upsInputTable

table mandatory
.1.3.6.1.4.1.4555.1.1.7.1.3.3 · 1 row entry · 5 columns
Uses the socomec variant from /opt/observium/mibs/socomec.
Command help
Walk upsInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SOCOMECUPS7-MIB' -M '/opt/observium/mibs/socomec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SOCOMECUPS7-MIB::upsInputTable'
A list of input table entries.  The number of entries
is given by the value of upsInputNumLines.
upsInputEntry row .1.3.6.1.4.1.4555.1.1.7.1.3.3.1
An entry containing information applicable to a
particular input line.
Indexes
No indexes recorded
Column Syntax OID
Integer32 .1.3.6.1.4.1.4555.1.1.7.1.3.3.1.1
The input utility line voltage in 0.1 volts.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.4555.1.1.7.1.3.3.1.2
The magnitude of the present input current in 0.1 A.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.4555.1.1.7.1.3.3.1.3
The maximum utility line voltage in 0.1 VAC for last 1 minute.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.4555.1.1.7.1.3.3.1.4
The minimum utility line voltage in 0.1 VAC for last 1 minute.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.4555.1.1.7.1.3.3.1.5

upsOutputTable

table mandatory
.1.3.6.1.4.1.4555.1.1.7.1.4.4 · 1 row entry · 6 columns
Uses the socomec variant from /opt/observium/mibs/socomec.
Command help
Walk upsOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SOCOMECUPS7-MIB' -M '/opt/observium/mibs/socomec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SOCOMECUPS7-MIB::upsOutputTable'
A list of output table entries.  The number of
entries is given by the value of upsOutputNumLines.
upsOutputEntry row .1.3.6.1.4.1.4555.1.1.7.1.4.4.1
An entry containing information applicable to a
particular output line.
Indexes
No indexes recorded
Column Syntax OID
The output line identifier.
Integer32 .1.3.6.1.4.1.4555.1.1.7.1.4.4.1.1
The output voltage of the UPS system in 0.1 volts.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.4555.1.1.7.1.4.4.1.2
The output current of the UPS system in 0.1 Amps.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.4555.1.1.7.1.4.4.1.3
The percentage of the UPS power capacity presently
being used on this output line
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.4555.1.1.7.1.4.4.1.4
upsOutputKvamandatory
Output apparent power of the UPS in 0.1 kVA.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.4555.1.1.7.1.4.4.1.5
upsOutputKwmandatory
Output apparent power of the UPS in 0.1 kW.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.4555.1.1.7.1.4.4.1.6

upsBypassTable

table mandatory
.1.3.6.1.4.1.4555.1.1.7.1.5.3 · 1 row entry · 3 columns
Uses the socomec variant from /opt/observium/mibs/socomec.
Command help
Walk upsBypassTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SOCOMECUPS7-MIB' -M '/opt/observium/mibs/socomec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SOCOMECUPS7-MIB::upsBypassTable'
A list of bypass table entries.  The number of
entries is given by the value of upsBypassNumLines.
upsBypassEntry row .1.3.6.1.4.1.4555.1.1.7.1.5.3.1
An entry containing information applicable to a
particular bypass input.
Indexes
No indexes recorded
Column Syntax OID
The bypass line identifier.
Integer32 .1.3.6.1.4.1.4555.1.1.7.1.5.3.1.1
The present bypass voltage of the UPS system in 0.1 volts.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.4555.1.1.7.1.5.3.1.2
The present bypass current of the UPS system in 0.1 Amps.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.4555.1.1.7.1.5.3.1.3

upsAlarmTable

table mandatory
.1.3.6.1.4.1.4555.1.1.7.1.6.2 · 1 row entry · 4 columns
Uses the socomec variant from /opt/observium/mibs/socomec.
Command help
Walk upsAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SOCOMECUPS7-MIB' -M '/opt/observium/mibs/socomec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SOCOMECUPS7-MIB::upsAlarmTable'
A list of alarm table entries.  The table contains
zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect.  The table
is initially empty at agent startup.  The agent
creates a row in the table each time a condition is
detected and deletes that row when that condition no
longer pertains.  The agent creates the first row with
upsAlarmId equal to 1, and increments the value of
upsAlarmId each time a new row is created, wrapping to
the first free value greater than or equal to 1 when
the maximum value of upsAlarmId would otherwise be
exceeded.  Consequently, after multiple operations,
the table may become sparse, e.g., containing entries
for rows 95, 100, 101, and 203 and the entries should
not be assumed to be in chronological order because
upsAlarmId might have wrapped.
          
