WARNING:The UPS is operating on battery power. This trap is
persistent and is resent at one minute intervals until
the UPS either turns off or is no longer running on
battery.
upsTrapBatteryLow
.1.3.6.1.4.1.4555.1.1.7.2.0.10
CRITICAL: The battery is near of the end of backup time.
upsTrapBatteryAlarm
.1.3.6.1.4.1.4555.1.1.7.2.0.11
WARNING: The battery is in alarm.
upsTrapUpsCriticalAlarm
.1.3.6.1.4.1.4555.1.1.7.2.0.12
CRITICAL: A critical alarm has been detected on the UPS.
upsTrapLoadOFF
.1.3.6.1.4.1.4555.1.1.7.2.0.13
CRITICAL: The load has been disconnected from the UPS. LOAD OFF.
upsTrapCommunicationLost
.1.3.6.1.4.1.4555.1.1.7.2.0.14
CRITICAL: UPS is no more communicating with the agent.
upsTrapOnBatteryPower
.1.3.6.1.4.1.4555.1.1.7.2.0.15
WARNING: The UPS has switched to battery backup power.
upsTrapBatteryTestfailed
.1.3.6.1.4.1.4555.1.1.7.2.0.16
WARNING: The Battery test has detected a weak battery.
upsTrapTemperatureAlarm
.1.3.6.1.4.1.4555.1.1.7.2.0.17
WARNING: The UPS internal temperature has reached the threshold.
upsTrapOnBypass
.1.3.6.1.4.1.4555.1.1.7.2.0.18
WARNING: Load supplied by automatic Bypass.
upsTrapUpsPreventiveAlarm
.1.3.6.1.4.1.4555.1.1.7.2.0.19
WARNING: A preventive alarm has been detected by the UPS.
upsTrapTestCompleted
.1.3.6.1.4.1.4555.1.1.7.2.0.2
INFORMATION:This trap is sent upon completion of a UPS diagnostic
test.
upsTrapShutdownWarning
.1.3.6.1.4.1.4555.1.1.7.2.0.20
WARNING: A warning message has be sent to shutdown agent.
upsTrapShutdownrequest
.1.3.6.1.4.1.4555.1.1.7.2.0.21
WARNING: A shutdown command has been sent to agent.
upsTrapUpsNormal
.1.3.6.1.4.1.4555.1.1.7.2.0.22
INFORMATION: The UPS status is normal. Load protected by UPS
upsTrapPowerRestored
.1.3.6.1.4.1.4555.1.1.7.2.0.23
INFORMATION: The Input supply has been restored
upsTrapAlarmCancelled
.1.3.6.1.4.1.4555.1.1.7.2.0.24
INFORMATION: Alarm cancelled. All alarms are disabled
upsTrapComEstablished
.1.3.6.1.4.1.4555.1.1.7.2.0.25
INFORMATION: The communication between UPS and the agent has been restored
upsTrapShutdwonCancelled
.1.3.6.1.4.1.4555.1.1.7.2.0.26
INFORMATION: The UPS has cancelled the shutdown procedure to agent
upsTrapAgentRestarting
.1.3.6.1.4.1.4555.1.1.7.2.0.27
INFORMATION: NET VISION is restarting
upsTrapEmdTempLow
.1.3.6.1.4.1.4555.1.1.7.2.0.28
CRITICAL: EMD Sensor detected low temperature.
upsTrapEmdTempNotLow
.1.3.6.1.4.1.4555.1.1.7.2.0.29
INFORMATION: EMD Sensor Not under low temperature.
upsTrapAlarmEntryAdded
.1.3.6.1.4.1.4555.1.1.7.2.0.3
WARNING:This trap is sent each time an alarm is inserted into
to the alarm table. It is sent on the insertion of
all alarms except for upsAlarmOnBattery and
upsAlarmTestInProgress.
upsTrapEmdTempHigh
.1.3.6.1.4.1.4555.1.1.7.2.0.30
CRITICAL: EMD Sensor detected high temperature.
upsTrapEmdTempNotHigh
.1.3.6.1.4.1.4555.1.1.7.2.0.31
INFORMATION: EMD Sensor Not over high temperature.
upsTrapEmdHumidityLow
.1.3.6.1.4.1.4555.1.1.7.2.0.32
CRITICAL: EMD Sensor detected low humidity.
upsTrapEmdHumidityNotLow
.1.3.6.1.4.1.4555.1.1.7.2.0.33
INFORMATION: EMD Sensor Not under low humidity.
upsTrapEmdHumidityHigh
.1.3.6.1.4.1.4555.1.1.7.2.0.34
CRITICAL: EMD Sensor detected high humidity.
upsTrapEmdHumidityNotHigh
.1.3.6.1.4.1.4555.1.1.7.2.0.35
INFORMATION: EMD Sensor Not over high humidity.
upsTrapEmdFirstInputActive
.1.3.6.1.4.1.4555.1.1.7.2.0.36
CRITICAL: The input is active.
upsTrapEmdFirstInputRestored
.1.3.6.1.4.1.4555.1.1.7.2.0.37
INFORMATION: The input is restored.
upsTrapEmdSecondInputActive
.1.3.6.1.4.1.4555.1.1.7.2.0.38
CRITICAL: The input is active.
upsTrapEmdSecondInputRestored
.1.3.6.1.4.1.4555.1.1.7.2.0.39
INFORMATION: The input is restored.
upsTrapAlarmEntryRemoved
.1.3.6.1.4.1.4555.1.1.7.2.0.4
INFORMATION:This trap is sent each time an alarm is removed from
the alarm table. It is sent on the removal of all
alarms except for upsAlarmTestInProgress.
upsTrapSessionLogin
.1.3.6.1.4.1.4555.1.1.7.2.0.40
INFORMATION: New Admin or User session opened.
upsTrapLoginUnsuccesfulTentative
.1.3.6.1.4.1.4555.1.1.7.2.0.41
WARNING: Admin or User account locked.
upsTrapTest
.1.3.6.1.4.1.4555.1.1.7.2.0.42
INFORMATION: Send test trap.
upsTrapImminentStop
.1.3.6.1.4.1.4555.1.1.7.2.0.5
CRITICAL: The UPS is near to switch off the output power.
upsTrapOverload
.1.3.6.1.4.1.4555.1.1.7.2.0.6
WARNING: The UPS output is in overload. Output load rate more than 100%
upsTrapRedundancyLost
.1.3.6.1.4.1.4555.1.1.7.2.0.7
WARNING: Redundancy is lost.
upsTrapBatteryCircuitOpen
.1.3.6.1.4.1.4555.1.1.7.2.0.8
CRITICAL: The battery has been disconnected from UPS
upsTrapBatteryDischarged
.1.3.6.1.4.1.4555.1.1.7.2.0.9
CRITICAL: The battery has been detected as discharged.