RITTAL-CMC-III-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
17
Rows
17
Columns
160
.1.3.6.1.4.1.2606.7.2.14 · 1 row entry · 2 columns
Uses the rittal variant from /opt/observium/mibs/rittal.
Command help
Walk cmcIIIUnitLoadTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RITTAL-CMC-III-MIB' -M '/opt/observium/mibs/rittal:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RITTAL-CMC-III-MIB::cmcIIIUnitLoadTable'
A list of system load entries.
cmcIIIUnitLoadEntry row .1.3.6.1.4.1.2606.7.2.14.1
Entries of system load table.
Column Syntax OID
Index for the system load table.
These are the past minutes the load is given for.
Unsigned32
Constraints:
range: 1-10
.1.3.6.1.4.1.2606.7.2.14.1.1
System load average multiplied by 100.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2606.7.2.14.1.2
.1.3.6.1.4.1.2606.7.3.3.2 · 1 row entry · 7 columns
Uses the rittal variant from /opt/observium/mibs/rittal.
Command help
Walk cmcIIITimerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RITTAL-CMC-III-MIB' -M '/opt/observium/mibs/rittal:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RITTAL-CMC-III-MIB::cmcIIITimerTable'
Headline of Timer Table.
cmcIIITimerEntry row .1.3.6.1.4.1.2606.7.3.3.2.1
Entries of Timer Table.
Column Syntax OID
Index for the list of timer entries. Its value ranges
between 1 and the value of cmcIIINumberOfTimers.
Unsigned32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.7.3.3.2.1.1
Actual status of the timer.
Enumeration
Enumerated Values:
1switchedOff
2switchedOn
3noTime
.1.3.6.1.4.1.2606.7.3.3.2.1.2
Selection of day of week for timer to switch.
Enumerationr/w
Enumerated Values:
1sun
2mon
3tue
4wed
5thu
6fri
7sat
8sat2sun
9mon2fri
10mon2sun
.1.3.6.1.4.1.2606.7.3.3.2.1.3
Time to switch on current function, Format: HH:MM.
OctetStringr/w
Constraints:
range: 5-5
.1.3.6.1.4.1.2606.7.3.3.2.1.4
Time to switch off current function, Format: HH:MM.
OctetStringr/w
Constraints:
range: 5-5
.1.3.6.1.4.1.2606.7.3.3.2.1.5
Control via RTC.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.2606.7.3.3.2.1.6
Function which is controlled via timer
1: Unlock of doors via keypad is disabled
2: Doors will be unlocked
3-6: sending traps to this trap receiver will be disabled
7-10: sending SMS to phone number 1..4 will be disable…
Enumerationr/w
Enumerated Values:
1disKeypads
2unlDoors
3disTrapRec1
4disTrapRec2
5disTrapRec3
6disTrapRec4
7disSMS1
8disSMS2
9disSMS3
10disSMS4
11schedule1
12schedule2
13schedule3
14schedule4
15schedule5
16schedule6
17schedule7
18schedule8
.1.3.6.1.4.1.2606.7.3.3.2.1.7
.1.3.6.1.4.1.2606.7.3.4.2 · 1 row entry · 3 columns
Uses the rittal variant from /opt/observium/mibs/rittal.
Command help
Walk cmcIIITrapReceiverTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RITTAL-CMC-III-MIB' -M '/opt/observium/mibs/rittal:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RITTAL-CMC-III-MIB::cmcIIITrapReceiverTable'
A list of trap receiver entries.
cmcIIITrapReceiverEntry row .1.3.6.1.4.1.2606.7.3.4.2.1
Entries of trapTable.
Column Syntax OID
Index for the trap receiver table. Its value ranges between
1 and the value of NumberOfTrapReceivers.
Unsigned32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.7.3.4.2.1.1
Enable SNMP version and trap/inform type or disable trap receiver.
Enumeration type snmpv3Inform(6) is not yet supported.
Enumerationr/w
Enumerated Values:
1disabled
2snmpv1Trap
3snmpv2cTrap
4snmpv2cInform
5snmpv3Trap
6snmpv3Inform
.1.3.6.1.4.1.2606.7.3.4.2.1.2
IP address of trap receiver.
OctetStringr/w
Constraints:
range: 0-64
.1.3.6.1.4.1.2606.7.3.4.2.1.3
.1.3.6.1.4.1.2606.7.3.5.10 · 1 row entry · 3 columns
Uses the rittal variant from /opt/observium/mibs/rittal.
Command help
Walk cmcIIISmtpReceiverTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RITTAL-CMC-III-MIB' -M '/opt/observium/mibs/rittal:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RITTAL-CMC-III-MIB::cmcIIISmtpReceiverTable'
A list of SMTP receiver entries.
cmcIIISmtpReceiverEntry row .1.3.6.1.4.1.2606.7.3.5.10.1
Entries of SMTPTable.