Alarms are named by an OBJECT IDENTIFIER,
upsAlarmDescr, to allow a single table to
reflect well known alarms plus alarms defined by a
particular implementation, i.e., as documented in the
private enterprise MIB definition for the device.  No
two rows will have the same value of upsAlarmDescr,
since alarms define conditions.  In order to meet this
requirement, care should be taken in the definition of
alarm conditions to insure that a system cannot enter
the same condition multiple times simultaneously.
          
The number of rows in the table at any given time is
reflected by the value of upsAlarmsPresent.
upsAlarmEntry row .1.3.6.1.4.1.4555.1.1.7.1.6.2.1
An entry containing information applicable to a
particular alarm.
Indexes
No indexes recorded
Column Syntax OID
upsAlarmIdmandatory
A unique identifier for an alarm condition. This
value must remain constant.
PositiveInteger
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.4555.1.1.7.1.6.2.1.1
upsAlarmDescrmandatory
A reference to an alarm description object. The
object referenced should not be accessible, but rather
be used to provide a unique description of the alarm
condition.
SNMPv2-TCAutonomousType
Description:
Represents an independently extensible type identification
value. It may, for example, indicate a particular sub-tree
with further MIB definitions, or define a particular type of
protocol or hardware.
.1.3.6.1.4.1.4555.1.1.7.1.6.2.1.2
upsAlarmTimemandatory
The value of sysUpTime when the alarm condition was
detected. If the alarm condition was detected at the
time of agent startup and presumably existed before
agent startup, the value of upsAlarmTime shall equal
0.
SNMPv2-TCTimeStamp
Based On: SNMPv2-SMITimeTicks
Description:
The value of the sysUpTime object at which a specific
occurrence happened. The specific occurrence must be

defined in the description of any object defined using this
type.

