upsSmartConfigRatedOutputVoltage
DGPUPS-MIB ·
.1.3.6.1.4.1.17420.1.1.2.5.2.1
Object
The nominal output voltage from the UPS in 1/10 VAC.
Possible values are 1000, 1200, 2080, 2200, 2250, 2300
and 2400.
NOTE: Only units that are 2200, 2250, 2300 and 2400 can
be changed. Allowable values are 2200, 2250, 2300 and
2400.
For these adjustable units, if a value other than
a supported value is provided in a set request, the
UPS interprets it as the next lower acceptable value.
If the provided value is lower than the lowest acceptable
value, the lowest acceptable value is used.
Context
- MIB
- DGPUPS-MIB
- OID
.1.3.6.1.4.1.17420.1.1.2.5.2.1- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- upsSmartConfig
Net-SNMP examples
How SNMP and these commands workScalars have one instance, identified by the .0 suffix.
Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'DGPUPS-MIB' -M '/opt/observium/mibs/digipower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'DGPUPS-MIB::upsSmartConfigRatedOutputVoltage.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'DGPUPS-MIB' -M '/opt/observium/mibs/digipower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'DGPUPS-MIB::upsSmartConfigRatedOutputVoltage'
Syntax
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647