Column Syntax OID
Index for the SMTP receiver table. Its value ranges between
1 and the value of NumberOfSmtpReceivers.
Unsigned32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.7.3.5.10.1.1
Enable or disable SMTP receiver.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.2606.7.3.5.10.1.2
IP address of SMTP receiver.
OctetStringr/w
Constraints:
range: 0-50
.1.3.6.1.4.1.2606.7.3.5.10.1.3
.1.3.6.1.4.1.2606.7.3.6.7 · 1 row entry · 3 columns
Uses the rittal variant from /opt/observium/mibs/rittal.
Command help
Walk cmcIIISmsReceiverTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RITTAL-CMC-III-MIB' -M '/opt/observium/mibs/rittal:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RITTAL-CMC-III-MIB::cmcIIISmsReceiverTable'
A list of SMS receiver entries.
cmcIIISmsReceiverEntry row .1.3.6.1.4.1.2606.7.3.6.7.1
Entries of SMSTable.
Column Syntax OID
Index for the SMS receiver table. Its value ranges between
1 and the value of NumberOfSmsReceivers.
Unsigned32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.7.3.6.7.1.1
Enable or disable SMS receiver.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.2606.7.3.6.7.1.2
Phone number of SMS receiver.
OctetStringr/w
Constraints:
range: 0-30
.1.3.6.1.4.1.2606.7.3.6.7.1.3
.1.3.6.1.4.1.2606.7.3.10.2 · 1 row entry · 6 columns
Uses the rittal variant from /opt/observium/mibs/rittal.
Command help
Walk cmcIIIShutdownTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RITTAL-CMC-III-MIB' -M '/opt/observium/mibs/rittal:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RITTAL-CMC-III-MIB::cmcIIIShutdownTable'
A list of shutdown entries.
cmcIIIShutdownEntry row .1.3.6.1.4.1.2606.7.3.10.2.1
Entries of Shutdown table.
Column Syntax OID
Index for the shutdown server table. Its value ranges between
1 and the value of cmcIIINumberOfShutdowns.
Unsigned32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.7.3.10.2.1.1
IP address or name of server to shutdown.
OctetStringr/w
Constraints:
range: 0-64
.1.3.6.1.4.1.2606.7.3.10.2.1.2
Name of server to shutdown.
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.2606.7.3.10.2.1.3
Port used to shutdown server.
Unsigned32r/w
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.7.3.10.2.1.4
Delay of server shutdown.
Unsigned32r/w
Constraints:
range: 0-999
.1.3.6.1.4.1.2606.7.3.10.2.1.5
Enable or disable this server shutdown entry.
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.2606.7.3.10.2.1.6
.1.3.6.1.4.1.2606.7.3.11.4 · 1 row entry · 3 columns
Uses the rittal variant from /opt/observium/mibs/rittal.
Command help
Walk cmcIIIModbusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RITTAL-CMC-III-MIB' -M '/opt/observium/mibs/rittal:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RITTAL-CMC-III-MIB::cmcIIIModbusTable'
A list of Modbus entries.
cmcIIIModbusEntry row .1.3.6.1.4.1.2606.7.3.11.4.1
Entries of Modbus table.
Column Syntax OID
Index for the Modbus access table. Its value ranges
between 1 and the value of cmcIIINumberOfModbusSources.
Unsigned32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.7.3.11.4.1.1
Modbus access for this source entry:
(1) readonly
(2) readwrite
This access is inferior to cmcIIIModbusStatus, e.g.
readwrite access also requires readwrite status.
Enumerationr/w
Enumerated Values:
1readonly
2readwrite
.1.3.6.1.4.1.2606.7.3.11.4.1.2
Source to restrict Modbus access.

It can either be a
specific hostname,
IP address, or a subnet represented as
IP/MASK (e.g. 10.10.10.0/255.255.255.0),
or IP/BITS (e.g. 10.10.10.0/24),
or the IPv6 equival…
OctetStringr/w
Constraints:
range: 0-64
.1.3.6.1.4.1.2606.7.3.11.4.1.3
.1.3.6.1.4.1.2606.7.4.1.2 · 1 row entry · 23 columns
Uses the rittal variant from /opt/observium/mibs/rittal.
Command help
Walk cmcIIIDevTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RITTAL-CMC-III-MIB' -M '/opt/observium/mibs/rittal:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RITTAL-CMC-III-MIB::cmcIIIDevTable'
Headline of device table.
cmcIIIDevEntry row .1.3.6.1.4.1.2606.7.4.1.2.1
Entries of device table.
Indexes
Column Syntax OID
Index of device connected to CMCIII PU.
Unsigned32
Constraints:
range: 1-126
.1.3.6.1.4.1.2606.7.4.1.2.1.1
Name of the device connected to CMCIII PU.
