PM-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
8
Rows
8
Columns
242
.1.3.6.1.4.1.10418.17.2.2.2 · 1 row entry · 8 columns
Uses the vertiv variant from /opt/observium/mibs/vertiv.
Command help
Walk pmActiveSessionsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PM-MIB' -M '/opt/observium/mibs/vertiv:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PM-MIB::pmActiveSessionsTable'
This table contains the list of active sessions.
pmActiveSessionsTableEntry row .1.3.6.1.4.1.10418.17.2.2.2.1
each entry has the information about the active session
Column Syntax OID
A unique index representing an entry in this table.
IF-MIBInterfaceIndexOrZero
Type Constraints:
range: 0..2147483647
Description:
This textual convention is an extension of the
InterfaceIndex convention. The latter defines a greater
than zero value used to identify an interface or interface
sub-layer in the managed system. This extension permits…
.1.3.6.1.4.1.10418.17.2.2.2.1.1
The name of the user that opens this session.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.10418.17.2.2.2.1.2
The name of the group that the user belongs to.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.10418.17.2.2.2.1.3
The session type.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.10418.17.2.2.2.1.4
Connection type.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.10418.17.2.2.2.1.5
Time of the session
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.10418.17.2.2.2.1.6
The source IP address of the session.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.10418.17.2.2.2.1.7
A set value of killSession(2) will kill the session.
noAction(1) = always returned in a GET. Does nothing if SET.
killSession(2)= when SET the appliance immediately kills the session.
Enumerationr/w
Enumerated Values:
1noAction
2killSession
.1.3.6.1.4.1.10418.17.2.2.2.1.8
.1.3.6.1.4.1.10418.17.2.5.2 · 1 row entry · 12 columns
Uses the vertiv variant from /opt/observium/mibs/vertiv.
Command help
Walk pmPowerMgmtSerialTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PM-MIB' -M '/opt/observium/mibs/vertiv:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PM-MIB::pmPowerMgmtSerialTable'
Information about each serial port thas has PDU connect.
pmPowerMgmtSerialTableEntry row .1.3.6.1.4.1.10418.17.2.5.2.1
Information about each serial port thas has PDU connect.
Column Syntax OID
The index of the register.
IF-MIBInterfaceIndex
Type Constraints:
range: 1..2147483647
Description:
A unique value, greater than zero, for each interface or
interface sub-layer in the managed system. It is
recommended that values are assigned contiguously starting
from 1. The value for each interface sub-layer must …
.1.3.6.1.4.1.10418.17.2.5.2.1.1
The number of the serial port when the PDU is connected.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.2.1.2
The device name of this serial port.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.2.1.3
Total number of units connected in this serial port.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.2.1.4
set/get buzzer(s) on or off for the chain.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.2.1.10
set/get syslog on or off for the chain.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.2.1.11
set/get over current proctection on or off for the chain.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.2.1.12
set/get cycle interval for the chain in whole seconds.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.2.1.13
set/get the poll rate for the chain in whole seconds.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.2.1.14
set the global password for admin user
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.2.1.15
noAction(1) = always returned in a GET. Does nothing if SET.
save(2) = when SET the save command is sent to PDU.
Enumerationr/w
Enumerated Values:
1noAction
2save
.1.3.6.1.4.1.10418.17.2.5.2.1.20
noAction(1) = always returned in a GET. Does nothing if SET.
restore(2) = when SET the restore command is sent to PDU.
Enumerationr/w
Enumerated Values:
1noAction
2restore
.1.3.6.1.4.1.10418.17.2.5.2.1.21
.1.3.6.1.4.1.10418.17.2.5.3 · 1 row entry · 76 columns
Uses the vertiv variant from /opt/observium/mibs/vertiv.
Command help
Walk pmPowerMgmtPDUTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PM-MIB' -M '/opt/observium/mibs/vertiv:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PM-MIB::pmPowerMgmtPDUTable'
This table contains the list of detected PDUs.
pmPowerMgmtPDUTableEntry row .1.3.6.1.4.1.10418.17.2.5.3.1
each entry has the information about the PDU.
Column Syntax OID
Number of serial port when the PDU is connected.
