WebGraph-OLD-Thermo-Hygro-Barometer-US-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
7
Rows
7
Columns
48
.1.3.6.1.4.1.5040.1.2.16.1.2
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebGraphThermoBaroSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-OLD-Thermo-Hygro-Barometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-OLD-Thermo-Hygro-Barometer-US-MIB::wtWebGraphThermoBaroSensorTable'
List of sensors.
List of sensor numbers.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermoBaroSensorNomandatory
Sensor number.
|
Integer32 Constraints: range: 1-2 |
.1.3.6.1.4.1.5040.1.2.16.1.2.1.1 |
.1.3.6.1.4.1.5040.1.2.16.1.3
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebGraphThermoBaroTempValueTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-OLD-Thermo-Hygro-Barometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-OLD-Thermo-Hygro-Barometer-US-MIB::wtWebGraphThermoBaroTempValueTable'
List of measurement values corresponding to the channel numbers.
Measurement values of the sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermoBaroTempValuemandatory
Measurement value of the sensor, ASCII, 5 characters in length.
|
OctetString Constraints: range: 5-5 |
.1.3.6.1.4.1.5040.1.2.16.1.3.1.1 |
.1.3.6.1.4.1.5040.1.2.16.1.4
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebGraphThermoBaroBinaryTempValueTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-OLD-Thermo-Hygro-Barometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-OLD-Thermo-Hygro-Barometer-US-MIB::wtWebGraphThermoBaroBinaryTempValueTable'
List of binary measurement values corresponding to the channel numbers.
Binary measurement values of the sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermoBaroBinaryTempValuemandatory
Binary measurement value of the sensor in 1/10 degrees Celsius or 1/10 per cent,
signed number, 0x4FFF6 indicates an invalid measured value. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.16.1.4.1.1 |
.1.3.6.1.4.1.5040.1.2.16.1.8
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebGraphThermoBaroTempValuePktTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-OLD-Thermo-Hygro-Barometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-OLD-Thermo-Hygro-Barometer-US-MIB::wtWebGraphThermoBaroTempValuePktTable'
List of measurement values corresponding to the channel numbers.
Measurement values of the sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermoBaroTempValuePktmandatory
Measurement value of the sensor, ASCII, 5 characters in length, delimeter is decimal point.
|
OctetString Constraints: range: 5-5 |
.1.3.6.1.4.1.5040.1.2.16.1.8.1.1 |
.1.3.6.1.4.1.5040.1.2.16.3.1.5.2
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebGraphThermoBaroAlarmIfTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-OLD-Thermo-Hygro-Barometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-OLD-Thermo-Hygro-Barometer-US-MIB::wtWebGraphThermoBaroAlarmIfTable'
List of alarm indices.
Numbers of the alarms.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermoBaroAlarmNomandatory
Alarm number.
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.5040.1.2.16.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.16.3.1.5.3
·
1 row entry
·
36 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebGraphThermoBaroAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-OLD-Thermo-Hygro-Barometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-OLD-Thermo-Hygro-Barometer-US-MIB::wtWebGraphThermoBaroAlarmTable'
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermoBaroAlarmTriggermandatory
Binary coded trigger conditions:
Octet 1: unused Octet 2: unused Octet 3: Bit 0: Timer Bit 1: ColdStart Bit 2: WarmStart Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2-7: unused |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.1 |
|
wtWebGraphThermoBaroAlarmMinmandatory
Minimum temperature in degrees with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.2 |
|
wtWebGraphThermoBaroAlarmMaxmandatory
Maximum temperature in degrees with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.3 |
|
wtWebGraphThermoBaroAlarmHysteresismandatory
Temperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.)
