66
.1.3.6.1.4.1.5040.1.2.42.1.2
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebGraphThermoHygroSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermo-Hygrometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermo-Hygrometer-US-MIB::wtWebGraphThermoHygroSensorTable'
List of sensors.
List of sensor numbers.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermoHygroSensorNomandatory
Sensor number.
|
Integer32 Constraints: range: 1-2 |
.1.3.6.1.4.1.5040.1.2.42.1.2.1.1 |
.1.3.6.1.4.1.5040.1.2.42.1.3
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebGraphThermoHygroTempValueTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermo-Hygrometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermo-Hygrometer-US-MIB::wtWebGraphThermoHygroTempValueTable'
List of measurement values corresponding to the channel numbers.
Measurement values of the sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermoHygroTempValuemandatory
Measurement value of the sensor, ASCII, 5 characters in length.
|
OctetString Constraints: range: 5-5 |
.1.3.6.1.4.1.5040.1.2.42.1.3.1.1 |
.1.3.6.1.4.1.5040.1.2.42.1.4
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebGraphThermoHygroBinaryTempValueTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermo-Hygrometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermo-Hygrometer-US-MIB::wtWebGraphThermoHygroBinaryTempValueTable'
List of binary measurement values corresponding to the channel numbers.
Binary measurement values of the sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermoHygroBinaryTempValuemandatory
Binary measurement value of the sensor in 1/10 degrees Celsius or 1/10 per cent,
signed number, 0x4FFF6 indicates an invalid measured value. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.42.1.4.1.1 |
.1.3.6.1.4.1.5040.1.2.42.1.8
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebGraphThermoHygroTempValuePktTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermo-Hygrometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermo-Hygrometer-US-MIB::wtWebGraphThermoHygroTempValuePktTable'
List of measurement values corresponding to the channel numbers.
Measurement values of the sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermoHygroTempValuePktmandatory
Measurement value of the sensor, ASCII, 5 characters in length, delimeter is decimal point.
|
OctetString Constraints: range: 5-5 |
.1.3.6.1.4.1.5040.1.2.42.1.8.1.1 |
.1.3.6.1.4.1.5040.1.2.42.3.1.5.2
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebGraphThermoHygroAlarmIfTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermo-Hygrometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermo-Hygrometer-US-MIB::wtWebGraphThermoHygroAlarmIfTable'
List of alarm indices.
Numbers of the alarms.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermoHygroAlarmNomandatory
Alarm number.
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.5040.1.2.42.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.42.3.1.5.3
·
1 row entry
·
52 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebGraphThermoHygroAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermo-Hygrometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermo-Hygrometer-US-MIB::wtWebGraphThermoHygroAlarmTable'
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermoHygroAlarmTriggermandatory
Binary coded trigger conditions:
Octet 1: unused Octet 2: unused Octet 3: Bit 0: Timer Bit 1: ColdStart Bit 2: WarmStart Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2-7: unused |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.1 |
|
wtWebGraphThermoHygroAlarmMinmandatory
Minimum temperature in degrees with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.2 |
|
wtWebGraphThermoHygroAlarmMaxmandatory
Maximum temperature in degrees with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.3 |
|
wtWebGraphThermoHygroAlarmHysteresismandatory
Temperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.)
, in degrees with maximum 2 decimal places. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.4 |
|
wtWebGraphThermoHygroAlarmDelaymandatory
Alarm will be delayed by setting this time while stable alarm
condition occur (time in minutes). |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.5 |
|
wtWebGraphThermoHygroAlarmIntervalmandatory
Send interval for alarm messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.6 |
|
wtWebGraphThermoHygroAlarmEnablemandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: TCP Client enable |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.7 |
|
wtWebGraphThermoHygroAlarmEMailAddrmandatory
E-Mail address for sending the alarm mail to.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.8 |
|
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.9 |
|
wtWebGraphThermoHygroAlarmMailTextmandatory
Alarm mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.10 |
|
wtWebGraphThermoHygroAlarmManagerIPmandatory
Name or IP address of the SNMP Manager which accepts the trap.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.11 |
|
wtWebGraphThermoHygroAlarmTrapTextmandatory
This text is sent in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.12 |
|
Binary coded options:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Attach Thermo.csv Enable Bit 1 : CSV-Data_since_last_report Bit 2-7: unused |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.13 |
|
wtWebGraphThermoHygroAlarmTcpIpAddrmandatory
Name or IP address of the TCP server which accepts the trap.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.14 |
|
wtWebGraphThermoHygroAlarmTcpPortmandatory
Port number of the TCP server which accepts the trap.
|
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.15 |
|
wtWebGraphThermoHygroAlarmTcpTextmandatory
This text is sent in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.16 |
|
Subject line for alarm clear mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.17 |
|
Alarm clear mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.18 |
|
This text is sent in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.19 |
|
This text is sent in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.20 |
|
wtWebGraphThermoHygroAlarmDeltaTempmandatory
Maximum rate of change degrees/min with maximum 2 decimal places.