IF-MIBInterfaceIndex
Type Constraints:
range: 1..2147483647
Description:
A unique value, greater than zero, for each interface or
interface sub-layer in the managed system. It is
recommended that values are assigned contiguously starting
from 1. The value for each interface sub-layer must …
.1.3.6.1.4.1.10418.17.2.5.3.1.1
A PDU position in the chain.
IF-MIBInterfaceIndexOrZero
Type Constraints:
range: 0..2147483647
Description:
This textual convention is an extension of the
InterfaceIndex convention. The latter defines a greater
than zero value used to identify an interface or interface
sub-layer in the managed system. This extension permits…
.1.3.6.1.4.1.10418.17.2.5.3.1.2
PDU identification.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.3.1.3
Name of serial port when the PDU is connected.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.3.1.4
Model of the PDU.
Returns N/A if not applicable.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.3.1.5
Vendor of the PDU.
Returns N/A if not applicable.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.3.1.6
Version of the PDU firmware.
Returns N/A if not applicable.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.3.1.7
Number of outlets of the PDU.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.8
Number of current sensors in the PDU.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.9
Current of the sensor 1 in this PDU unit in AMP.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current is 0.5 AMP.).
This OID is obsoleted. Th…
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.10
Maximum current of the sensor 1 in this PDU unit in AMP.
When the PDU does not have support for maximum value,
the value will be 0.
The value of this object is the actual current in
AMP * 10. You need to translate the …
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.11
Current of the sensor 2 in this PDU unit in AMP.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current is 0.5 AMP.).
This OID is obsoleted. T…
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.12
Maximum current of the sensor 2 in this PDU unit in AMP.
When the PDU does not have support for maximum value,
the value will be 0.
The value of this object is the actual current in
AMP * 10. You need to translate the …
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.13
Current of the sensor 3 in this PDU unit in AMP.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current is 0.5 AMP.)
This OID is obsoleted. Th…
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.14
Maximum current of the sensor 3 in this PDU unit in AMP.
When the PDU does not have support for maximum value,
the value will be 0.
The value of this object is the actual current in
AMP * 10. You need to translate the …
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.15
Number of temperature sensors in the PDU.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.16
Temperature of this PM unit in Celsius degrees.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, the temperature is 24 Celsius.)
If the …
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.17
Maximum temperature detected in this PM unit in Celsius degrees.
The value will be Zero when the PDU does not have support for maximum value.
The value of this object is the actual temperature in
degrees C * 10. You …
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.18
Temperature of this PM unit in Celsius degrees.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, the temperature is 24 Celsius.)
If the …
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.19
Maximum temperature detected in this PM unit in Celsius degrees.
The value will be Zero when the PDU does not have support for maximum value.
The value of this object is the actual temperature in
degrees C * 10. You ne…
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.20
Temperature of this PM unit in Celsius degrees.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, the temperature is 24 Celsius.)
If the …
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.21
Maximum temperature detected in this PM unit in Celsius degrees.
The value will be Zero when the PDU does not have support for maximum value.
The value of this object is the actual temperature in
degrees C * 10. You …
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.22
Number of humidity sensors in the PDU.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.23
Humidity of this PM unit .
If the humidity measurement is not installed this
value will be 0.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.24
Maximum humidity detected in this PM unit.
If the humidity measurement is not installed or the PDU does not have support for maximum value this
value will be 0.
Set with Zero value to clear the max. temperature.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.25
Humidity of this PM unit .
If the humidity measurement is not installed this
value will be 0.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.26
Maximum humidity detected in this PM unit.
If the humidity measurement is not installed or the PDU does not have support for maximum value this
value will be 0.
Set with Zero value to clear the max. temperature.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.27
Humidity of this PM unit .
If the humidity measurement is not installed this
value will be 0.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.28
Maximum humidity detected in this PM unit.
If the humidity measurement is not installed or the PDU does not have support for maximum value this
value will be 0.
Set with Zero value to clear the max. temperature.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.29
Number of voltage sensors in the PDU.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.30
Voltage of this sensor in this PDU unit.
