SCHLEIFENBAUER-DATABUS-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
16
Rows
16
Columns
138
.1.3.6.1.4.1.31034.12.1.1.1.2.4 · 1 row entry · 5 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk sdbMgmtCtrlDevicesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-DATABUS-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-DATABUS-MIB::sdbMgmtCtrlDevicesTable'
A table containing information of devices connected to the databus.
The number of entries is given by the value of sdbMgmtStsDevices.
sdbMgmtCtrlDevicesEntry row .1.3.6.1.4.1.31034.12.1.1.1.2.4.1
Information entry containing objects of a particular databus device.
Column Syntax OID
A unique value for each device. Its value ranges between 1 and the
value of sdbMgmtStsDevices with a maximum of 255. The value for each
device will remain constant until the next scan is performed.
Integer32
Constraints:
range: 1-255
.1.3.6.1.4.1.31034.12.1.1.1.2.4.1.1
User defined address.
This will be used for addressing the device on the databus.
Integer32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.31034.12.1.1.1.2.4.1.2
Hardware serial number.
This cannot be changed. It can be used as backup unit address.
format as 3 unsigned ints separated by dashes: int - int - int
OctetString
Constraints:
range: 17-17
.1.3.6.1.4.1.31034.12.1.1.1.2.4.1.3
Indication if the device is new on the databus.
Enumeration
Enumerated Values:
0no
1yes
.1.3.6.1.4.1.31034.12.1.1.1.2.4.1.4
Indication if the device is conflicting with another device on the
databus.
Enumeration
Enumerated Values:
0no
1yes
.1.3.6.1.4.1.31034.12.1.1.1.2.4.1.5
.1.3.6.1.4.1.31034.12.1.1.2.1.1 · 1 row entry · 16 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk sdbDevIdTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-DATABUS-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-DATABUS-MIB::sdbDevIdTable'
A table containing identification information of devices connected to
the databus.
The number of entries is given by the value of
sdbMgmtStsAddressableDevices.
sdbDevIdEntry row .1.3.6.1.4.1.31034.12.1.1.2.1.1.1
Information entry containing information objects of a particular
databus device.
Indexes
Column Syntax OID
Data model version.
Integer32
Constraints:
range: 0-9999
.1.3.6.1.4.1.31034.12.1.1.2.1.1.1.1
The firmware revision number.
Integer32
Constraints:
range: 0-9999
.1.3.6.1.4.1.31034.12.1.1.2.1.1.1.2
Date and time the firmware was built.
OctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.31034.12.1.1.2.1.1.1.3
SP sales order number.
OctetString
Constraints:
range: 0-16
.1.3.6.1.4.1.31034.12.1.1.2.1.1.1.4
SP product id.
OctetString
Constraints:
range: 0-16
.1.3.6.1.4.1.31034.12.1.1.2.1.1.1.5
SP serial number.
OctetString
Constraints:
range: 0-16
.1.3.6.1.4.1.31034.12.1.1.2.1.1.1.6
Hardware serial number.
This can not be changed. It can be used as backup unit address.
Format as 3 unsigned ints separated by dashes (-)
e.g. 12345-54321-00000
OctetString
Constraints:
range: 17-17
.1.3.6.1.4.1.31034.12.1.1.2.1.1.1.7
The MAC address.
This can not be changed. It represents an 802 MAC address as if it
were transmitted least significant bit first.
Format as six groups of 2 hexadecimal digits separated by colons (:)
e.g. D0:22:12:B0:00:…
OctetString
Constraints:
range: 17-17
.1.3.6.1.4.1.31034.12.1.1.2.1.1.1.8
User defined address.
This will be used for addressing the device on the databus.
Integer32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.31034.12.1.1.2.1.1.1.9
User configurable device name or identifier.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.31034.12.1.1.2.1.1.1.10
User configurable device location identifier.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.31034.12.1.1.2.1.1.1.11
Characters to be displayed as vanity text in display.
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.31034.12.1.1.2.1.1.1.12
A unique value for each device. Its value represents the unit address
of the device and is used to address individual devices in the tree.
The value for each device will remain constant until the next scan is
performed.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.31034.12.1.1.2.1.1.1.13
A unique value for each device group.
Its value represents the device type of the device.
Refer to manual for more information.
Enumeration
Enumerated Values:
0pdu
1dpm
2hpdu-G3
3dpm27e
.1.3.6.1.4.1.31034.12.1.1.2.1.1.1.14
The LCD-backlight flashes in a heartbeat rhythm to locate the unit.