If sysUpTime is reset t…
.1.3.6.1.4.1.4555.1.1.7.1.6.2.1.3
Extra description.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.4555.1.1.7.1.6.2.1.4
.1.3.6.1.4.1.4555.1.1.7.1.7.4 · 1 row entry · 5 columns
Uses the socomec variant from /opt/observium/mibs/socomec.
Command help
Walk upsControlShutdownParamTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SOCOMECUPS7-MIB' -M '/opt/observium/mibs/socomec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SOCOMECUPS7-MIB::upsControlShutdownParamTable'
Table which describes the parameters for shutdown process
when shutdown event occurs
shutdownParamEntry row .1.3.6.1.4.1.4555.1.1.7.1.7.4.1
Indexes
No indexes recorded
Column Syntax OID
The shutdown event identification
Integer32 .1.3.6.1.4.1.4555.1.1.7.1.7.4.1.1
Status of the corresponding shutdown Event.
When set to disable(), shutdown process will not start when
corresponding event occurred.
Enumerationr/w .1.3.6.1.4.1.4555.1.1.7.1.7.4.1.2
The Delay after the occurrence of the corresponding shutdown
event that Net Vision should issue shutdown request to
connected clients. For WeeklyScheduledShutdown and
SpecialScheduledShutdown, this is the time before th…
Integer32r/w .1.3.6.1.4.1.4555.1.1.7.1.7.4.1.3
The delay after the occurrence of the corresponding shutdown
event that the Net Vision will start sending the warning
message to the connected clients. The value is in units of
seconds
Integer32r/w .1.3.6.1.4.1.4555.1.1.7.1.7.4.1.4
The frequency of sending warning messages to the connected
clients when the corresponding shutdown event occurs.
The value is in units of seconds.
Integer32r/w .1.3.6.1.4.1.4555.1.1.7.1.7.4.1.5
.1.3.6.1.4.1.4555.1.1.7.1.7.5 · 1 row entry · 5 columns
Uses the socomec variant from /opt/observium/mibs/socomec.
Command help
Walk upsControlWeeklyScheduleTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SOCOMECUPS7-MIB' -M '/opt/observium/mibs/socomec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SOCOMECUPS7-MIB::upsControlWeeklyScheduleTable'
The table to schedule shutting down the ups by weekly.
upsControlWeeklyScheduleEntry row .1.3.6.1.4.1.4555.1.1.7.1.7.5.1
The entries for each day.
Indexes
No indexes recorded
Column Syntax OID
The index of scheduled events.
Integer32 .1.3.6.1.4.1.4555.1.1.7.1.7.5.1.1
The weekday on which the UPS should shut down.
Enumerationr/w .1.3.6.1.4.1.4555.1.1.7.1.7.5.1.2
The time that the process of shutting down the UPS will be initiated
in hh:mm format.
OctetStringr/w .1.3.6.1.4.1.4555.1.1.7.1.7.5.1.3
The weekday on which the UPS should restart
Enumerationr/w .1.3.6.1.4.1.4555.1.1.7.1.7.5.1.4
The time the UPS will restart in hh:mm format.
OctetStringr/w .1.3.6.1.4.1.4555.1.1.7.1.7.5.1.5
.1.3.6.1.4.1.4555.1.1.7.1.7.6 · 1 row entry · 5 columns
Uses the socomec variant from /opt/observium/mibs/socomec.
Command help
Walk upsControlSpecialScheduleTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SOCOMECUPS7-MIB' -M '/opt/observium/mibs/socomec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SOCOMECUPS7-MIB::upsControlSpecialScheduleTable'
The table to schedule shutting down the ups.
upsControlSpecialScheduleEntry row .1.3.6.1.4.1.4555.1.1.7.1.7.6.1
The entries for each day.
Indexes
No indexes recorded
Column Syntax OID
The index of scheduled events.
Integer32 .1.3.6.1.4.1.4555.1.1.7.1.7.6.1.1
The date on which the UPS should shut down in dd/mm/yyyy
format.
OctetStringr/w .1.3.6.1.4.1.4555.1.1.7.1.7.6.1.2
The time that the process of shutting down the UPS will be initiated
in hh:mm format
OctetStringr/w .1.3.6.1.4.1.4555.1.1.7.1.7.6.1.3
The date on which the UPS should restart in dd/mm/yyyy format
OctetStringr/w .1.3.6.1.4.1.4555.1.1.7.1.7.6.1.4
The time the UPS will restart in hh:mm format.
OctetStringr/w .1.3.6.1.4.1.4555.1.1.7.1.7.6.1.5
.1.3.6.1.4.1.4555.1.1.7.1.7.7 · 1 row entry · 5 columns
Uses the socomec variant from /opt/observium/mibs/socomec.
Command help
Walk upsControlEcoModeScheduleTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SOCOMECUPS7-MIB' -M '/opt/observium/mibs/socomec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SOCOMECUPS7-MIB::upsControlEcoModeScheduleTable'
The table to schedule enable/disable ups eco/mode by weekly.
upsControlEcoModeScheduleEntry row .1.3.6.1.4.1.4555.1.1.7.1.7.7.1
The entries for each day.
Indexes
No indexes recorded
Column Syntax OID
The index of scheduled events.
Integer32 .1.3.6.1.4.1.4555.1.1.7.1.7.7.1.1
The weekday on which the UPS Eco/Mode should enable.
Enumerationr/w .1.3.6.1.4.1.4555.1.1.7.1.7.7.1.2
The time that the UPS Eco/Mode will be enabled, in hh:mm format.
OctetStringr/w .1.3.6.1.4.1.4555.1.1.7.1.7.7.1.3
The weekday on which the UPS Eco/Mode should disable
Enumerationr/w .1.3.6.1.4.1.4555.1.1.7.1.7.7.1.4
The time the UPS Eco/Mode will disabled, in hh:mm format.
OctetStringr/w .1.3.6.1.4.1.4555.1.1.7.1.7.7.1.5

