RNX-UPDU-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
5
Rows
5
Columns
34
.1.3.6.1.4.1.55108.1.2.1 · 1 row entry · 5 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk upduModuleTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RNX-UPDU-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RNX-UPDU-MIB::upduModuleTable'
A list of module entries.
upduModuleEntry row .1.3.6.1.4.1.55108.1.2.1.1
An entry containing information for a particular module.
Indexes
Column Syntax OID
Module index.
Integer32
Constraints:
range: 0-8
.1.3.6.1.4.1.55108.1.2.1.1.1
Module type: tells what type of module it is.
Enumeration
Enumerated Values:
0unknown
1icm
2meterModule
.1.3.6.1.4.1.55108.1.2.1.1.2
Part number
OctetString .1.3.6.1.4.1.55108.1.2.1.1.3
Module serial number.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.55108.1.2.1.1.4
Module lot number.
OctetString .1.3.6.1.4.1.55108.1.2.1.1.5
.1.3.6.1.4.1.55108.1.3.1 · 1 row entry · 14 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk upduMeterTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RNX-UPDU-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RNX-UPDU-MIB::upduMeterTable'
Holds information about each Power module.
upduMeterEntry row .1.3.6.1.4.1.55108.1.3.1.1
An entry provides a power data
Column Syntax OID
Number of the meter on the Module.
Integer32
Constraints:
range: 0-11
.1.3.6.1.4.1.55108.1.3.1.1.1
Meter name.
OctetString
Constraints:
range: 0-15
.1.3.6.1.4.1.55108.1.3.1.1.2
Meter type: Tell if the meter is per-phase, per PDU,
per module or for a single outlet or outlet group. For
pduTotalCalc, phaseTotalCalc, moduleTotalCalc, the
total is calculated (sum of the measurements of the
underlyi…
Enumeration
Enumerated Values:
0pduTotal
1pduTotalCalc
2phaseTotal
3phaseTotalCalc
4moduleTotal
5moduleTotalCalc
6outlet
7outletGroup
.1.3.6.1.4.1.55108.1.3.1.1.3
Positive active energy in watt hours.
WhWattHours .1.3.6.1.4.1.55108.1.3.1.1.4
Reactive energy from quadrant R1 in volt-ampere reactives hours.
varhVoltAmpereReactiveHours .1.3.6.1.4.1.55108.1.3.1.1.5
Reactive energy from quadrant R4 in volt-ampere reactives hours.
varhVoltAmpereReactiveHours .1.3.6.1.4.1.55108.1.3.1.1.6
Active power at a given instant.
WWatts .1.3.6.1.4.1.55108.1.3.1.1.7
Reactive power at a given instant.
varVoltAmpereReactives .1.3.6.1.4.1.55108.1.3.1.1.8
Apparent power at a given instant.
VAVoltAmperes .1.3.6.1.4.1.55108.1.3.1.1.9
RMS voltage at a given instant.
mVMilliVolts .1.3.6.1.4.1.55108.1.3.1.1.10
RMS current at a given instant.
mAMilliAmperes .1.3.6.1.4.1.55108.1.3.1.1.11
System-defined object name.
OctetString .1.3.6.1.4.1.55108.1.3.1.1.12
User-configured unique object name. Write access has to be
explicitly enabled in the UPDU configuration (see SNMP
options).
OctetStringr/w
Constraints:
range: 0-23
.1.3.6.1.4.1.55108.1.3.1.1.13
User-configured description. Write access has to be
explicitly enabled in the UPDU configuration (see SNMP
options).
OctetStringr/w
Constraints:
range: 0-127
.1.3.6.1.4.1.55108.1.3.1.1.14
.1.3.6.1.4.1.55108.1.3.2 · 1 row entry · 5 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk upduSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RNX-UPDU-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RNX-UPDU-MIB::upduSensorTable'
Holds information about sensors connected to the PDU.
upduSensorEntry row .1.3.6.1.4.1.55108.1.3.2.1
Holds the information related to one specific sensor.
Indexes
Column Syntax OID
Sensor port number.
Integer32
Constraints:
range: 1-3
.1.3.6.1.4.1.55108.1.3.2.1.1
Sensor port name as printed on the front plate.
OctetString .1.3.6.1.4.1.55108.1.3.2.1.2
Sensor type.
Enumeration
Enumerated Values:
0none
1temp
2tempHumidity
.1.3.6.1.4.1.55108.1.3.2.1.3
Temperature in tenth degrees.
deg-C/10TenthDegreesCelsius .1.3.6.1.4.1.55108.1.3.2.1.4
Relative humidity in per mil. Set to 0 for temperature only sensor.
/1000Permil .1.3.6.1.4.1.55108.1.3.2.1.5

upduRcmTable

table
.1.3.6.1.4.1.55108.1.3.3 · 1 row entry · 5 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk upduRcmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RNX-UPDU-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RNX-UPDU-MIB::upduRcmTable'
Holds information about embedded residual current monitors.
upduRcmEntry row .1.3.6.1.4.1.55108.1.3.3.1
An entry provides Residual current data
Column Syntax OID
RCM index.
Integer32
Constraints:
range: 0-11
.1.3.6.1.4.1.55108.1.3.3.1.1
RCM name.
OctetString
Constraints:
range: 0-15
.1.3.6.1.4.1.55108.1.3.3.1.2
RMS residual current.
mA/10TenthMilliAmperes .1.3.6.1.4.1.55108.1.3.3.1.3
DC residual current.
mA/10TenthMilliAmperes .1.3.6.1.4.1.55108.1.3.3.1.4
RCM sensor health
Enumeration
Enumerated Values:
0ok
1nodata
2timeout
3internalerror
4selftestfailed
.1.3.6.1.4.1.55108.1.3.3.1.5
.1.3.6.1.4.1.55108.1.4.1 · 1 row entry · 5 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk upduRelayTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RNX-UPDU-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RNX-UPDU-MIB::upduRelayTable'
Holds Relay state.
upduRelayEntry row .1.3.6.1.4.1.55108.1.4.1.1
An entry provides the status for a relay.
Column Syntax OID
Relay index.
Integer32
Constraints:
range: 1-12
.1.3.6.1.4.1.55108.1.4.1.1.1
Comma-separated list of meter names this relay controls.
OctetString
Constraints:
range: 0-255
.1.3.6.1.4.1.55108.1.4.1.1.2
Defines the desired state of the relay.
Enumerationr/w
Enumerated Values:
0off
1on
2unknown
.1.3.6.1.4.1.55108.1.4.1.1.3
Defines the operational state of the relay.
Enumeration
Enumerated Values:
0off
1on
2unknown
.1.3.6.1.4.1.55108.1.4.1.1.4
Gives the relay condition. Ok if the desired state
corresponds to the operational state, failed if it
differs and unknown if the operational state is not
known.
Enumeration
Enumerated Values:
0ok
1failed
2unknown
.1.3.6.1.4.1.55108.1.4.1.1.5