Enumerationr/w
Enumerated Values:
0off
1on
.1.3.6.1.4.1.31034.12.1.1.2.1.1.1.15
Wiring configuration type used.
Integer32
Constraints:
range: 0-256
.1.3.6.1.4.1.31034.12.1.1.2.1.1.1.16
.1.3.6.1.4.1.31034.12.1.1.2.2.1 · 1 row entry · 10 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk sdbDevCfTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-DATABUS-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-DATABUS-MIB::sdbDevCfTable'
A table containing configuration information of devices connected to
the databus.
The number of entries is given by the value of
sdbMgmtStsAddressableDevices.
sdbDevCfEntry row .1.3.6.1.4.1.31034.12.1.1.2.2.1.1
Configuration entry containing configuration objects of a particular
databus device.
Indexes
Column Syntax OID
Number of phases for input metering.
Integer32
Constraints:
range: 3-3
range: 0-1
.1.3.6.1.4.1.31034.12.1.1.2.2.1.1.1
Total number of outlets including hardwired without switch/metered
modules.
Integer32
Constraints:
range: 0-54
.1.3.6.1.4.1.31034.12.1.1.2.2.1.1.2
Number of switched outlets.
If outlet numbering is non-contiguous its the highest outlet number.
Integer32
Constraints:
range: 0-54
.1.3.6.1.4.1.31034.12.1.1.2.2.1.1.3
Number of metered outlets.
If outlet numbering is non-contiguous its the highest outlet number.
Integer32
Constraints:
range: 0-54
.1.3.6.1.4.1.31034.12.1.1.2.2.1.1.4
The number sensors.
Integer32
Constraints:
range: 0-16
.1.3.6.1.4.1.31034.12.1.1.2.2.1.1.5
Maximum rated load of device per phase
AInteger32
Constraints:
range: 32-32
range: 16-16
.1.3.6.1.4.1.31034.12.1.1.2.2.1.1.6
Number of branches for input metering.
Integer32
Constraints:
range: 0-6
.1.3.6.1.4.1.31034.12.1.1.2.2.1.1.7
Nuetral current measurement.
Integer32
Constraints:
range: 0-1
.1.3.6.1.4.1.31034.12.1.1.2.2.1.1.8
Number of temperature sensors present in the system.
Integer32
Constraints:
range: 0-16
.1.3.6.1.4.1.31034.12.1.1.2.2.1.1.9
The number of totals rows for the configuration.
Integer32
Constraints:
range: 0-16
.1.3.6.1.4.1.31034.12.1.1.2.2.1.1.10
.1.3.6.1.4.1.31034.12.1.1.2.3.1 · 1 row entry · 14 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk sdbDevSsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-DATABUS-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-DATABUS-MIB::sdbDevSsTable'
A table containing system status information of devices connected to
the databus.
The number of entries is given by the value of
sdbMgmtStsAddressableDevices.
sdbDevSsEntry row .1.3.6.1.4.1.31034.12.1.1.2.3.1.1
System status entry containing system status objects of a particular
databus device.
Indexes
Column Syntax OID
Returns an internal status or error code.
A value of 0 means OK.
If not 0 it can be any of the following codes. Multiple status codes
can be active at the same time. The value will be the sum of the
active status codes.…
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.31034.12.1.1.2.3.1.1.1
An alert has been raised due to temperature exceeding treshhold.
0 = no alert
1 = internal temperature sensor
2 = external temperature sensor
Integer32
Constraints:
range: 0-2
.1.3.6.1.4.1.31034.12.1.1.2.3.1.1.2
An alert has been raised due to current exceeding treshhold.
The value indicates the exceeding phase. 0 = no alert.
Integer32
Constraints:
range: 0-3
.1.3.6.1.4.1.31034.12.1.1.2.3.1.1.3
An alert has been raised due to current exceeding treshhold.
The value indicates the exceeding outlet. 0 = no alert.
Integer32
Constraints:
range: 0-54
.1.3.6.1.4.1.31034.12.1.1.2.3.1.1.4
An alert has been raised due to a voltage dip.
The value indicates the dipped phase. 0 = no alert.
Integer32
Constraints:
range: 0-3
.1.3.6.1.4.1.31034.12.1.1.2.3.1.1.5
An alert has been raised due to the current of a metered outlet
suddenly dropping to near zero, possibly indicating a blown fuse.
