dcPwrSysDischargeAmps
OBS ✓
AlphaPowerSystem-MIB ·
.1.3.6.1.4.1.7309.4.1.1.4
Object
scalar Integer32
This value indicates the present load current.
The integer value represent a two digit fix decimal (Value = real current * 100) in Amps.
Observium directly uses this object
This object is referenced by an Observium discovery or polling workflow.
Used in:
Sensors
Explore Observium network monitoring
Context
- MIB
- AlphaPowerSystem-MIB
- OID
.1.3.6.1.4.1.7309.4.1.1.4- Type
- scalar
- Access
- readonly
- Status
- current
- Parent
- dcPwrSysVariable
Net-SNMP examples
How SNMP and these commands workScalars have one instance, identified by the .0 suffix.
Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'AlphaPowerSystem-MIB' -M '/opt/observium/mibs/alpha:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'AlphaPowerSystem-MIB::dcPwrSysDischargeAmps.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'AlphaPowerSystem-MIB' -M '/opt/observium/mibs/alpha:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'AlphaPowerSystem-MIB::dcPwrSysDischargeAmps'
Syntax
Integer32
Values & Constraints
Object Constraints
range: -1000000000-1000000000