This OID is obsoleted. The value can be retrieved
from pmPowerMgmtPDUTableVoltageValue,
pmPowerMgmtPhasesTableVoltageValue, or
pmPowerMgmtOutletsTableVoltageValue
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.31
Maximum voltage of this sensor in this PDU unit.
Set with Zero value to clear the maximum voltage.
This OID is obsoleted. The value can be retrieved
from pmPowerMgmtPDUTableVoltageMax,
pmPowerMgmtPhasesTableVoltageMax…
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.32
Voltage of this sensor in this PDU unit.
This OID is obsoleted. The value can be retrieved
from pmPowerMgmtPDUTableVoltageValue,
pmPowerMgmtPhasesTableVoltageValue, or
pmPowerMgmtOutletsTableVoltageValue
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.33
Maximum voltage of this sensor in this PDU unit.
Set with Zero value to clear the maximum voltage.
This OID is obsoleted. The value can be retrieved
from pmPowerMgmtPDUTableVoltageMax,
pmPowerMgmtPhasesTableVoltageMax…
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.34
Voltage of this sensor in this PDU unit.
This OID is obsoleted. The value can be retrieved
from pmPowerMgmtPDUTableVoltageValue,
pmPowerMgmtPhasesTableVoltageValue, or
pmPowerMgmtOutletsTableVoltageValue
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.35
Maximum voltage of this sensor in this PDU unit.
Set with Zero value to clear the maximum voltage.
This OID is obsoleted. The value can be retrieved
from pmPowerMgmtPDUTableVoltageMax,
pmPowerMgmtPhasesTableVoltageMax…
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.36
Number of phases of the PDU.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.37
Number of banks in the PDU.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.38
Number of sensors in the PDU.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.40
A set value of 2 will set the PDU to factory default settings.
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the factory default command is sent to the PDU.
Enumerationr/w
Enumerated Values:
1noAction
2reset
.1.3.6.1.4.1.10418.17.2.5.3.1.41
PDUs cold start delay in whole seconds (0-60).
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.42
A set value of power*(2) will send command to PDU.
noAction(1) = always returned in a GET. Does nothing if SET.
reboot(2) = when SET the reboot command is sent to PDU.
Enumerationr/w
Enumerated Values:
1noAction
2reboot
.1.3.6.1.4.1.10418.17.2.5.3.1.43
Maximum value of current allowed in the PDU (A x 10).
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.44
Show the PDU alarm status.
Returns 0 if not supported.
Enumeration
Enumerated Values:
1normal
2blow-fuse
3hw-ocp
4high-critical
5high-warning
6low-warning
7low-critical
.1.3.6.1.4.1.10418.17.2.5.3.1.45
Actual value of current in the PDU (A x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.50
Maximum value of current in the PDU (A x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.51
Minimum value of current in the PDU (A x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.52
Average value of current in the PDU (A x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.53
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU.
Enumerationr/w
Enumerated Values:
1noAction
2reset
.1.3.6.1.4.1.10418.17.2.5.3.1.54
Actual value of power in the PDU (W x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.60
Maximum value of power in the PDU (W x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.61
Minimum value of power in the PDU (W x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.62
Average value of power in the PDU (W x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.63
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU.
Enumerationr/w
Enumerated Values:
1noAction
2reset
.1.3.6.1.4.1.10418.17.2.5.3.1.64
Type of power values.
Returns 0 if not supported.
Enumeration
Enumerated Values:
0none-sensor
1estimated
2measured
.1.3.6.1.4.1.10418.17.2.5.3.1.65
Actual value of voltage in the PDU (V).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.70
Maximum value of voltage in the PDU (V).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.71
Minimum value of voltage in the PDU (V).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.72
Average value of voltage in the PDU (V).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.73
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU.
Enumerationr/w
Enumerated Values:
1noAction
2reset
.1.3.6.1.4.1.10418.17.2.5.3.1.74
Type of voltage values.
Returns 0 if not supported.
Enumeration
Enumerated Values:
0none-sensor
1estimated
2measured
.1.3.6.1.4.1.10418.17.2.5.3.1.75
Actual value of power factor in the PDU (Pf x 100).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.80
Maximum value of power factor in the PDU (Pf x 100).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.81
Minimum value of power factor in the PDU (Pf x 100).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.82
Average value of power factor in the PDU (Pf x 100).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.83
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU.