The value indicates the dropped outlet. 0 = no alert.
Integer32
Constraints:
range: 0-54
.1.3.6.1.4.1.31034.12.1.1.2.3.1.1.6
An alert has been raised due to the current of a metered input
suddenly dropping to near zero, possibly indicating a blown fuse.
The value indicates the dropped phase. 0 = no alert.
Integer32
Constraints:
range: 0-3
.1.3.6.1.4.1.31034.12.1.1.2.3.1.1.7
An alert has been raised due to a change in the number of sensors.
The value indicates the previous amount of sensors.
Integer32
Constraints:
range: 0-16
.1.3.6.1.4.1.31034.12.1.1.2.3.1.1.8
An alert has been raised due to voltage drop on this outlet.
The value indicates the first failed outlet.
Integer32
Constraints:
range: 0-54
.1.3.6.1.4.1.31034.12.1.1.2.3.1.1.9
An alert has been raised due to current exceeding treshhold.
The value indicates the exceeding branch. 0 = no alert.
Integer32
Constraints:
range: 0-18
.1.3.6.1.4.1.31034.12.1.1.2.3.1.1.10
An alert has been raised due to a voltage dip.
The value indicates the dipped branch. 0 = no alert.
Integer32
Constraints:
range: 0-18
.1.3.6.1.4.1.31034.12.1.1.2.3.1.1.11
An alert has been raised due to current exceeding treshhold.
0 = no alert
1 = current alert
Integer32
Constraints:
range: 0-1
.1.3.6.1.4.1.31034.12.1.1.2.3.1.1.12
A residual current alert has been raised.
0 = no alert
1 = current exceeding treshhold alert
2 = sensor error
Integer32
Constraints:
range: 0-2
.1.3.6.1.4.1.31034.12.1.1.2.3.1.1.13
0 = no alarm >0 = or slave number for alert
Integer32
Constraints:
range: 0-9
.1.3.6.1.4.1.31034.12.1.1.2.3.1.1.14
.1.3.6.1.4.1.31034.12.1.1.2.4.1 · 1 row entry · 5 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk sdbDevRsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-DATABUS-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-DATABUS-MIB::sdbDevRsTable'
A table providing reset capabilities to devices connected to the
databus.
The number of entries is given by the value of
sdbMgmtStsAddressableDevices.
sdbDevRsEntry row .1.3.6.1.4.1.31034.12.1.1.2.4.1.1
Reset entry providing reset objects of a particular databus device.
Indexes
Column Syntax OID
Warm reboot/reset of device controller.
NOTE: this will have NO effect on outlet status!
Enumerationr/w
Enumerated Values:
0idle
1reboot
.1.3.6.1.4.1.31034.12.1.1.2.4.1.1.1
Reset all alert signals and device status code.
Enumerationr/w
Enumerated Values:
0idle
1reset
.1.3.6.1.4.1.31034.12.1.1.2.4.1.1.2
Reset of all input kWh subtotal counters to zero.
Enumerationr/w
Enumerated Values:
0idle
1zero
.1.3.6.1.4.1.31034.12.1.1.2.4.1.1.3
Reset of all outlet kWh subtotal counter to zero.
Enumerationr/w
Enumerated Values:
0idle
1zero
.1.3.6.1.4.1.31034.12.1.1.2.4.1.1.4
Reset all peak and dip values to zero.
Enumerationr/w
Enumerated Values:
0idle
1reset
.1.3.6.1.4.1.31034.12.1.1.2.4.1.1.5
.1.3.6.1.4.1.31034.12.1.1.2.5.1 · 1 row entry · 13 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk sdbDevStTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-DATABUS-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-DATABUS-MIB::sdbDevStTable'
A table containing setting information of devices connected to the
databus.
The number of entries is given by the value of
sdbMgmtStsAddressableDevices.
sdbDevStEntry row .1.3.6.1.4.1.31034.12.1.1.2.5.1.1
Setting entry containing settings objects of a particular databus
device.
Indexes
Column Syntax OID
Auto reset alerts configuration.
If set to 0 the auto reset alerts feature is disabled. If set to a
value greater then 0, the auto reset alerts feature is enabled and
alerts will get cleared after the configured amount …
secondsInteger32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.31034.12.1.1.2.5.1.1.2
Use original or longer names for inputs, outlets and sensors.
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.31034.12.1.1.2.5.1.1.3
Amount of ms a current peak should last before an alert is raised.
msInteger32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.31034.12.1.1.2.5.1.1.4
Minimal delay between two successive relay switches in milliseconds.
