | reducing |
4 | boosting |
5 | manualBypass |
6 | other |
7 | none |
8 | on-eco |
Object Constraints
range: 0-64
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| dupsOutputPower2 mandatory The Output line 2 real power of the UPS system in watts. | scalar | Integer32 | .1.3.6.1.4.1.2254.2.4.5.10 |
| dupsOutputLoad2 mandatory The current UPS output line 2 load expressed in percent
of rated capacity. | scalar | Integer32 | .1.3.6.1.4.1.2254.2.4.5.11 |
| dupsOutputVoltage3 mandatory The Output line 3 voltage of the UPS system in 1/10 V. | scalar | Integer32 | .1.3.6.1.4.1.2254.2.4.5.12 |
| dupsOutputCurrent3 mandatory The Output line 3 current of the UPS system in 1/10 A. | scalar | Integer32 | .1.3.6.1.4.1.2254.2.4.5.13 |
| dupsOutputPower3 mandatory The Output line 3 real power of the UPS system in watts. | scalar | Integer32 | .1.3.6.1.4.1.2254.2.4.5.14 |
| dupsOutputLoad3 mandatory The current UPS output line 3 load expressed in percent
of rated capacity. | scalar | Integer32 | .1.3.6.1.4.1.2254.2.4.5.15 |
| dupsOutputFrequency mandatory The present output frequency in 1/10 Hz. | scalar | 0.1 Hertz Integer32 | .1.3.6.1.4.1.2254.2.4.5.2 |
| dupsOutputNumLines mandatory The number of output lines utilized in this device. | scalar | Integer32 | .1.3.6.1.4.1.2254.2.4.5.3 |
| dupsOutputVoltage1 mandatory The Output line 1 voltage of the UPS system in 1/10 V. | scalar | Integer32 | .1.3.6.1.4.1.2254.2.4.5.4 |
| dupsOutputCurrent1 mandatory The Output line 1 current of the UPS system in 1/10 A. | scalar | Integer32 | .1.3.6.1.4.1.2254.2.4.5.5 |
| dupsOutputPower1 mandatory The Output line 1 real power of the UPS system in watts. | scalar | Integer32 | .1.3.6.1.4.1.2254.2.4.5.6 |
| dupsOutputLoad1 mandatory The current UPS output line 1 load expressed in percent
of rated capacity. | scalar | Integer32 | .1.3.6.1.4.1.2254.2.4.5.7 |
| dupsOutputVoltage2 mandatory The Output line 2 voltage of the UPS system in 1/10 V. | scalar | Integer32 | .1.3.6.1.4.1.2254.2.4.5.8 |
| dupsOutputCurrent2 mandatory The Output line 2 current of the UPS system in 1/10 A. | scalar | Integer32 | .1.3.6.1.4.1.2254.2.4.5.9 |