seetag-cust-alm3
DataAire-dap4-al-MIB ·
.1.3.6.1.4.1.9839.2.1.1.58
Object
scalar
N/A Integer32
Local alarm #3: See tag inside door =Optional alarm. External alarm input required
Context
- MIB
- DataAire-dap4-al-MIB
- OID
.1.3.6.1.4.1.9839.2.1.1.58- Type
- scalar
- Access
- readonly
- Status
- current
- Units
- N/A
- Parent
- digitalObjects
- Siblings
- 59
Syntax
N/A Integer32
Values & Constraints
Object Constraints
range: 0-1
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| dehum-on Dehumidify mode is running | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.1 |
| air-flow-alm No air flow alarm | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.10 |
| filter-alm Dirty filter from digital input | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.11 |
| humidifier-alm Alarm from humidifier digital input | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.12 |
| firestat-alm Temperature of return air above firestat alarm set point | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.13 |
| shortcycle-alm One or more comps has short cycled | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.14 |
| humidity-fail Sensor is out of range | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.15 |
| ret-air-fail Sensor is out of range | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.16 |
| maint-alm Maintenance Schedule Due alarm | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.17 |
| c1-hp-alm High pressure alarm | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.18 |
| c1-lp-alm Low pressure alarm | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.19 |
| hum-on Humidifier is running | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.2 |
| c2-hp-alm High pressure alarm | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.20 |
| c2-lp-alm Low pressure alarm | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.21 |
| smoke-alm Smoke detected from digital input | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.22 |
| wtr-flow-alm No water flow alarm | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.23 |
| disch-air-fail Sensor is out of range | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.24 |
| ra-tmp-hi-alm Temperature of return air above alarm set point | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.25 |
| ra-tmp-lo-alm Temperature of return air below alarm set point | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.26 |
| hum-hi-alm Humidity above alarm set point | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.27 |
| hum-lo-alm Humidity below alarm set point | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.28 |
| fan-overload Fan overload | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.29 |
| engy-on Energy saver is running | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.3 |
| stdby-pump-on Standby pump on: Check primary pump -Optional alarm. Pump failure input signal required | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.30 |
| cust-msg-sw1 Custom alarm #1 -Optional alarm. External alarm input required. Factory programmed custom message required | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.31 |
| cust-msg-sw2 Custom alarm #2 -Optional alarm. External alarm input required. Factory programmed custom message required | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.32 |
| cust-msg-sw3 Custom alarm #3 -Optional alarm. External alarm input required. Factory programmed custom message required | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.33 |
| cust-msg-sw4 Custom alarm #4 -Optional alarm. External alarm input required. Factory programmed custom message required | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.34 |
| humsw-inhibit Humidifier stopped due to custom alarm switch | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.35 |
| heat-inhibit Heat inhibited due to custom switch alarm condition | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.36 |
| rht-hum-inhibit Reheat and humidification inhibited from operation | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.37 |
| disch-tmp-lo-alm Temperature of discharge air below alarm set point | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.38 |
| override-alm Manual override: Check bypass switches - Standard alarm. Manual override switch is on | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.39 |
| cool-inhibit Cooling inhibit from Zone Master | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.4 |
| condensation-alm High condensation from digital input | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.40 |
| unit-in-standby Unit in standby, all functions held off - Optional alarm. Control input signal required Factory setting required | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.41 |
| cw-sns-fail Sensor is out of range | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.42 |
| humsw-chk-cyl Humidifier stopped due to custom alarm switch | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.43 |
| bms-cooling-inhibit Cooling operation inhibited by BMS | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.44 |
| bms-heat-inhibit Heat inhibited due to bms | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.45 |
| bms-humidifier-inhibit Humidifier operation inhibited by BMS | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.46 |
| bms-dehum-inhibit Dehumidify mode inhibited by bms | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.47 |
| fan-inhibit-bms Inhibit fan by bms | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.48 |
| hum-expect Reduces control humidity cycling | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.49 |
| heat-held Heat inhibited due to alarm condition | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.5 |
| usashr-f-c Temperature Mode 0=_C 1=_F | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.50 |
| lead-comp Lead compressor select 0= C1, 1= C2 | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.52 |
| wtrvlv-dir Water valve direct or reverse acting | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.53 |
| ups-on-alm Alarm: UPS power on: Check main power -Optional alarm. External alarm input required | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.54 |
| pwrup-alm Loss of power requires manual reset of alarm | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.55 |
| seetag-cust-alm1 Local alarm #1: See tag inside door =Optional alarm. External alarm input required | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.56 |
| seetag-cust-alm2 Local alarm #2: See tag inside door =Optional alarm. External alarm input required | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.57 |
| seetag-cust-alm4 Local alarm #4: See tag inside door =Optional alarm. External alarm input required | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.59 |
| humidifier-inhibit Humidifier stopped due to alarm | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.6 |
| shortcycle-alm-en Enable short cycle alarm of the compressors | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.60 |
| superv-off Supervisor (BMS) On-Off. Show the state OFFbyBMS in main mask (1: Off; 0: On | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.61 |
| dehum-inhibit Dehum is inhibited | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.7 |
| rht-during-dehum reheat during dehum | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.8 |
| floor-wtr-alm Water under floor alarm | scalar | N/A Integer32 | .1.3.6.1.4.1.9839.2.1.1.9 |