Minimal delay is 100 ms. Will always be respected!
msInteger32r/w
Constraints:
range: 100-65535
.1.3.6.1.4.1.31034.12.1.1.2.5.1.1.5
Set backlight on time in seconds.
0 keeps display always on.
Note that keeping the backlight on may decrease luminosity over time.
sInteger32r/w
Constraints:
range: 120-120
range: 240-240
range: 60-60
range: 10-10
range: 0-0
.1.3.6.1.4.1.31034.12.1.1.2.5.1.1.6
Behaviour of outlets on power-up.
Enumerationr/w
Enumerated Values:
0off
1sameState
2sameStateDelayed
.1.3.6.1.4.1.31034.12.1.1.2.5.1.1.7
Maximum temperature threshold
An alert will be generated whenever the temperature is above this
value. Zero means disabled.
degrees CelsiusInteger32r/w
Constraints:
range: 0-99
.1.3.6.1.4.1.31034.12.1.1.2.5.1.1.8
Display orientation.
Enumerationr/w
Enumerated Values:
0noDisplay
1verticalDisplayOnTop
2verticalDisplayUpsideDown
3horizontalDisplayAtLeft
4horizontalDisplayAtRight
.1.3.6.1.4.1.31034.12.1.1.2.5.1.1.9
Allow alerts to be reset locally on device by pushing one of the
buttons.
Enumerationr/w
Enumerated Values:
0notAllowed
1allowed
.1.3.6.1.4.1.31034.12.1.1.2.5.1.1.10
Enables the current drop detection function.
Enumerationr/w
Enumerated Values:
0off
1inputsOnly
2outletsOnly
3inputsAndOutlets
.1.3.6.1.4.1.31034.12.1.1.2.5.1.1.11
Allow the USB port to be used for specific tasks
Enumerationr/w
Enumerated Values:
0usbDisabled
1onlyFirmwareUpdates
.1.3.6.1.4.1.31034.12.1.1.2.5.1.1.13
Enable sensoe change alerts
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.31034.12.1.1.2.5.1.1.14
Overrides the timeout. If this is set to 1 then the timeout will be ignored, otherwise the timeout will be taken into account.
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.31034.12.1.1.2.5.1.1.15
.1.3.6.1.4.1.31034.12.1.1.2.6.1 · 1 row entry · 14 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk sdbDevInTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-DATABUS-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-DATABUS-MIB::sdbDevInTable'
A table containing information of inputs of devices connected to the
databus.
sdbDevInEntry row .1.3.6.1.4.1.31034.12.1.1.2.6.1.1
Inputs entry containing objects of an input of a particular databus
device.
Note that this table has two indexes. sdbDevIdIndex to identify a
particular device and sdbDevInIndex to identify a particular input
of the dev…
Column Syntax OID
A unique value for each input. Its value ranges between 1 and the
value of sdbDevCfPhases.
Integer32
Constraints:
range: 1-54
.1.3.6.1.4.1.31034.12.1.1.2.6.1.1.1
Total kWh value of an input. This value can not be reset.
kWhKiloWattHour
Type Constraints:
range: 0..16777215
.1.3.6.1.4.1.31034.12.1.1.2.6.1.1.2
Subtotal kWh value of an input. This value can be reset.
kWhKiloWattHour
Type Constraints:
range: 0..16777215
.1.3.6.1.4.1.31034.12.1.1.2.6.1.1.3
Power factor of input.
The power factor of an AC power system is defined as the ratio of the
real or active power to the apparent power and is a number between 0
and 1. This value is expressed as a percentage between 0%…
%CentiPercent
Type Constraints:
range: 0..10000
.1.3.6.1.4.1.31034.12.1.1.2.6.1.1.4
Actual apparent, RMS current.
ACentiAmpere
Type Constraints:
range: 0..327680
.1.3.6.1.4.1.31034.12.1.1.2.6.1.1.5
Peak apparent, RMS current.
Highest value since last reset of the alerts.
ACentiAmpere
Type Constraints:
range: 0..327680
.1.3.6.1.4.1.31034.12.1.1.2.6.1.1.6
The actual voltage.
VCentiVolt
Type Constraints:
range: 0..327680
.1.3.6.1.4.1.31034.12.1.1.2.6.1.1.7
RMS voltage dip.
Lowest value since reset of alerts.
