.1.3.6.1.4.1.4555.1.1.7.1.3.3
·
1 row entry
·
5 columns
Uses the socomec variant from
Command help
/opt/observium/mibs/socomec.
Walk upsInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SOCOMECUPS7-MIB' -M '/opt/observium/mibs/socomec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SOCOMECUPS7-MIB::upsInputTable'
A list of input table entries. The number of entries is given by the value of upsInputNumLines.
An entry containing information applicable to a
particular input line.
particular input line.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
upsInputLineIndexmandatory | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.3.3.1.1 |
upsInputVoltagemandatory The input utility line voltage in 0.1 volts. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4555.1.1.7.1.3.3.1.2 |
upsInputCurrentmandatory The magnitude of the present input current in 0.1 A. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4555.1.1.7.1.3.3.1.3 |
upsInputVoltageMaxmandatory The maximum utility line voltage in 0.1 VAC for last 1 minute. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4555.1.1.7.1.3.3.1.4 |
upsInputVoltageMinmandatory The minimum utility line voltage in 0.1 VAC for last 1 minute. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4555.1.1.7.1.3.3.1.5 |
.1.3.6.1.4.1.4555.1.1.7.1.4.4
·
1 row entry
·
6 columns
Uses the socomec variant from
Command help
/opt/observium/mibs/socomec.
Walk upsOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SOCOMECUPS7-MIB' -M '/opt/observium/mibs/socomec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SOCOMECUPS7-MIB::upsOutputTable'
A list of output table entries. The number of entries is given by the value of upsOutputNumLines.
An entry containing information applicable to a
particular output line.
particular output line.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
upsOutputLineIndexmandatory The output line identifier. | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.4.4.1.1 |
upsOutputVoltagemandatory The output voltage of the UPS system in 0.1 volts. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4555.1.1.7.1.4.4.1.2 |
upsOutputCurrentmandatory The output current of the UPS system in 0.1 Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4555.1.1.7.1.4.4.1.3 |
upsOutputPercentLoadmandatory The percentage of the UPS power capacity presentlybeing used on this output line | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4555.1.1.7.1.4.4.1.4 |
upsOutputKvamandatory Output apparent power of the UPS in 0.1 kVA. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4555.1.1.7.1.4.4.1.5 |
upsOutputKwmandatory Output apparent power of the UPS in 0.1 kW. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4555.1.1.7.1.4.4.1.6 |
.1.3.6.1.4.1.4555.1.1.7.1.5.3
·
1 row entry
·
3 columns
Uses the socomec variant from
Command help
/opt/observium/mibs/socomec.
Walk upsBypassTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SOCOMECUPS7-MIB' -M '/opt/observium/mibs/socomec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SOCOMECUPS7-MIB::upsBypassTable'
A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.
An entry containing information applicable to a
particular bypass input.
particular bypass input.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
upsBypassLineIndexmandatory The bypass line identifier. | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.5.3.1.1 |
upsBypassVoltagemandatory The present bypass voltage of the UPS system in 0.1 volts. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4555.1.1.7.1.5.3.1.2 |
upsBypassCurrentmandatory The present bypass current of the UPS system in 0.1 Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4555.1.1.7.1.5.3.1.3 |
.1.3.6.1.4.1.4555.1.1.7.1.6.2
·
1 row entry
·
4 columns
Uses the socomec variant from
Command help
/opt/observium/mibs/socomec.
Walk upsAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SOCOMECUPS7-MIB' -M '/opt/observium/mibs/socomec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SOCOMECUPS7-MIB::upsAlarmTable'
A list of alarm table entries. The table contains
zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect. The table
is initially empty at agent startup. The agent
creates a row in the table each time a condition is
detected and deletes that row when that condition no
longer pertains. The agent creates the first row with
upsAlarmId equal to 1, and increments the value of
upsAlarmId each time a new row is created, wrapping to
the first free value greater than or equal to 1 when
the maximum value of upsAlarmId would otherwise be
exceeded. Consequently, after multiple operations,
the table may become sparse, e.g., containing entries
for rows 95, 100, 101, and 203 and the entries should
not be assumed to be in chronological order because
upsAlarmId might have wrapped.
Alarms are named by an OBJECT IDENTIFIER,
upsAlarmDescr, to allow a single table to
reflect well known alarms plus alarms defined by a
particular implementation, i.e., as documented in the
private enterprise MIB definition for the device. No
two rows will have the same value of upsAlarmDescr,
since alarms define conditions. In order to meet this
requirement, care should be taken in the definition of
alarm conditions to insure that a system cannot enter
the same condition multiple times simultaneously.
The number of rows in the table at any given time is
reflected by the value of upsAlarmsPresent.
