RNX-UPDU-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
5
Rows
5
Columns
34
upduModuleTable
table.1.3.6.1.4.1.55108.1.2.1
·
1 row entry
·
5 columns
Uses the bachmann variant from
Command help
/opt/observium/mibs/bachmann.
Walk upduModuleTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RNX-UPDU-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RNX-UPDU-MIB::upduModuleTable'
A list of module entries.
An entry containing information for a particular module.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
Module index.
|
Integer32 Constraints: range: 0-8 |
.1.3.6.1.4.1.55108.1.2.1.1.1 |
||||||
|
Module type: tells what type of module it is.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.55108.1.2.1.1.2 |
||||||
|
Part number
|
OctetString | .1.3.6.1.4.1.55108.1.2.1.1.3 |
||||||
|
Module serial number.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.55108.1.2.1.1.4 |
||||||
|
Module lot number.
|
OctetString | .1.3.6.1.4.1.55108.1.2.1.1.5 |
upduMeterTable
table.1.3.6.1.4.1.55108.1.3.1
·
1 row entry
·
14 columns
Uses the bachmann variant from
Command help
/opt/observium/mibs/bachmann.
Walk upduMeterTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RNX-UPDU-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RNX-UPDU-MIB::upduMeterTable'
Holds information about each Power module.
An entry provides a power data
Indexes
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Number of the meter on the Module.
|
Integer32 Constraints: range: 0-11 |
.1.3.6.1.4.1.55108.1.3.1.1.1 |
||||||||||||||||
|
Meter name.
|
OctetString Constraints: range: 0-15 |
.1.3.6.1.4.1.55108.1.3.1.1.2 |
||||||||||||||||
|
Meter type: Tell if the meter is per-phase, per PDU,
per module or for a single outlet or outlet group. For pduTotalCalc, phaseTotalCalc, moduleTotalCalc, the total is calculated (sum of the measurements of the underlyi… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.55108.1.3.1.1.3 |
||||||||||||||||
|
Positive active energy in watt hours.
|
WhWattHours | .1.3.6.1.4.1.55108.1.3.1.1.4 |
||||||||||||||||
|
Reactive energy from quadrant R1 in volt-ampere reactives hours.
|
varhVoltAmpereReactiveHours | .1.3.6.1.4.1.55108.1.3.1.1.5 |
||||||||||||||||
|
Reactive energy from quadrant R4 in volt-ampere reactives hours.
|
varhVoltAmpereReactiveHours | .1.3.6.1.4.1.55108.1.3.1.1.6 |
||||||||||||||||
|
Active power at a given instant.
|
WWatts | .1.3.6.1.4.1.55108.1.3.1.1.7 |
||||||||||||||||
|
Reactive power at a given instant.
|
varVoltAmpereReactives | .1.3.6.1.4.1.55108.1.3.1.1.8 |
||||||||||||||||
|
Apparent power at a given instant.
|
VAVoltAmperes | .1.3.6.1.4.1.55108.1.3.1.1.9 |
||||||||||||||||
|
RMS voltage at a given instant.
|
mVMilliVolts | .1.3.6.1.4.1.55108.1.3.1.1.10 |
||||||||||||||||
|
RMS current at a given instant.
|
mAMilliAmperes | .1.3.6.1.4.1.55108.1.3.1.1.11 |
||||||||||||||||
|
System-defined object name.
|
OctetString | .1.3.6.1.4.1.55108.1.3.1.1.12 |
||||||||||||||||
|
User-configured unique object name. Write access has to be
explicitly enabled in the UPDU configuration (see SNMP options). |
OctetStringr/w Constraints: range: 0-23 |
.1.3.6.1.4.1.55108.1.3.1.1.13 |
||||||||||||||||
|
User-configured description. Write access has to be
explicitly enabled in the UPDU configuration (see SNMP options). |
OctetStringr/w Constraints: range: 0-127 |
.1.3.6.1.4.1.55108.1.3.1.1.14 |
upduSensorTable
table.1.3.6.1.4.1.55108.1.3.2
·
1 row entry
·
5 columns
Uses the bachmann variant from
Command help
/opt/observium/mibs/bachmann.
Walk upduSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RNX-UPDU-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RNX-UPDU-MIB::upduSensorTable'
Holds information about sensors connected to the PDU.
Holds the information related to one specific sensor.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
Sensor port number.
|
Integer32 Constraints: range: 1-3 |
.1.3.6.1.4.1.55108.1.3.2.1.1 |
||||||
|
Sensor port name as printed on the front plate.
|
OctetString | .1.3.6.1.4.1.55108.1.3.2.1.2 |
||||||
|
Sensor type.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.55108.1.3.2.1.3 |
||||||
|
Temperature in tenth degrees.
|
deg-C/10TenthDegreesCelsius | .1.3.6.1.4.1.55108.1.3.2.1.4 |
||||||
|
Relative humidity in per mil. Set to 0 for temperature only sensor.
|
/1000Permil | .1.3.6.1.4.1.55108.1.3.2.1.5 |
upduRcmTable
table.1.3.6.1.4.1.55108.1.3.3
·
1 row entry
·
5 columns
Uses the bachmann variant from
Command help
/opt/observium/mibs/bachmann.
Walk upduRcmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RNX-UPDU-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RNX-UPDU-MIB::upduRcmTable'
Holds information about embedded residual current monitors.
An entry provides Residual current data
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
RCM index.
|
Integer32 Constraints: range: 0-11 |
.1.3.6.1.4.1.55108.1.3.3.1.1 |
||||||||||
|
RCM name.
|
OctetString Constraints: range: 0-15 |
.1.3.6.1.4.1.55108.1.3.3.1.2 |
||||||||||
|
RMS residual current.
|
mA/10TenthMilliAmperes | .1.3.6.1.4.1.55108.1.3.3.1.3 |
||||||||||
|
DC residual current.
|
mA/10TenthMilliAmperes | .1.3.6.1.4.1.55108.1.3.3.1.4 |
||||||||||
|
RCM sensor health
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.55108.1.3.3.1.5 |
upduRelayTable
table.1.3.6.1.4.1.55108.1.4.1
·
1 row entry
·
5 columns
Uses the bachmann variant from
Command help
/opt/observium/mibs/bachmann.
Walk upduRelayTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RNX-UPDU-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RNX-UPDU-MIB::upduRelayTable'
Holds Relay state.
An entry provides the status for a relay.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
Relay index.
|
Integer32 Constraints: range: 1-12 |
.1.3.6.1.4.1.55108.1.4.1.1.1 |
||||||
|
Comma-separated list of meter names this relay controls.
|
OctetString Constraints: range: 0-255 |
.1.3.6.1.4.1.55108.1.4.1.1.2 |
||||||
|
Defines the desired state of the relay.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.55108.1.4.1.1.3 |
||||||
|
Defines the operational state of the relay.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.55108.1.4.1.1.4 |
||||||
|
Gives the relay condition. Ok if the desired state
corresponds to the operational state, failed if it differs and unknown if the operational state is not known. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.55108.1.4.1.1.5 |