MODBUS HR 40089: BIC & ATS Switch Position.
40089:00 BTS Position Inputs BTS Norm On
40089:01 BTS Position Inputs BTS Norm Off
40089:02 BTS Position Inputs BTS Emer On
40089:03 BTS Position Inputs BTS Emer Off
40089:04 ATS Position Inputs ATS Norm On
40089:05 ATS Position Inputs ATS Norm Off
40089:06 ATS Position Inputs ATS Emer On
40089:07 ATS Position Inputs ATS Emer Off
40089:08-15 Undefined