upsDevicesTable

table mandatory
.1.3.6.1.4.1.4555.1.1.7.1.8.5 · 1 row entry · 6 columns
Uses the socomec variant from /opt/observium/mibs/socomec.
Command help
Walk upsDevicesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SOCOMECUPS7-MIB' -M '/opt/observium/mibs/socomec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SOCOMECUPS7-MIB::upsDevicesTable'
The devices powered by UPS and registered to NET VISION
upsDevicesEntry row .1.3.6.1.4.1.4555.1.1.7.1.8.5.1
The devices protected by NET VISION
Indexes
No indexes recorded
Column Syntax OID
indexOfDevicemandatory
The index of the device that is powered from UPS.
NonNegativeInteger
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.4555.1.1.7.1.8.5.1.1
addrOfDevicemandatory
The ip address of the device.
OctetString .1.3.6.1.4.1.4555.1.1.7.1.8.5.1.2
nameOfDevicemandatory
The name/description of the device powered from UPS.
OctetString .1.3.6.1.4.1.4555.1.1.7.1.8.5.1.3
The device registered to NET VISION
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.4555.1.1.7.1.8.5.1.4
The device status connection
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.4555.1.1.7.1.8.5.1.5
The device severity
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.4555.1.1.7.1.8.5.1.6

upsAgentTrapsReceiversTable

table mandatory
.1.3.6.1.4.1.4555.1.1.7.1.9.21 · 1 row entry · 4 columns
Uses the socomec variant from /opt/observium/mibs/socomec.
Command help
Walk upsAgentTrapsReceiversTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SOCOMECUPS7-MIB' -M '/opt/observium/mibs/socomec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SOCOMECUPS7-MIB::upsAgentTrapsReceiversTable'
A list of managers to send traps to.  The number of
entries is given by the value of upsAgentNumTrapReceivers
upsAgentTrapsReceiversEntry row .1.3.6.1.4.1.4555.1.1.7.1.9.21.1
The managers to send traps to.
Indexes
No indexes recorded
Column Syntax OID
trapsIndexmandatory
The index to a trap receiver entry.
Integer32 .1.3.6.1.4.1.4555.1.1.7.1.9.21.1.1
The IP address of the manager to send a trap to.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.4555.1.1.7.1.9.21.1.2
The community name to use in the trap when sent to the manager.
OctetStringr/w .1.3.6.1.4.1.4555.1.1.7.1.9.21.1.3
The trap group that NMS desired.
Enumerationr/w .1.3.6.1.4.1.4555.1.1.7.1.9.21.1.4
.1.3.6.1.4.1.4555.1.1.7.1.9.22 · 1 row entry · 4 columns
Uses the socomec variant from /opt/observium/mibs/socomec.
Command help
Walk upsAgentFirewallControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SOCOMECUPS7-MIB' -M '/opt/observium/mibs/socomec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SOCOMECUPS7-MIB::upsAgentFirewallControlTable'
A list of managers which can access Net Vision with private
community string.
upsAgentFirewallControlEntry row .1.3.6.1.4.1.4555.1.1.7.1.9.22.1
The managers.
Indexes
No indexes recorded
Column Syntax OID
firewallIndexmandatory
The index to a firewall entry.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.4555.1.1.7.1.9.22.1.1
The IP address of the firewall
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.4555.1.1.7.1.9.22.1.2
The firewall prefix length.
Integer32r/w .1.3.6.1.4.1.4555.1.1.7.1.9.22.1.3
The firewall action mode
Enumerationr/w .1.3.6.1.4.1.4555.1.1.7.1.9.22.1.4