OctetString
Constraints:
range: 0-30
.1.3.6.1.4.1.2606.7.4.1.2.1.2
Descriptional text for device connected to CMCIII PU.
OctetStringr/w
Constraints:
range: 0-40
.1.3.6.1.4.1.2606.7.4.1.2.1.3
Type of device chassis connected to CMCIII PU.
The authoritative identification of the device contained
in the entity is allocated within the SMI cmcIIIProducts
subtree (1.3.6.1.4.1.2606.7.7) and provides an easy and
un…
ObjectIdentifier .1.3.6.1.4.1.2606.7.4.1.2.1.4
Node ID of device connected to CMCIII PU.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.7.4.1.2.1.5
General Status of device connected to CMCIII PU
(1) Device not available
(2) OK
(3) Device detected, confirmation required
(4) Device lost (disconnected), confirmation required
(5) Device changed
(6) Error
(7) Firmware …
Enumeration
Enumerated Values:
1notAvail
2ok
3detect
4lost
5changed
6error
7fwUpdate
8fwUpdateRun
.1.3.6.1.4.1.2606.7.4.1.2.1.6
Article number of device connected to CMCIII PU.
OctetString
Constraints:
range: 0-10
.1.3.6.1.4.1.2606.7.4.1.2.1.7
Location of device connected to CMCIII PU.
OctetStringr/w
Constraints:
range: 0-40
.1.3.6.1.4.1.2606.7.4.1.2.1.8
CAN bus of device connected to CMCIII PU.
Enumeration
Enumerated Values:
1canBus1
2canBus2
3virtual
4modbus
5wireless
.1.3.6.1.4.1.2606.7.4.1.2.1.9
Position (order) of device in CAN bus connected to CMCIII PU.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.7.4.1.2.1.10
FW version of device connected to CMCIII PU.
OctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.2606.7.4.1.2.1.11
HW version of device connected to CMCIII PU.
OctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.2606.7.4.1.2.1.12
Serial number of device connected to CMCIII PU.
OctetString
Constraints:
range: 8-8
.1.3.6.1.4.1.2606.7.4.1.2.1.13
Production week of device connected to CMCIII PU.
OctetString
Constraints:
range: 8-8
.1.3.6.1.4.1.2606.7.4.1.2.1.14
Timestamp of last change of device connected to CMCIII PU
according to operating time cmcIIIUnitUpTime.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2606.7.4.1.2.1.15
URL to device page of CMCIII PU (if available).
OctetString
Constraints:
range: 0-30
.1.3.6.1.4.1.2606.7.4.1.2.1.16
Number of variables available on this device.
This variable will give the number of rows of the
variable table cmcIIIVarTable belonging to this device.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.7.4.1.2.1.17
Number of messages available in this device.
This variable will give the number of rows of the message
table cmcIIIMsgTable belonging to this device.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.7.4.1.2.1.18
Latest status of this device.
OctetString
Constraints:
range: 0-160
.1.3.6.1.4.1.2606.7.4.1.2.1.19
Standby power consumption of device in mA.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.7.4.1.2.1.20
Maximal power consumption of device in mA.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.7.4.1.2.1.21
Corresponding entPhysicalIndex of this device. 0 if none exists.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.7.4.1.2.1.22
Assembly of this device.
OctetString
Constraints:
range: 0-100
.1.3.6.1.4.1.2606.7.4.1.2.1.23
.1.3.6.1.4.1.2606.7.4.2.2 · 1 row entry · 15 columns
Uses the rittal variant from /opt/observium/mibs/rittal.
Command help
Walk cmcIIIVarTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RITTAL-CMC-III-MIB' -M '/opt/observium/mibs/rittal:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RITTAL-CMC-III-MIB::cmcIIIVarTable'
Headline of variable table.
cmcIIIVarEntry row .1.3.6.1.4.1.2606.7.4.2.2.1
Entries of variable table.
Column Syntax OID
Index for the device. Its value ranges
between 1 and the value of cmcIIINumberOfDevs.
Unsigned32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.7.4.2.2.1.1
Index for the list of value entries. Its value ranges
between 1 and the value of cmcIIINumberOfVars.
Unsigned32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.7.4.2.2.1.2
Clear name of variable.
OctetString
Constraints:
range: 0-50
.1.3.6.1.4.1.2606.7.4.2.2.1.3
Type of variable.
