SCTE-HMS-GEN-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
1
Rows
1
Columns
29
.1.3.6.1.4.1.5591.1.6.2
·
1 row entry
·
29 columns
Uses the scte variant from
Command help
/opt/observium/mibs/scte.
Walk genDeviceTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCTE-HMS-GEN-MIB' -M '/opt/observium/mibs/scte:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCTE-HMS-GEN-MIB::genDeviceTable'
Table containing information about the individual generators being monitored
List of information about each generator being monitored.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
genDeviceAddressmandatory
Index into the psDeviceTable.
Address of Generator on the RS-485 Path |
Integer32 Constraints: range: 1-15 |
.1.3.6.1.4.1.5591.1.6.2.1.1 |
||||||||
|
genProtocolVersionmandatory
Version of the SCTE HMS protocol implemented in the monitored
equipment. The 'Protocol Version' implementation will comply with the defined protocol in the SCTE 25-3 (formerly HMS 022) document with the corresponding … |
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.5591.1.6.2.1.2 |
||||||||
|
genSoftwareVersionmandatory
The contents of this field are vendor specific. The intent
is to provide a text representation of the power supply or generator system software version. Any printable ASCII characters ca be included in this field. NULL… |
OctetString Constraints: range: 8-8 |
.1.3.6.1.4.1.5591.1.6.2.1.3 |
||||||||
|
genDeviceIdmandatory
The content of this field is vendor specific. The intent is
to provide manufacturer and/or product specific ASCII text information that will propagate to the manager's console verbatim. The following special characters… |
OctetString Constraints: range: 32-32 |
.1.3.6.1.4.1.5591.1.6.2.1.4 |
||||||||
|
genGasHazardOptionmandatory
Defines if gas hazard sensor is installed.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.6.2.1.5 |
||||||||
|
genWaterIntrusionOptionmandatory
Defines if water intrusion sensor is installed.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.6.2.1.6 |
||||||||
|
genPadShearOptionmandatory
Defines if pad shear sensor is installed.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.6.2.1.7 |
||||||||
|
genDoorOptionmandatory
Defines if separate generator door is installed.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.6.2.1.8 |
||||||||
|
genChargerOptionmandatory
Defines if charger fail signal is supported.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.6.2.1.9 |
||||||||
|
genFuelOptionmandatory
Defines if low fuel detection is supported.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.6.2.1.10 |
||||||||
|
genVBatIgnitionOptionmandatory
Defines if engine ignition battery voltage is monitored.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.6.2.1.11 |
||||||||
|
genTempOptionmandatory
Defines if engine enclosure temperature is monitored.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.6.2.1.12 |
||||||||
|
genGeneratorStatusmandatory
Defines the current state of generator operation.
1 = Off 2 = Running(test) 3 = Running 4 = Fail (A condition preventing the generator from functioning) This item requires entries in the discr… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.6.2.1.13 |
||||||||
|
genGasHazardmandatory
The concentration of hydrocarbon fuel in the
generator enclosure has exceeded safe limits. Generator operation is suspended. The alarm is cleared when the sensor is reset via the 'Reset Latched Generator Alarms' com… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.6.2.1.14 |
||||||||
|
genWaterIntrusionmandatory
Water level within the generator or fuel enclosure
has exceeded safe limits for generator operation. Generator operation is suspended while this alarm is active. The alarm is reset when the water returns to a safe leve… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.6.2.1.15 |
||||||||
|
genPadShearmandatory
Indicates that the generator or fuel enclosure
has shifted from its mounting position. Generator operation is suspended. The alarm is reset when the unit its returned to its original position. This item … |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.6.2.1.16 |
||||||||
|
genEnclosureDoormandatory
Indicates current status of the generator
and/or auxiliary fuel enclosure door. This item requires entries in the discrete property table. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.6.2.1.17 |
||||||||
|
genChargermandatory
Indicates if the ignition battery charger is operating.
This item requires entries in the discrete property table. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.6.2.1.18 |
||||||||
|
genFuelmandatory
Indicates if the engine's fuel supply is sufficient
for extended operation. Alarm is reset when fuel is replenished. This item requires entries in the discrete property table. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.6.2.1.19 |
||||||||
|
genVBatIgnitionmandatory
Scaled representation of the generator's
ignition battery in 1/100 Volts. This item requires an entry in the property table. |
Integer32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.5591.1.6.2.1.20 |
||||||||
|
genEnclosureTemperaturemandatory
Temperature inside generator's enclosure in degrees C.
This item requires an entry in the property table. |
Integer32 Constraints: range: -40-80 |
.1.3.6.1.4.1.5591.1.6.2.1.21 |
||||||||
|
genEquipmentControloptional
When written, the appropriate corresponding command action
is sent to the generator. 1 = End generator test 2 = Start generator test 3 = Reset latched generator alarms which may be preventing a generator… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.5591.1.6.2.1.22 |
||||||||
|
genOilOptionmandatory
Defines if oil pressure is monitored.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.6.2.1.23 |
||||||||
|
genMinorAlarmSupportmandatory
Defines if the minor alarm indicator is supported.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.6.2.1.24 |
||||||||
|
genMajorAlarmSupportmandatory
Defines if the major alarm indicator is supported.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.6.2.1.25 |
||||||||
|
genOiloptional
Indicates if the engine's oil is adequate for safe operation.
Alarm is reset when the condition returns to normal. This item requires entries in the discrete property table. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.6.2.1.26 |
||||||||
|
genMinorAlarmoptional
Indicates if the generator is indicating a minor alarm.
The generator requires attention, but does not require an immediate visit to the generator. This item requires entries in the discrete property tabl… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.6.2.1.27 |
||||||||
|
genMajorAlarmoptional
Indicates if the generator is indicating a major alarm.
The generator requires immediate attention, and should be visited immediately to remedy the situation. This item requires entries in the discrete pr… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.6.2.1.28 |
||||||||
|
genVendorOIDoptional
This object provides a means for a vendor to
point to a vendor specific extension of this MIB. |
ObjectIdentifier | .1.3.6.1.4.1.5591.1.6.2.1.29 |