VCentiVolt
Type Constraints:
range: 0..327680
.1.3.6.1.4.1.31034.12.1.1.2.6.1.1.8
Calculated apparent power.
VAInteger32
Constraints:
range: 0-327680
.1.3.6.1.4.1.31034.12.1.1.2.6.1.1.9
Calculated real power.
WInteger32
Constraints:
range: 0-327680
.1.3.6.1.4.1.31034.12.1.1.2.6.1.1.10
Maximum current per input phase.
Should last at least sdbDevStPeakDuration ms before triggering an
alert.
ACentiAmperer/w
Type Constraints:
range: 0..327680
.1.3.6.1.4.1.31034.12.1.1.2.6.1.1.11
The multiplier to use for the input CTs.
Integer32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.31034.12.1.1.2.6.1.1.12
User configurable naming of inputs or phases.
OctetStringr/w
Constraints:
range: 0-8
.1.3.6.1.4.1.31034.12.1.1.2.6.1.1.13
Reset input kWh subtotal counter of a single input to zero.
Enumerationr/w
Enumerated Values:
0idle
1zero
.1.3.6.1.4.1.31034.12.1.1.2.6.1.1.14
.1.3.6.1.4.1.31034.12.1.1.2.7.1 · 1 row entry · 2 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk sdbDevOutTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-DATABUS-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-DATABUS-MIB::sdbDevOutTable'
A table containing information of outlets of devices connected to the
databus.
sdbDevOutEntry row .1.3.6.1.4.1.31034.12.1.1.2.7.1.1
Outlets entry containing objects of an outlet of a particular databus
device.
Note that this table has two indexes. sdbDevIdIndex to identify a
particular device and sdbDevOutIndex to identify a particular outlet
of the…
Column Syntax OID
A unique value for each outlet. Its value ranges between 1 and the
value of sdbDevCfOutletsTotal.
Integer32
Constraints:
range: 1-54
.1.3.6.1.4.1.31034.12.1.1.2.7.1.1.1
User configurable naming of individual outlets.
OctetStringr/w
Constraints:
range: 0-8
.1.3.6.1.4.1.31034.12.1.1.2.7.1.1.2
.1.3.6.1.4.1.31034.12.1.1.2.7.2 · 1 row entry · 11 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk sdbDevOutMtTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-DATABUS-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-DATABUS-MIB::sdbDevOutMtTable'
A table containing information of metered outlets of devices connected
to the databus.
sdbDevOutMtEntry row .1.3.6.1.4.1.31034.12.1.1.2.7.2.1
Metered outlets entry containing objects of a metered outlet of a
particular databus device.
Note that this table has two indexes. sdbDevIdIndex to identify a
particular device and sdbDevOutMtIndex to identify a particu…
Column Syntax OID
A unique value for each outlet. Its value ranges between 1 and the
value of sdbDevCfOutletsMetered.
Integer32
Constraints:
range: 1-54
.1.3.6.1.4.1.31034.12.1.1.2.7.2.1.1
Total kWh value of an outlet. This value can not be reset.
kWhKiloWattHour
Type Constraints:
range: 0..16777215
.1.3.6.1.4.1.31034.12.1.1.2.7.2.1.2
Subotal kWh value of an outlet. This value can be reset.
kWhKiloWattHour
Type Constraints:
range: 0..16777215
.1.3.6.1.4.1.31034.12.1.1.2.7.2.1.3
Power factor of outlet.
The power factor of an AC power system is defined as the ratio of the
real or active power to the apparent power and is a number between 0
and 1. This number is expressed as a percentage between …
%CentiPercent
Type Constraints:
range: 0..10000
.1.3.6.1.4.1.31034.12.1.1.2.7.2.1.4
Actual apparent, RMS current.
ACentiAmpere
Type Constraints:
range: 0..327680
.1.3.6.1.4.1.31034.12.1.1.2.7.2.1.5
Peak apparent, RMS current.
Highest value since last reset of the alerts.
ACentiAmpere
Type Constraints:
range: 0..327680
.1.3.6.1.4.1.31034.12.1.1.2.7.2.1.6
Actual voltage on outlet.
VCentiVolt
Type Constraints:
range: 0..327680
.1.3.6.1.4.1.31034.12.1.1.2.7.2.1.7
Maximum current per outlet.
Should last at least sdbDevStPeakDuration ms before triggering an
alert.
ACentiAmperer/w
Type Constraints:
range: 0..327680
.1.3.6.1.4.1.31034.12.1.1.2.7.2.1.8
The multiplier to use for the outlet CTs.