Enumeration
Enumerated Values:
1description
2value
3setHigh
4setWarn
5setLow
6hysteresis
7status
8statusEnum
9setWarnLow
10unit
11alarmDur
12steps
13configPar
14category
15logic
16logicEnum
17setCntrl
18offset
19type
20output
21outputdelay
22outputaction
23outdelayExec
24outputEnum
25config
26configNum
27configLcpFcs
28assembly
29configWiring
30sensitivity
31accessTime
32accessLogic
33position
34positionEnum
35pin
36sequence
37remote
38stringValue
39remoteTimeout
40outputPWM
41rotation
42circuit
43rizoneArray
44socketType
45customValue
46rcmPosition
47rcmPosEnum
48rcmResult
50productDate
51orderNr
52devName
53devLocation
54currentMin
55currentMax
56mode
80keycode
81command
82commandEnum
83commandKeypad
84commandService
85commandRack
86commandRCM
87commandStatus
90unitType
91swVersion
92serialNumber
93mountPos
94mountPosEnum
95gsmStatus
96connected
97connectedEnum
98hwVersion
100grouping
110scaleValue
111scaleUnit
112scaleStart
113scaleEnd
120commandCtrl
121commandCtrlDP
122commandCtrlWdt
123fanAffect
124waterAffect
125commandDP
126commandBEP
127commandMiniCh
128remoteBEP
130location
131building
132level
133room
134row
135rack
136operatingTime
137numberOfRU
138tagsQuit
139tagsChanged
140uid
145opModeBEP
146opModeMiniCh
150commandControl
151commandSignal
254ignore
255illegal
.1.3.6.1.4.1.2606.7.4.2.2.1.4
Unit of variable e. g. degree C.
OctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.2606.7.4.2.2.1.5
Datatype of variable.
Enumeration
Enumerated Values:
1notAvail
2int
3string
4enum
.1.3.6.1.4.1.2606.7.4.2.2.1.6
Scaling factor of variable value,
e. g. -100 -> value has to be divided by 100
+100 -> value has to be multiplied by 100.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.7.4.2.2.1.7
Constraints of value,
e. g. [-_ a-zA-Z0-9]+ (if VariableDatatype is 'string').
OctetString
Constraints:
range: 0-64
.1.3.6.1.4.1.2606.7.4.2.2.1.8
Steps of variable value (resolution).
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.7.4.2.2.1.9
Value as string, including sign (+/-) and unit (degree C).
OctetStringr/w
Constraints:
range: 0-40
.1.3.6.1.4.1.2606.7.4.2.2.1.10
Value as integer.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.7.4.2.2.1.11
Timestamp of last update or change
according to operating time cmcIIIUnitUpTime.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2606.7.4.2.2.1.12
Access for value.
Enumeration
Enumerated Values:
1none
2readonly
3readwrite
4readwriteswitch
5readwriteextended
.1.3.6.1.4.1.2606.7.4.2.2.1.13
Quality of variable.
Enumeration
Enumerated Values:
1undefined
2ok
3warning
4alarm
5info
21undefinedNoValue
22okNoValue
23warningNoValue
24alarmNoValue
25infoNoValue
.1.3.6.1.4.1.2606.7.4.2.2.1.14
Corresponding entPhysicalIndex of this variable. 0 if none exists.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.7.4.2.2.1.15
.1.3.6.1.4.1.2606.7.4.2.3 · 1 row entry · 6 columns
Uses the rittal variant from /opt/observium/mibs/rittal.
Command help
Walk cmcIIIVarByTypeTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RITTAL-CMC-III-MIB' -M '/opt/observium/mibs/rittal:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RITTAL-CMC-III-MIB::cmcIIIVarByTypeTable'
Headline of variable by type table.
cmcIIIVarByTypeEntry row .1.3.6.1.4.1.2606.7.4.2.3.1
Entries of variable by type table.
Column Syntax OID
Type of variable.
Enumeration
Enumerated Values:
1description
2value
3setHigh
4setWarn
5setLow
6hysteresis
7status
8statusEnum
9setWarnLow
10unit
11alarmDur
12steps
13configPar
14category
15logic
16logicEnum
17setCntrl
18offset
19type
20output
21outputdelay
22outputaction
23outdelayExec
24outputEnum
25config
26configNum
27configLcpFcs
28assembly
29configWiring
30sensitivity
31accessTime
32accessLogic
33position
34positionEnum
35pin
36sequence
37remote
38stringValue
40outputPWM
41rotation
42circuit
43rizoneArray
44socketType
45customValue
46rcmPosition
47rcmPosEnum
48rcmResult
50productDate
51orderNr
52devName
53devLocation
54currentMin
55currentMax
80keycode
81command
82commandEnum
83commandKeypad
84commandService
85commandRack
86commandRCM
90unitType
91swVersion
92serialNumber
93mountPos
94mountPosEnum
95gsmStatus
96connected
97connectedEnum
100grouping
110scaleValue
111scaleUnit
112scaleStart
113scaleEnd
120commandCtrl
121commandCtrlDP
122commandCtrlWdt
123fanAffect
124waterAffect
125commandDP
126commandBEP
127commandMiniCh
128remoteBEP
130location
131building
132level
133room
134row
135rack
136operatingTime
137numberOfRU
138tagsQuit
139tagsChanged
140uid
145opModeMiniCh
146opModeBEP
254ignore
255illegal
.1.3.6.1.4.1.2606.7.4.2.3.1.1
Index for the device. Its value ranges
between 1 and the value of cmcIIINumberOfDevs.