Compared with the average of a period of 5 minutes. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.21 |
|
wtWebGraphThermoHygroAlarmRHMinmandatory
Minimum rel. Humidity in percent with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.22 |
|
wtWebGraphThermoHygroAlarmRHMaxmandatory
Maximum rel.Humidity in percent with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.23 |
|
Hysterese rel. Humidity in percent with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.24 |
|
wtWebGraphThermoHygroAlarmAHMinmandatory
Minimum abs. Humidity in g/(m*m*m) with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.25 |
|
wtWebGraphThermoHygroAlarmAHMaxmandatory
Maximum abs. Humidity in g/(m*m*m) with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.26 |
|
IP address of the syslog server to which the Webio device should send syslog messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.27 |
|
wtWebGraphThermoHygroAlarmSyslogPortmandatory
Port number of the syslog server to which the Webio device should send syslog messages.
|
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.28 |
|
wtWebGraphThermoHygroAlarmSyslogTextmandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.29 |
|
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.30 |
|
Local data port: 1..65535 or AUTO: the next free port will be assigned.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.31 |
|
Name of the file including path informations.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.32 |
|
wtWebGraphThermoHygroAlarmFtpTextmandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.33 |
|
Alarm clear message to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.34 |
|
wtWebGraphThermoHygroAlarmFtpOptionmandatory
Binary coded options, select only one option at the same time:
STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.35 |
|
wtWebGraphThermoHygroAlarmTimerCronmandatory
This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Rang… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.36 |
|
wtWebGraphThermoHygroAlarmNamemandatory
Alert name
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.39 |
|
wtWebGraphThermoHygroAlarmActivemandatory
Alert active
1 = ON 0 = OFF |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.40 |
|
Binary coded options, select only one option at the same time:
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 1-7: unused Bit 0 : HHTP Request Authentication enable |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.61 |
|
HTTP Request: User
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.62 |
|
HTTP Request: Password
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.63 |
|
HTTP Request: Set URL
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.64 |
|
HTTP Request: Clear URL
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.65 |
|
HTTP Request: Server Port
|
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.66 |
|
MQTT Publish: Topic path
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.67 |
|
MQTT Publish: Topic SET message
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.68 |
|
MQTT Publish: Topic CLEAR message
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.69 |
|
Binary coded options:
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 2-7: unused Bit 1 : Sensor 1 Bit 0 : Sensor 0 |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.70 |
|
If window type is INSIDE the alarm is genereted when the temperature
is greater minumum value and lower than maximum value. If window type is OUTSIDE the alarm is generated when the measured value is lower than the mini… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.71 |
|
Port number of the SNMP Manager to which the Webio device should send SNMP traps.
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.76 |
|
wtWebGraphThermoHygroAlarmMqttQoSmandatory
Binary coded value:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: QoS 0 Bit 1: QoS 1 Bit 2: QoS 2 Bit 3-7:unused |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.77 |
|
wtWebGraphThermoHygroAlarmMqttRetainmandatory
Binary coded value:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : retain enable Bit 1-7 : unused |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.42.3.1.5.3.1.78 |
.1.3.6.1.4.1.5040.1.2.42.3.1.6.2.3
·
1 row entry
·
2 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebGraphThermoHygroSensorColorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermo-Hygrometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermo-Hygrometer-US-MIB::wtWebGraphThermoHygroSensorColorTable'
List of sensor colors for the praphical presentation.
Numbers of the sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
Color of the sensors at the praphical presention.
|
OctetStringr/w Constraints: range: 3-3 |
.1.3.6.1.4.1.5040.1.2.42.3.1.6.2.3.1.1 |
|
Assignes one of 4 scales to a sensor:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Use Scale 1 Bit 1 : Use Scale 2 Bit 2-7: unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.1.6.2.3.1.2 |
.1.3.6.1.4.1.5040.1.2.42.3.2.1
·
1 row entry
·
7 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebGraphThermoHygroPortTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermo-Hygrometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermo-Hygrometer-US-MIB::wtWebGraphThermoHygroPortTable'
List of settings depending on the sensor number.
Sensor parameters for the individual sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermoHygroPortNamemandatory
Name of the sensor.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.2.1.1.1 |
|
wtWebGraphThermoHygroPortTextmandatory
Description of the sensor.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.2.1.1.2 |
|
wtWebGraphThermoHygroPortOffset1mandatory
Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 1.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.2.1.1.3 |
|
Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.2.1.1.4 |
|
wtWebGraphThermoHygroPortOffset2mandatory
Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 2.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.2.1.1.5 |
|
Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.2.1.1.6 |
|
wtWebGraphThermoHygroPortCommentmandatory
Offset calibration: informations of date, name of operator, reference devices.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.42.3.2.1.1.7 |