An entry containing information applicable to a
particular alarm.
particular alarm.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
upsAlarmIdmandatory A unique identifier for an alarm condition. Thisvalue must remain constant. | PositiveInteger Type Constraints: range: 1..2147483647 | .1.3.6.1.4.1.4555.1.1.7.1.6.2.1.1 |
upsAlarmDescrmandatory A reference to an alarm description object. Theobject referenced should not be accessible, but rather be used to provide a unique description of the alarm condition. | SNMPv2-TCAutonomousType Description: Represents an independently extensible type identification value. It may, for example, indicate a particular sub-tree with further MIB definitions, or define a particular type of protocol or hardware. | .1.3.6.1.4.1.4555.1.1.7.1.6.2.1.2 |
upsAlarmTimemandatory The value of sysUpTime when the alarm condition wasdetected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0. | SNMPv2-TCTimeStamp Based On: SNMPv2-SMITimeTicks Description: The value of the sysUpTime object at which a specific occurrence happened. The specific occurrence must be defined in the description of any object defined using this type. If sysUpTime is reset t… | .1.3.6.1.4.1.4555.1.1.7.1.6.2.1.3 |
upsAlarmExtDesmandatory Extra description. | SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… | .1.3.6.1.4.1.4555.1.1.7.1.6.2.1.4 |
.1.3.6.1.4.1.4555.1.1.7.1.7.4
·
1 row entry
·
5 columns
Uses the socomec variant from
Command help
/opt/observium/mibs/socomec.
Walk upsControlShutdownParamTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SOCOMECUPS7-MIB' -M '/opt/observium/mibs/socomec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SOCOMECUPS7-MIB::upsControlShutdownParamTable'
Table which describes the parameters for shutdown process when shutdown event occurs
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
upsControlEventIndexmandatory The shutdown event identification | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.7.4.1.1 |
upsControlEventStatusmandatory Status of the corresponding shutdown Event.When set to disable(), shutdown process will not start when corresponding event occurred. | Enumerationr/w | .1.3.6.1.4.1.4555.1.1.7.1.7.4.1.2 |
upsControlDelaymandatory The Delay after the occurrence of the corresponding shutdownevent that Net Vision should issue shutdown request to connected clients. For WeeklyScheduledShutdown and SpecialScheduledShutdown, this is the time before th… | Integer32r/w | .1.3.6.1.4.1.4555.1.1.7.1.7.4.1.3 |
upsControlFirstWarningmandatory The delay after the occurrence of the corresponding shutdownevent that the Net Vision will start sending the warning message to the connected clients. The value is in units of seconds | Integer32r/w | .1.3.6.1.4.1.4555.1.1.7.1.7.4.1.4 |
upsControlWarningIntervalmandatory The frequency of sending warning messages to the connectedclients when the corresponding shutdown event occurs. The value is in units of seconds. | Integer32r/w | .1.3.6.1.4.1.4555.1.1.7.1.7.4.1.5 |
.1.3.6.1.4.1.4555.1.1.7.1.7.5
·
1 row entry
·
5 columns
Uses the socomec variant from
Command help
/opt/observium/mibs/socomec.
Walk upsControlWeeklyScheduleTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SOCOMECUPS7-MIB' -M '/opt/observium/mibs/socomec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SOCOMECUPS7-MIB::upsControlWeeklyScheduleTable'
The table to schedule shutting down the ups by weekly.
The entries for each day.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
upsControlWeeklyIndexmandatory The index of scheduled events. | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.7.5.1.1 |
upsControlWeeklyShutdownDaymandatory The weekday on which the UPS should shut down. | Enumerationr/w | .1.3.6.1.4.1.4555.1.1.7.1.7.5.1.2 |
upsControlWeeklyShutdownTimemandatory The time that the process of shutting down the UPS will be initiatedin hh:mm format. | OctetStringr/w | .1.3.6.1.4.1.4555.1.1.7.1.7.5.1.3 |
upsControlWeeklyRestartDaymandatory The weekday on which the UPS should restart | Enumerationr/w | .1.3.6.1.4.1.4555.1.1.7.1.7.5.1.4 |
upsControlWeeklyRestartTimemandatory The time the UPS will restart in hh:mm format. | OctetStringr/w | .1.3.6.1.4.1.4555.1.1.7.1.7.5.1.5 |
.1.3.6.1.4.1.4555.1.1.7.1.7.6
·
1 row entry
·
5 columns
Uses the socomec variant from
Command help
/opt/observium/mibs/socomec.
Walk upsControlSpecialScheduleTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SOCOMECUPS7-MIB' -M '/opt/observium/mibs/socomec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SOCOMECUPS7-MIB::upsControlSpecialScheduleTable'
The table to schedule shutting down the ups.
The entries for each day.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
upsControlSpecialIndexmandatory The index of scheduled events. | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.7.6.1.1 |
upsControlSpecialShutdownDaymandatory The date on which the UPS should shut down in dd/mm/yyyyformat. | OctetStringr/w | .1.3.6.1.4.1.4555.1.1.7.1.7.6.1.2 |
upsControlSpecialShutdownTimemandatory The time that the process of shutting down the UPS will be initiatedin hh:mm format | OctetStringr/w | .1.3.6.1.4.1.4555.1.1.7.1.7.6.1.3 |
upsControlSpecialRestartDaymandatory The date on which the UPS should restart in dd/mm/yyyy format | OctetStringr/w | .1.3.6.1.4.1.4555.1.1.7.1.7.6.1.4 |
upsControlSpecialRestartTimemandatory The time the UPS will restart in hh:mm format. | OctetStringr/w | .1.3.6.1.4.1.4555.1.1.7.1.7.6.1.5 |
.1.3.6.1.4.1.4555.1.1.7.1.7.7
·
1 row entry
·
5 columns
Uses the socomec variant from
Command help
/opt/observium/mibs/socomec.
Walk upsControlEcoModeScheduleTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SOCOMECUPS7-MIB' -M '/opt/observium/mibs/socomec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SOCOMECUPS7-MIB::upsControlEcoModeScheduleTable'
The table to schedule enable/disable ups eco/mode by weekly.
The entries for each day.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
upsControlEcoModeIndexmandatory The index of scheduled events. | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.7.7.1.1 |
upsControlEcoModeStartDaymandatory The weekday on which the UPS Eco/Mode should enable. | Enumerationr/w | .1.3.6.1.4.1.4555.1.1.7.1.7.7.1.2 |
upsControlEcoModeStartTimemandatory The time that the UPS Eco/Mode will be enabled, in hh:mm format. | OctetStringr/w | .1.3.6.1.4.1.4555.1.1.7.1.7.7.1.3 |
upsControlEcoModeEndDaymandatory The weekday on which the UPS Eco/Mode should disable | Enumerationr/w | .1.3.6.1.4.1.4555.1.1.7.1.7.7.1.4 |
upsControlEcoModeEndTimemandatory The time the UPS Eco/Mode will disabled, in hh:mm format. | OctetStringr/w | .1.3.6.1.4.1.4555.1.1.7.1.7.7.1.5 |
.1.3.6.1.4.1.4555.1.1.7.1.8.5
·
1 row entry
·
6 columns
Uses the socomec variant from
Command help
/opt/observium/mibs/socomec.
Walk upsDevicesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SOCOMECUPS7-MIB' -M '/opt/observium/mibs/socomec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SOCOMECUPS7-MIB::upsDevicesTable'
The devices powered by UPS and registered to NET VISION
The devices protected by NET VISION
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
indexOfDevicemandatory The index of the device that is powered from UPS. | NonNegativeInteger Type Constraints: range: 1..2147483647 | .1.3.6.1.4.1.4555.1.1.7.1.8.5.1.1 |
addrOfDevicemandatory The ip address of the device. | OctetString | .1.3.6.1.4.1.4555.1.1.7.1.8.5.1.2 |
nameOfDevicemandatory The name/description of the device powered from UPS. | OctetString | .1.3.6.1.4.1.4555.1.1.7.1.8.5.1.3 |
timeOfConnectionmandatory The device registered to NET VISION | SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… | .1.3.6.1.4.1.4555.1.1.7.1.8.5.1.4 |
statusOfConnectionmandatory The device status connection | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4555.1.1.7.1.8.5.1.5 |
severityOfConnectionmandatory The device severity | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4555.1.1.7.1.8.5.1.6 |
.1.3.6.1.4.1.4555.1.1.7.1.9.21
·
1 row entry
·
4 columns
Uses the socomec variant from
Command help
/opt/observium/mibs/socomec.
Walk upsAgentTrapsReceiversTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SOCOMECUPS7-MIB' -M '/opt/observium/mibs/socomec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SOCOMECUPS7-MIB::upsAgentTrapsReceiversTable'
A list of managers to send traps to. The number of entries is given by the value of upsAgentNumTrapReceivers
The managers to send traps to.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
trapsIndexmandatory The index to a trap receiver entry. | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.9.21.1.1 |
trapsReceiverAddrmandatory The IP address of the manager to send a trap to. | SNMPv2-TCDisplayStringr/w Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… | .1.3.6.1.4.1.4555.1.1.7.1.9.21.1.2 |
receiverCommunityStringmandatory The community name to use in the trap when sent to the manager. | OctetStringr/w | .1.3.6.1.4.1.4555.1.1.7.1.9.21.1.3 |
receiverNmstypemandatory The trap group that NMS desired. | Enumerationr/w | .1.3.6.1.4.1.4555.1.1.7.1.9.21.1.4 |
.1.3.6.1.4.1.4555.1.1.7.1.9.22
·
1 row entry
·
4 columns
Uses the socomec variant from
Command help
/opt/observium/mibs/socomec.
Walk upsAgentFirewallControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SOCOMECUPS7-MIB' -M '/opt/observium/mibs/socomec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SOCOMECUPS7-MIB::upsAgentFirewallControlTable'
A list of managers which can access Net Vision with private community string.
The managers.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
firewallIndexmandatory The index to a firewall entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4555.1.1.7.1.9.22.1.1 |
firewallControlAddrmandatory The IP address of the firewall | SNMPv2-TCDisplayStringr/w Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… | .1.3.6.1.4.1.4555.1.1.7.1.9.22.1.2 |
firewallPrefixLengthmandatory The firewall prefix length. | Integer32r/w | .1.3.6.1.4.1.4555.1.1.7.1.9.22.1.3 |
firewallActionModemandatory The firewall action mode | Enumerationr/w | .1.3.6.1.4.1.4555.1.1.7.1.9.22.1.4 |