upsSmartConfigLowTransferVolt
DGPUPS-MIB ·
.1.3.6.1.4.1.17420.1.1.2.5.2.3
Object
scalar
mandatory
r/w
Integer32
The minimum line voltage in 1/10 VAC allowed before the
UPS system transfers to battery backup.
Allowable values depend on the UPS used:
120 Volt units allow settings of 970, 1000, 1030, 1060.
100 Volt units allow settings of 810, 830, 850, 870.
230 Volt units allow settings of 1880, 1960, 2040, 2080.
208 Volt units allow settings of 1680, 1720, 1770, 1820.
If a value other than a supported value is provided in a
set request, the UPS interprets it as a the next higher
acceptable value. If the provided value is higher than
the highest acceptable value, the highest acceptable
value is used.
Context
- MIB
- DGPUPS-MIB
- OID
.1.3.6.1.4.1.17420.1.1.2.5.2.3- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- upsSmartConfig
Syntax
Integer32
Values & Constraints
No enumerated values or constraints recorded.