Unsigned32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.7.4.2.3.1.2
Index for the list of value entries. Its value ranges
between 1 and the value of cmcIIINumberOfVars.
Unsigned32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.7.4.2.3.1.3
Value as string, including sign (+/-) and unit (degree C).
OctetString
Constraints:
range: 0-40
.1.3.6.1.4.1.2606.7.4.2.3.1.4
Value as integer.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.7.4.2.3.1.5
Timestamp of last update or change
according to operating time cmcIIIUnitUpTime.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2606.7.4.2.3.1.6
.1.3.6.1.4.1.2606.7.4.2.4 · 1 row entry · 6 columns
Uses the rittal variant from /opt/observium/mibs/rittal.
Command help
Walk cmcIIIVarByQualityTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RITTAL-CMC-III-MIB' -M '/opt/observium/mibs/rittal:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RITTAL-CMC-III-MIB::cmcIIIVarByQualityTable'
Headline of variable by quality table.
cmcIIIVarByQualityEntry row .1.3.6.1.4.1.2606.7.4.2.4.1
Entries of variable by quality table.
The view of this table may be reduced using the bits of cmcIIIVarByQualityHide.
Column Syntax OID
Quality of variable.
Enumeration
Enumerated Values:
1undefined
2ok
3warning
4alarm
5info
21undefinedNoValue
22okNoValue
23warningNoValue
24alarmNoValue
25infoNoValue
.1.3.6.1.4.1.2606.7.4.2.4.1.1
Index for the device. Its value ranges
between 1 and the value of cmcIIINumberOfDevs.
Unsigned32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.7.4.2.4.1.2
Index for the list of value entries. Its value ranges
between 1 and the value of cmcIIINumberOfVars.
Unsigned32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.7.4.2.4.1.3
Value as string, including sign (+/-) and unit (degree C).
OctetString
Constraints:
range: 0-40
.1.3.6.1.4.1.2606.7.4.2.4.1.4
Value as integer.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.7.4.2.4.1.5
Timestamp of last update or change
according to operating time cmcIIIUnitUpTime.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2606.7.4.2.4.1.6
.1.3.6.1.4.1.2606.7.4.2.5 · 1 row entry · 4 columns
Uses the rittal variant from /opt/observium/mibs/rittal.
Command help
Walk cmcIIIVarIntDynTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RITTAL-CMC-III-MIB' -M '/opt/observium/mibs/rittal:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RITTAL-CMC-III-MIB::cmcIIIVarIntDynTable'
Headline of dynamically changed variable table of cmcIIIVarDatatype int(2) or enum(4).
This table is updated each cmcIIIVarDynUpdateRate seconds only.
This table has variables updated/changed within the last cmcIIIVarDynUpdateHistory seconds only.
This table has dynamic integer variables (cmcIIIVarDataType = int(2) or enum(4)) only.
cmcIIIVarIntDynEntry row .1.3.6.1.4.1.2606.7.4.2.5.1
Entries of dynamically changed table.
Column Syntax OID
Index for the device. Its value ranges
between 1 and the value of cmcIIINumberOfDevs.
Unsigned32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.7.4.2.5.1.1
Index for the list of value entries. Its value ranges
between 1 and the value of cmcIIINumberOfVars.
Unsigned32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.7.4.2.5.1.2
Timestamp of last update or change
according to operating time cmcIIIUnitUpTime.
Entries may be restricted by cmcIIIDynUpdateHistory.
Unsigned32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.2606.7.4.2.5.1.3
Value as integer.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.7.4.2.5.1.4
.1.3.6.1.4.1.2606.7.4.2.6 · 1 row entry · 4 columns
Uses the rittal variant from /opt/observium/mibs/rittal.
Command help
Walk cmcIIIVarStrDynTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RITTAL-CMC-III-MIB' -M '/opt/observium/mibs/rittal:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RITTAL-CMC-III-MIB::cmcIIIVarStrDynTable'
Headline of dynamically changed variable table of cmcIIIVarDataType string(3).
This table is updated each cmcIIIVarDynUpdateRate seconds only.
This table has variables updated/changed within the last cmcIIIVarDynUpdateHistory seconds only.
This table has dynamic string variables (cmcIIIVarDataType = string(3)) only.
Please note, this table will be empty in most cases as strings are rarely changing.
cmcIIIVarStrDynEntry row .1.3.6.1.4.1.2606.7.4.2.6.1
Entries of dynamically changed table.