Enumerationr/w
Enumerated Values:
1noAction
2reset
.1.3.6.1.4.1.10418.17.2.5.3.1.84
Type of power values.
Returns 0 if not supported.
Enumeration
Enumerated Values:
0none-sensor
1estimated
2measured
.1.3.6.1.4.1.10418.17.2.5.3.1.85
A set value of power*(2-4) will send command to PDU.
noAction(1) = always returned in a GET. Does nothing if SET.
powerOn(2) = when SET the power On command is sent to PDU.
powerOff(3) = when SET the power Off command …
Enumerationr/w
Enumerated Values:
1noAction
2powerOn
3powerOff
4powerCycle
.1.3.6.1.4.1.10418.17.2.5.3.1.90
A set value of power*(2) will send command to PDU.
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU.
Returns 0 if not supported.
Enumerationr/w
Enumerated Values:
1noAction
2reset
.1.3.6.1.4.1.10418.17.2.5.3.1.91
outlet high critical (alarm) current threshold (A x 10).
Set fails if value is lower that CurrentHighWarning.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.100
outlet high warning current threshold (A x 10).
Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.101
outlet low warning current threshold (A x 10).
Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.102
outlet low critical current threshold (A x 10).
Set fails if value is higher than CurrentLowWarning.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.103
pdu energy value (Wh).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.3.1.105
time at which energy calculation commenced (ISO8601 format).
Returns N/A if not applicable.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.3.1.106
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU.
Enumerationr/w
Enumerated Values:
1noAction
2reset
.1.3.6.1.4.1.10418.17.2.5.3.1.107
.1.3.6.1.4.1.10418.17.2.5.5 · 1 row entry · 41 columns
Uses the vertiv variant from /opt/observium/mibs/vertiv.
Command help
Walk pmPowerMgmtOutletsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PM-MIB' -M '/opt/observium/mibs/vertiv:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PM-MIB::pmPowerMgmtOutletsTable'
This table contains the information about outlets.
pmPowerMgmtOutletsTableEntry row .1.3.6.1.4.1.10418.17.2.5.5.1
each entry has the information about the outlet.
Column Syntax OID
Serial Port number.
IF-MIBInterfaceIndex
Type Constraints:
range: 1..2147483647
Description:
A unique value, greater than zero, for each interface or
interface sub-layer in the managed system. It is
recommended that values are assigned contiguously starting
from 1. The value for each interface sub-layer must …
.1.3.6.1.4.1.10418.17.2.5.5.1.1
Index.
IF-MIBInterfaceIndex
Type Constraints:
range: 1..2147483647
Description:
A unique value, greater than zero, for each interface or
interface sub-layer in the managed system. It is
recommended that values are assigned contiguously starting
from 1. The value for each interface sub-layer must …
.1.3.6.1.4.1.10418.17.2.5.5.1.2
Number of the outlet in the PDU.
IF-MIBInterfaceIndex
Type Constraints:
range: 1..2147483647
Description:
A unique value, greater than zero, for each interface or
interface sub-layer in the managed system. It is
recommended that values are assigned contiguously starting
from 1. The value for each interface sub-layer must …
.1.3.6.1.4.1.10418.17.2.5.5.1.3
Name of the outlet.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.5.1.4
Status of the outlet.
Returns 0 if not supported.
Enumeration
Enumerated Values:
1off
2on
3offLocked
4onLocked
5offCycle
6onPendingOff
7offPendingOn
8onPendingCycle
9notSet
10onFixed
11offShutdown
12tripped
.1.3.6.1.4.1.10418.17.2.5.5.1.5
A set value of power*(2-6) will send command to PDU.
noAction(1) = always returned in a GET. Does nothing if SET.
powerOn(2) = when SET the power On command is sent to PDU.
powerOff(3) = when SET the power Off command …
Enumerationr/w
Enumerated Values:
1noAction
2powerOn
3powerOff
4powerCycle
5powerLock
6powerUnlock
.1.3.6.1.4.1.10418.17.2.5.5.1.6
Serial Port Name where the PDU is connected.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.5.1.7
PDU identification.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.5.1.8
post on delay for the outlet (seconds x 10)
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.5.1.9
post off delay for the outlet (seconds x 10)
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.5.1.10
Show the outlet alarm status.