Integer32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.31034.12.1.1.2.7.2.1.9
Calculated apparent power.
VAInteger32
Constraints:
range: 0-327680
.1.3.6.1.4.1.31034.12.1.1.2.7.2.1.10
Calculated real power.
WInteger32
Constraints:
range: 0-327680
.1.3.6.1.4.1.31034.12.1.1.2.7.2.1.11
.1.3.6.1.4.1.31034.12.1.1.2.7.3 · 1 row entry · 6 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk sdbDevOutSwTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-DATABUS-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-DATABUS-MIB::sdbDevOutSwTable'
A table containing information of switched outlets of devices
connected to the databus.
sdbDevOutSwEntry row .1.3.6.1.4.1.31034.12.1.1.2.7.3.1
Switched outlets entry containing objects of a switched outlet of a
particular databus device.
Note that this table has two indexes. sdbDevIdIndex to identify a
particular device and sdbDevOutSwIndex to identify a parti…
Column Syntax OID
A unique value for each outlet. Its value ranges between 1 and the
value of sdbDevCfOutletsSwitched.
Integer32
Constraints:
range: 1-54
.1.3.6.1.4.1.31034.12.1.1.2.7.3.1.1
The actual state of the outlet relay.
Note that Writing is only effective after setting sdbDevOutSwUnlock.
Enumerationr/w
Enumerated Values:
0off
1on
.1.3.6.1.4.1.31034.12.1.1.2.7.3.1.2
A one indicates pending activity; the switch delay has not yet
expired.
Enumeration
Enumerated Values:
0idle
1scheduled
.1.3.6.1.4.1.31034.12.1.1.2.7.3.1.3
Switching and rebooting is unlocked for 10 seconds by writing a 1.
Enumerationr/w
Enumerated Values:
0locked
1unlocked
.1.3.6.1.4.1.31034.12.1.1.2.7.3.1.4
Delay before an individual outlet switches on at power-up.
sInteger32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.31034.12.1.1.2.7.3.1.5
Reboot outlet relay if current state is on and outlet is unlocked;
The outlet will be turned on after 10 seconds.
Enumerationr/w
Enumerated Values:
0idle
1reboot
.1.3.6.1.4.1.31034.12.1.1.2.7.3.1.6
.1.3.6.1.4.1.31034.12.1.1.2.8.1 · 1 row entry · 6 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk sdbDevMeasuresTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-DATABUS-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-DATABUS-MIB::sdbDevMeasuresTable'
A table containing information of temperatures of devices connected to
the databus.
sdbDevMeasuresEntry row .1.3.6.1.4.1.31034.12.1.1.2.8.1.1
Device measures entry containing temperature information objects of a
particular databus device.
Indexes
Column Syntax OID
Actual internal device temperature in deg C
degrees CelsiusCentiCelsius
Type Constraints:
range: 0..9900
.1.3.6.1.4.1.31034.12.1.1.2.8.1.1.1
Actual external device temperature sensor in deg C.
degrees CelsiusCentiCelsius
Type Constraints:
range: 0..9900
.1.3.6.1.4.1.31034.12.1.1.2.8.1.1.2
Peak internal device temperature since last reset of alerts.
degrees CelsiusCentiCelsius
Type Constraints:
range: 0..9900
.1.3.6.1.4.1.31034.12.1.1.2.8.1.1.3
Peak external device temperature since last reset of alerts.
degrees CelsiusCentiCelsius
Type Constraints:
range: 0..9900
.1.3.6.1.4.1.31034.12.1.1.2.8.1.1.4
Residual current.
ACentiAmpere
Type Constraints:
range: 0..327680
.1.3.6.1.4.1.31034.12.1.1.2.8.1.1.5
Peak residual current.
ACentiAmpere
Type Constraints:
range: 0..327680
.1.3.6.1.4.1.31034.12.1.1.2.8.1.1.6
.1.3.6.1.4.1.31034.12.1.1.2.8.2 · 1 row entry · 4 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk sdbDevSnsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-DATABUS-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-DATABUS-MIB::sdbDevSnsTable'
A table containing information of sensors of devices connected to the
databus.
sdbDevSnsEntry row .1.3.6.1.4.1.31034.12.1.1.2.8.2.1
Sensors entry containing objects of a sensor of a particular databus
device.