Column Syntax OID
Index for the device. Its value ranges
between 1 and the value of cmcIIINumberOfDevs.
Unsigned32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.7.4.2.6.1.1
Index for the list of value entries. Its value ranges
between 1 and the value of cmcIIINumberOfVars.
Unsigned32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.7.4.2.6.1.2
Timestamp of last update or change
according to operating time cmcIIIUnitUpTime.
Entries may be restricted by cmcIIIDynUpdateHistory.
Unsigned32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.2606.7.4.2.6.1.3
Value as string.
OctetString
Constraints:
range: 0-40
.1.3.6.1.4.1.2606.7.4.2.6.1.4
.1.3.6.1.4.1.2606.7.4.3.2 · 1 row entry · 16 columns
Uses the rittal variant from /opt/observium/mibs/rittal.
Command help
Walk cmcIIIMsgTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RITTAL-CMC-III-MIB' -M '/opt/observium/mibs/rittal:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RITTAL-CMC-III-MIB::cmcIIIMsgTable'
Headline of message table.
cmcIIIMsgEntry row .1.3.6.1.4.1.2606.7.4.3.2.1
Entries of message table.
Column Syntax OID
Index for the device. Its value ranges
between 1 and the value of cmcIIINumberOfDevs.
Unsigned32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.7.4.3.2.1.1
Index for the list of message entries. Its value ranges
between 1 and the value of cmcIIINumberOfMsgs.
Unsigned32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.7.4.3.2.1.2
Text for each message (entry in the table).
OctetString
Constraints:
range: 0-40
.1.3.6.1.4.1.2606.7.4.3.2.1.3
Actual message status
1: not available
2: configuration has changed (sensor new, changed, lost)
3: error
4: OK
5: alarm, e.g. smoke, vibration...
6: warning of analog value, value reached high warning threshold
7: analo…
Enumeration
Enumerated Values:
1notAvail
2configChanged
3error
4ok
5alarm
6highWarn
7lowAlarm
8highAlarm
9lowWarn
10setOff
11setOn
12open
13closed
14locked
15unlRemote
16doorOpen
17service
18standby
19busy
20noAccess
21lost
22detected
23lowVoltage
24probeopen
25probeshort
26calibration
27inactive
28active
29noPower
30readOnly
31exchanged
32valveOpen
33warning
34remote
.1.3.6.1.4.1.2606.7.4.3.2.1.4
Setup of Alarm relay for this message/alarm
1: no switching of alarm relay
2: switching of alarm relay.
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.7.4.3.2.1.5
Setup of Alarm beeper for this alarm
1: no audible alarm
2: audible alarm.
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.7.4.3.2.1.6
Each bit is representing an entry of cmcIIITrapReceiverTable.
If the corresponding cmcIIITrapReceiverStatus is enabled
setting this bit enables sending messages to this receiver.
Bitsr/w
Enumerated Values:
0receiver1
1receiver2
2receiver3
3receiver4
4receiver5
5receiver6
6receiver7
7receiver8
8receiver9
9receiver10
10receiver11
11receiver12
12receiver13
13receiver14
14receiver15
15receiver16
.1.3.6.1.4.1.2606.7.4.3.2.1.7
Each bit is representing an entry of cmcIIISmtpReceiverTable.
If the corresponding cmcIIISmtpReceiverStatus is enabled
setting this bit enables sending messages to this receiver.
Bitsr/w
Enumerated Values:
0receiver1
1receiver2
2receiver3
3receiver4
4receiver5
5receiver6
6receiver7
7receiver8
8receiver9
9receiver10
10receiver11
11receiver12
12receiver13
13receiver14
14receiver15
15receiver16
.1.3.6.1.4.1.2606.7.4.3.2.1.8
Each bit is representing an entry of cmcIIISmsReceiverTable.
If the corresponding cmcIIISmsReceiverStatus is enabled
setting this bit enables sending messages to this receiver.
Bitsr/w
Enumerated Values:
0receiver1
1receiver2
2receiver3
3receiver4
4receiver5
5receiver6
6receiver7
7receiver8
8receiver9
9receiver10
10receiver11
11receiver12
12receiver13
13receiver14
14receiver15
15receiver16
.1.3.6.1.4.1.2606.7.4.3.2.1.9
Reset of this alarm
1: auto
2: manual, alarm needs confirmation, e. g. with 'C' key.
Enumerationr/w
Enumerated Values:
1auto
2manual
.1.3.6.1.4.1.2606.7.4.3.2.1.10
Delay of alarm condition.
SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2606.7.4.3.2.1.11
Alarm condition disabled by scheduler.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.7.4.3.2.1.12
Quality of variable.
