cpqRPMTrapUPSLossOfRedundancyCleared

CPQRPM-MIB · .1.3.6.1.4.1.232.154.2.0.21024

Object

notification
A UPS device is reporting a loss of redundancy due to one of the following.
1. One or more of the Electronics Modules has failed
2. One or more of the electronics modules has been manually removed.
3. The amount of load on the UPS has increased to the point that the UPS is no longer
   able to support an N+1 configuration.
          
Recommendations:
          
1. Check the UPS to see if one of the modules has failed.
2. Make sure that all modules are securely plugged in.
3. Reduce the load to return the N+1 configuration.
4. If the amount of load is now going to exceed and N+1 configuration permanently,
   change the configuration on the front panel of the UPS to Capacity instead of Parallel N+1.