Note that this table has two indexes. sdbDevIdIndex to identify a
particular device and sdbDevSnsIndex to identify a particular sensor
of the …
Column Syntax OID
A unique value for each sensor. Its value ranges between 1 and the
value of sdbDevCfSensors.
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.31034.12.1.1.2.8.2.1.1
Type of connected sensor.
T = Temperature (C)
H = Humidity (%)
I = dry switch contact
OctetString
Constraints:
range: 1-1
.1.3.6.1.4.1.31034.12.1.1.2.8.2.1.2
Value of connected sensor
Integer32
Constraints:
range: 0-327680
.1.3.6.1.4.1.31034.12.1.1.2.8.2.1.3
User definable name for sensors.
OctetStringr/w
Constraints:
range: 0-18
.1.3.6.1.4.1.31034.12.1.1.2.8.2.1.4
.1.3.6.1.4.1.31034.12.1.1.2.9.1 · 1 row entry · 5 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk sdbDevPerformanceTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-DATABUS-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-DATABUS-MIB::sdbDevPerformanceTable'
A table containing information of sensors of devices connected to the
databus.
sdbDevPerformanceEntry row .1.3.6.1.4.1.31034.12.1.1.2.9.1.1
Performance counters of a particular databus device.
Note that this table has two indexes. sdbDevIdIndex to identify a
particular device and sdbDevPerformanceIndex to identify a particular counter
of the device identifi…
Column Syntax OID
A unique value for each counter. Its value ranges between 1 and 16.
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.31034.12.1.1.2.9.1.1.1
Value of counter
Integer32
Constraints:
range: 0-16777215
.1.3.6.1.4.1.31034.12.1.1.2.9.1.1.2
Max of counter
Integer32
Constraints:
range: 0-16777215
.1.3.6.1.4.1.31034.12.1.1.2.9.1.1.3
Limit of counter
Integer32
Constraints:
range: 0-16777215
.1.3.6.1.4.1.31034.12.1.1.2.9.1.1.4
User definable name for counter.
OctetStringr/w
Constraints:
range: 0-12
.1.3.6.1.4.1.31034.12.1.1.2.9.1.1.5
.1.3.6.1.4.1.31034.12.1.1.2.9.2 · 1 row entry · 2 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk sdbDevPerformanceResetTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-DATABUS-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-DATABUS-MIB::sdbDevPerformanceResetTable'
A table containing the last reset reason of the device
sdbDevPerformanceResetEntry row .1.3.6.1.4.1.31034.12.1.1.2.9.2.1
Setting entry containing settings objects of a particular databus
device.
Indexes
Column Syntax OID
Last reset reason.
OctetStringr/w
Constraints:
range: 0-64
.1.3.6.1.4.1.31034.12.1.1.2.9.2.1.1
Uptime before last reset
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.31034.12.1.1.2.9.2.1.2
.1.3.6.1.4.1.31034.12.1.1.2.10.1 · 1 row entry · 14 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk sdbDevBranchTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-DATABUS-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-DATABUS-MIB::sdbDevBranchTable'
A table containing information of inputs of devices connected to the
databus.
sdbDevBranchEntry row .1.3.6.1.4.1.31034.12.1.1.2.10.1.1
Inputs entry containing objects of an input of a particular databus
device.
Note that this table has two indexes. sdbDevIdIndex to identify a
particular device and sdbDevBranchIndex to identify a particular input
of the…
Column Syntax OID
A unique value for each input. Its value ranges between 1 and the
value of sdbDevCfPhases.
Integer32
Constraints:
range: 1-54
.1.3.6.1.4.1.31034.12.1.1.2.10.1.1.1
Total kWh value of an input. This value can not be reset.
kWhKiloWattHour
Type Constraints:
range: 0..16777215
.1.3.6.1.4.1.31034.12.1.1.2.10.1.1.2
Subtotal kWh value of an input. This value can be reset.
kWhKiloWattHour
Type Constraints:
range: 0..16777215
.1.3.6.1.4.1.31034.12.1.1.2.10.1.1.3
Power factor of input.
The power factor of an AC power system is defined as the ratio of the
real or active power to the apparent power and is a number between 0
and 1. This value is expressed as a percentage between 0%…
%CentiPercent
Type Constraints:
range: 0..10000
.1.3.6.1.4.1.31034.12.1.1.2.10.1.1.4
Actual apparent, RMS current.
ACentiAmpere
Type Constraints:
range: 0..327680
.1.3.6.1.4.1.31034.12.1.1.2.10.1.1.5
Peak apparent, RMS current.