Enumeration
Enumerated Values:
1undefined
2ok
3warning
4alarm
5info
21undefinedNoValue
22okNoValue
23warningNoValue
24alarmNoValue
25infoNoValue
.1.3.6.1.4.1.2606.7.4.3.2.1.13
Index of variable 'Status' in variable table generating this message.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.7.4.3.2.1.14
Index of variable 'Value' in the variable table.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.7.4.3.2.1.15
Message status text.
OctetString
Constraints:
range: 0-160
.1.3.6.1.4.1.2606.7.4.3.2.1.16
.1.3.6.1.4.1.2606.7.4.4.2 · 1 row entry · 22 columns
Uses the rittal variant from /opt/observium/mibs/rittal.
Command help
Walk cmcIIIDrcTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RITTAL-CMC-III-MIB' -M '/opt/observium/mibs/rittal:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RITTAL-CMC-III-MIB::cmcIIIDrcTable'
Headline of DRC table.
cmcIIIDrcEntry row .1.3.6.1.4.1.2606.7.4.4.2.1
Entries of DRC table.
Indexes
Column Syntax OID
Index for the DRC. Its value ranges
between 1 and the value of cmcIIINumberOfDrcs.
Unsigned32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.7.4.4.2.1.1
DRC status of device.
Enumeration
Enumerated Values:
1notAvail
2configChanged
3error
4ok
5alarm
17service
21lost
22detected
.1.3.6.1.4.1.2606.7.4.4.2.1.2
Timestamp of last DRC change
according to operating time cmcIIIUnitUpTime.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2606.7.4.4.2.1.3
Unit of Installation of DRC.
OctetStringr/w
Constraints:
range: 0-10
.1.3.6.1.4.1.2606.7.4.4.2.1.4
Location of Installation of DRC.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.2606.7.4.4.2.1.5
Building of Installation of DRC.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.2606.7.4.4.2.1.6
Level of Installation of DRC.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.2606.7.4.4.2.1.7
Room of Installation of DRC.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.2606.7.4.4.2.1.8
Row of Installation of DRC.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.2606.7.4.4.2.1.9
Rack number of Installation of DRC.
OctetStringr/w
Constraints:
range: 0-8
.1.3.6.1.4.1.2606.7.4.4.2.1.10
Manufacture date of DRC, format DD.MM.YYYY.
OctetString
Constraints:
range: 0-10
.1.3.6.1.4.1.2606.7.4.4.2.1.11
Serial number of DRC.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2606.7.4.4.2.1.12
Operational hours of DRC.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2606.7.4.4.2.1.13
Number of RUs.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2606.7.4.4.2.1.14
Percentage of occupied RUs.
Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.2606.7.4.4.2.1.15
Total Power in Watts, calculated from all cmcIIIDrcPower -values.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2606.7.4.4.2.1.16
Software version of controller.
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.2606.7.4.4.2.1.17
Software version of controller bootloader.
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.2606.7.4.4.2.1.18
Firmware version of controller.
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.2606.7.4.4.2.1.19
Software version of antenna module.
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.2606.7.4.4.2.1.20
Software version of antenna modul bootloader.
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.2606.7.4.4.2.1.21
Command (to) send to the DRC
1: no Quit command
2: Quit command
3: LED auto, LED will show status of TAG (detected, lost..)
4: LEDs of occupied RUs will be switched on
5: LEDs of free RUs will be switched on.
Enumerationr/w
Enumerated Values:
1noQuit
2quit
3ledAuto
4ledOnOccupied
5ledOnFreeRU
.1.3.6.1.4.1.2606.7.4.4.2.1.22
.1.3.6.1.4.1.2606.7.4.4.3 · 1 row entry · 32 columns
Uses the rittal variant from /opt/observium/mibs/rittal.
Command help
Walk cmcIIITagTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RITTAL-CMC-III-MIB' -M '/opt/observium/mibs/rittal:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RITTAL-CMC-III-MIB::cmcIIITagTable'
Headline of DRC Tag table.
cmcIIITagEntry row .1.3.6.1.4.1.2606.7.4.4.3.1
Entries of tag table.
Column Syntax OID
Index for the DRC. Its value ranges
between 1 and the value of cmcIIINumberOfDrcs.
Unsigned32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.7.4.4.3.1.1
Index for the RU of this DRC. This is the RU for this tag.
Unsigned32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.7.4.4.3.1.2
Status of the unit at this RU.
Enumeration
Enumerated Values:
1notAvail
2configChanged
3error
4ok
5alarm
17service
21lost
22detected
.1.3.6.1.4.1.2606.7.4.4.3.1.3
UID of the tag of the unit mounted at this position (RU).
OctetString
Constraints:
range: 0-16
.1.3.6.1.4.1.2606.7.4.4.3.1.4
Tag position within this RU, 0,1 or 2.
0: topmost position
1: middle position
2: lowermost position.
Unsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.2606.7.4.4.3.1.5
Formfactor of the chassis (number of RUs).