, in degrees with maximum 2 decimal places. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.4 |
|
wtWebGraphThermoBaroAlarmDelaymandatory
Alarm will be delayed by setting this time while stable alarm
condition occur (time in minutes). |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.5 |
|
wtWebGraphThermoBaroAlarmIntervalmandatory
Send interval for alarm messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.6 |
|
wtWebGraphThermoBaroAlarmEnablemandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: TCP Client enable |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.7 |
|
wtWebGraphThermoBaroAlarmEMailAddrmandatory
E-Mail address for sending the alarm mail to.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.8 |
|
wtWebGraphThermoBaroAlarmMailSubjectmandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.9 |
|
wtWebGraphThermoBaroAlarmMailTextmandatory
Alarm mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.10 |
|
wtWebGraphThermoBaroAlarmManagerIPmandatory
Name or IP address of the SNMP Manager which accepts the trap.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.11 |
|
wtWebGraphThermoBaroAlarmTrapTextmandatory
This text is sent in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.12 |
|
wtWebGraphThermoBaroAlarmMailOptionsmandatory
Binary coded options:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Attach Thermo.csv Enable Bit 1 : CSV-Data_since_last_report Bit 2-7: unused |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.13 |
|
wtWebGraphThermoBaroAlarmTcpIpAddrmandatory
Name or IP address of the TCP server which accepts the trap.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.14 |
|
wtWebGraphThermoBaroAlarmTcpPortmandatory
Port number of the TCP server which accepts the trap.
|
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.15 |
|
wtWebGraphThermoBaroAlarmTcpTextmandatory
This text is sent in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.16 |
|
Subject line for alarm clear mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.17 |
|
Alarm clear mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.18 |
|
This text is sent in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.19 |
|
This text is sent in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.20 |
|
wtWebGraphThermoBaroAlarmDeltaTempmandatory
Maximum rate of change degrees/min with maximum 2 decimal places.
Compared with the average of a period of 5 minutes. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.21 |
|
wtWebGraphThermoBaroAlarmRHMinmandatory
Minimum rel. Humidity in percent with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.22 |
|
wtWebGraphThermoBaroAlarmRHMaxmandatory
Maximum rel.Humidity in percent with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.23 |
|
Hysterese rel. Humidity in percent with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.24 |
|
wtWebGraphThermoBaroAlarmAHMinmandatory
Minimum abs. Humidity in g/(m*m*m) with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.25 |
|
wtWebGraphThermoBaroAlarmAHMaxmandatory
Maximum abs. Humidity in g/(m*m*m) with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.26 |
|
IP address of the syslog server to which the Webio device should send syslog messages.
|
RFC1155-SMIIpAddressr/w Type Constraints: range: 4 |
.1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.27 |
|
wtWebGraphThermoBaroAlarmSyslogPortmandatory
Port number of the syslog server to which the Webio device should send syslog messages.
|
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.28 |
|
wtWebGraphThermoBaroAlarmSyslogTextmandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.29 |
|
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.30 |
|
wtWebGraphThermoBaroAlarmFtpDataPortmandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.31 |
|
wtWebGraphThermoBaroAlarmFtpFileNamemandatory
Name of the file including path informations.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.32 |
|
wtWebGraphThermoBaroAlarmFtpTextmandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.33 |
|
Alarm clear message to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.34 |
|
wtWebGraphThermoBaroAlarmFtpOptionsmandatory
Binary coded options, select only one option at the same time:
STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.35 |
|
wtWebGraphThermoBaroAlarmTimerCronmandatory
This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Rang… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.1.5.3.1.36 |
.1.3.6.1.4.1.5040.1.2.16.3.2.1
·
1 row entry
·
7 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebGraphThermoBaroPortTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-OLD-Thermo-Hygro-Barometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-OLD-Thermo-Hygro-Barometer-US-MIB::wtWebGraphThermoBaroPortTable'
List of settings depending on the sensor number.
Sensor parameters for the individual sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermoBaroPortNamemandatory
Name of the sensor.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.2.1.1.1 |
|
wtWebGraphThermoBaroPortTextmandatory
Description of the sensor.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.2.1.1.2 |
|
wtWebGraphThermoBaroPortOffset1mandatory
Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 1.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.2.1.1.3 |
|
wtWebGraphThermoBaroPortTemperature1mandatory
Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.2.1.1.4 |
|
wtWebGraphThermoBaroPortOffset2mandatory
Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 2.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.2.1.1.5 |
|
wtWebGraphThermoBaroPortTemperature2mandatory
Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.2.1.1.6 |
|
wtWebGraphThermoBaroPortCommentmandatory
Offset calibration: informations of date, name of operator, reference devices.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.16.3.2.1.1.7 |