Highest value since last reset of the alerts.
ACentiAmpere
Type Constraints:
range: 0..327680
.1.3.6.1.4.1.31034.12.1.1.2.10.1.1.6
The actual voltage.
VCentiVolt
Type Constraints:
range: 0..327680
.1.3.6.1.4.1.31034.12.1.1.2.10.1.1.7
RMS voltage dip.
Lowest value since reset of alerts.
VCentiVolt
Type Constraints:
range: 0..327680
.1.3.6.1.4.1.31034.12.1.1.2.10.1.1.8
Calculated apparent power.
VAInteger32
Constraints:
range: 0-327680
.1.3.6.1.4.1.31034.12.1.1.2.10.1.1.9
Calculated real power.
WInteger32
Constraints:
range: 0-327680
.1.3.6.1.4.1.31034.12.1.1.2.10.1.1.10
Maximum current per input phase.
Should last at least sdbDevStPeakDuration ms before triggering an
alert.
ACentiAmperer/w
Type Constraints:
range: 0..327680
.1.3.6.1.4.1.31034.12.1.1.2.10.1.1.11
The multiplier to use for the input CTs.
Integer32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.31034.12.1.1.2.10.1.1.12
User configurable naming of branches.
OctetStringr/w
Constraints:
range: 0-8
.1.3.6.1.4.1.31034.12.1.1.2.10.1.1.13
Reset input kWh subtotal counter of a single input to zero.
Enumerationr/w
Enumerated Values:
0idle
1zero
.1.3.6.1.4.1.31034.12.1.1.2.10.1.1.14
.1.3.6.1.4.1.31034.12.1.1.2.11.1 · 1 row entry · 11 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk sdbDevTotalsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-DATABUS-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-DATABUS-MIB::sdbDevTotalsTable'
A table containing information of inputs of devices connected to the
databus.
sdbDevTotalsEntry row .1.3.6.1.4.1.31034.12.1.1.2.11.1.1
Inputs entry containing objects of an input of a particular databus
device.
Note that this table has two indexes. sdbDevIdIndex to identify a
particular device and sdbDevTotalsIndex to identify a particular input
of the…
Column Syntax OID
A unique value for each input. Its value ranges between 1 and the
value of sdbDevCfPhases.
Integer32
Constraints:
range: 1-54
.1.3.6.1.4.1.31034.12.1.1.2.11.1.1.1
Total kWh value of an input. This value can not be reset.
kWhKiloWattHour
Type Constraints:
range: 0..16777215
.1.3.6.1.4.1.31034.12.1.1.2.11.1.1.2
Power factor of input.
The power factor of an AC power system is defined as the ratio of the
real or active power to the apparent power and is a number between 0
and 1. This value is expressed as a percentage between 0%…
%CentiPercent
Type Constraints:
range: 0..10000
.1.3.6.1.4.1.31034.12.1.1.2.11.1.1.3
Actual apparent, RMS current.
ACentiAmpere
Type Constraints:
range: 0..327680
.1.3.6.1.4.1.31034.12.1.1.2.11.1.1.4
Peak apparent, RMS current.
Highest value since last reset of the alerts.
ACentiAmpere
Type Constraints:
range: 0..327680
.1.3.6.1.4.1.31034.12.1.1.2.11.1.1.5
Calculated apparent power.
VAInteger32
Constraints:
range: 0-327680
.1.3.6.1.4.1.31034.12.1.1.2.11.1.1.6
Calculated real power.
WInteger32
Constraints:
range: 0-327680
.1.3.6.1.4.1.31034.12.1.1.2.11.1.1.7
Neutral current of phases.
ACentiAmpere
Type Constraints:
range: 0..327680
.1.3.6.1.4.1.31034.12.1.1.2.11.1.1.8
Peak neutral current of phases.
ACentiAmpere
Type Constraints:
range: 0..327680
.1.3.6.1.4.1.31034.12.1.1.2.11.1.1.9
Maximum neutral current.
Should last at least sdbDevStPeakDuration ms before triggering an
alert.
ACentiAmperer/w
Type Constraints:
range: 0..327680
.1.3.6.1.4.1.31034.12.1.1.2.11.1.1.10
Maximum residual current.
Should last at least sdbDevStPeakDuration ms before triggering an
alert.
ACentiAmperer/w
Type Constraints:
range: 0..327680
.1.3.6.1.4.1.31034.12.1.1.2.11.1.1.11