Unsigned32r/w
Constraints:
range: 0-9999
.1.3.6.1.4.1.2606.7.4.4.3.1.6
Tag offset.
Offset of the tag related to the topmost position (in one-third of a RU).
Unsigned32r/w
Constraints:
range: 0-9999
.1.3.6.1.4.1.2606.7.4.4.3.1.7
Position (RU) of the chassis.
Unsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.2606.7.4.4.3.1.8
Class of the device.
Enumerationr/w
Enumerated Values:
1notDefined
2blankingPlate
3componentShelf
4cableRouting
5patchPanelCatX
6patchPanelFibreOptic
7ups
8powerSupply
9kvm
10switch
11monitorKeyboardDrawer
12monitor
13server
14storage
.1.3.6.1.4.1.2606.7.4.4.3.1.9
Description name of the unit at this RU.
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.2606.7.4.4.3.1.10
Manufacturer of the unit at this RU.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.2606.7.4.4.3.1.11
Type Name of the unit at this RU.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.2606.7.4.4.3.1.12
Serial number of the Unit at this RU.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.2606.7.4.4.3.1.13
Vendor of the unit at this RU.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.2606.7.4.4.3.1.14
MAC address 1 of the Unit at this RU.
OctetStringr/w
Constraints:
range: 0-17
.1.3.6.1.4.1.2606.7.4.4.3.1.15
MAC address 2 of the unit at this RU.
OctetStringr/w
Constraints:
range: 0-17
.1.3.6.1.4.1.2606.7.4.4.3.1.16
Vendor contact of the unit at this RU.
OctetStringr/w
Constraints:
range: 0-64
.1.3.6.1.4.1.2606.7.4.4.3.1.17
Name of Unit at this RU.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.2606.7.4.4.3.1.18
Inventory code of the unit at this RU.
OctetStringr/w
Constraints:
range: 0-200
.1.3.6.1.4.1.2606.7.4.4.3.1.19
Power in Watts of the unit at this RU.
SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2606.7.4.4.3.1.20
Current in Amperes*10 of the unit at this RU.
SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2606.7.4.4.3.1.21
Voltage in Volts of the unit at this RU.
SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2606.7.4.4.3.1.22
Last service of the unit at this RU.
OctetStringr/w
Constraints:
range: 0-40
.1.3.6.1.4.1.2606.7.4.4.3.1.23
Next service of the Unit at this RU.
OctetStringr/w
Constraints:
range: 0-40
.1.3.6.1.4.1.2606.7.4.4.3.1.24
Last update of the unit at this RU.
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.2606.7.4.4.3.1.25
Next update of the unit at this RU.
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.2606.7.4.4.3.1.26
Initial start (YYYYMMDD) of the unit at this RU.
OctetStringr/w
Constraints:
range: 0-8
.1.3.6.1.4.1.2606.7.4.4.3.1.27
Custom field of the unit at this RU.
OctetStringr/w
Constraints:
range: 0-40
.1.3.6.1.4.1.2606.7.4.4.3.1.28
Command (to) send to the unit at this RU.
Enumerationr/w
Enumerated Values:
1noQuit
2quit
3ledAuto
4ledOn
.1.3.6.1.4.1.2606.7.4.4.3.1.29
Start position (bottom) of the chassis of this tag.
The resolution is one-third of a RU.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2606.7.4.4.3.1.30
End position (top) of the chassis of this tag.
The resolution is one-third of a RU.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2606.7.4.4.3.1.31
Tag position mapping to the antennas.
The resolution is one-third of a RU, one RU has three antennas.
Position 1 is at the bottom of the rack.
This value ranges from 1 to cmcIIIDrcNumberOfRU*3.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2606.7.4.4.3.1.32
.1.3.6.1.4.1.2606.7.4.5.2 · 1 row entry · 5 columns
Uses the rittal variant from /opt/observium/mibs/rittal.
Command help
Walk cmcIIIFileTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RITTAL-CMC-III-MIB' -M '/opt/observium/mibs/rittal:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RITTAL-CMC-III-MIB::cmcIIIFileTable'
Headline of file table.
cmcIIIFileEntry row .1.3.6.1.4.1.2606.7.4.5.2.1
Entries of file table.
Indexes
Column Syntax OID
Index for the file. Its value ranges
between 1 and the value of cmcIIINumberOfFiles.
Unsigned32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.7.4.5.2.1.1
Timestamp of last file change
according to operating time cmcIIIUnitUpTime.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2606.7.4.5.2.1.2
Size of the file in bytes.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2606.7.4.5.2.1.3
Checksum of the file.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2606.7.4.5.2.1.4
Name of the file.
OctetString
Constraints:
range: 0-40
.1.3.6.1.4.1.2606.7.4.5.2.1.5