Returns 0 if not supported.
Enumeration
Enumerated Values:
1normal
2blow-fuse
3hw-ocp
4high-critical
5high-warning
6low-warning
7low-critical
.1.3.6.1.4.1.10418.17.2.5.5.1.45
Actual value of current in the outlet (A x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.5.1.50
Maximum value of current in the outlet (A x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.5.1.51
Minimum value of current in the outlet (A x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.5.1.52
Average value of current in the outlet (A x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.5.1.53
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU.
Enumerationr/w
Enumerated Values:
1noAction
2reset
.1.3.6.1.4.1.10418.17.2.5.5.1.54
Actual value of power in the outlet (W x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.5.1.60
Maximum value of power in the outlet (W x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.5.1.61
Minimum value of power in the outlet (W x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.5.1.62
Average value of power in the outlet (W x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.5.1.63
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU.
Enumerationr/w
Enumerated Values:
1noAction
2reset
.1.3.6.1.4.1.10418.17.2.5.5.1.64
Type of power values.
Returns 0 if not supported.
Enumeration
Enumerated Values:
0none-sensor
1estimated
2measured
.1.3.6.1.4.1.10418.17.2.5.5.1.65
Actual value of voltage in the outlet (V).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.5.1.70
Maximum value of voltage in the outlet (V).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.5.1.71
Minimum value of voltage in the outlet (V).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.5.1.72
Average value of voltage in the outlet (V).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.5.1.73
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU.
Enumerationr/w
Enumerated Values:
1noAction
2reset
.1.3.6.1.4.1.10418.17.2.5.5.1.74
Type of voltage values.
Returns 0 if not supported.
Enumeration
Enumerated Values:
0none-sensor
1estimated
2measured
.1.3.6.1.4.1.10418.17.2.5.5.1.75
Actual value of power factor in the outlet (Pf x 100).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.5.1.80
Maximum value of power factor in the outlet (Pf x 100).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.5.1.81
Minimum value of power factor in the outlet (Pf x 100).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.5.1.82
Average value of power factor in the outlet (Pf x 100).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.5.1.83
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU.
Enumerationr/w
Enumerated Values:
1noAction
2reset
.1.3.6.1.4.1.10418.17.2.5.5.1.84
Type of power factor values.
Returns 0 if not supported.
Enumeration
Enumerated Values:
0none-sensor
1estimated
2measured
.1.3.6.1.4.1.10418.17.2.5.5.1.85
outlet high critical (alarm) current threshold (A x 10).
Set fails if value is lower that CurrentHighWarning.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.5.1.100
outlet high warning current threshold (A x 10).
Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.5.1.101
outlet low warning current threshold (A x 10).
Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.5.1.102
outlet low critical current threshold (A x 10).
Set fails if value is higher than CurrentLowWarning.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.5.1.103
outlet energy value (Wh).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.5.1.105
time at which energy calculation commenced (ISO8601 format).
Returns N/A if not applicable.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.5.1.106
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU.
Enumerationr/w
Enumerated Values:
1noAction
2reset
.1.3.6.1.4.1.10418.17.2.5.5.1.107
.1.3.6.1.4.1.10418.17.2.5.7 · 1 row entry · 4 columns
Uses the vertiv variant from /opt/observium/mibs/vertiv.
Command help
Walk pmPowerMgmtGroupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PM-MIB' -M '/opt/observium/mibs/vertiv:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PM-MIB::pmPowerMgmtGroupTable'
This table contains the information about group of outlets.
pmPowerMgmtGroupTableEntry row .1.3.6.1.4.1.10418.17.2.5.7.1
each entry has the information about group of outlets.
Column Syntax OID
Index of the group.
IF-MIBInterfaceIndexOrZero
Type Constraints:
range: 0..2147483647
Description:
This textual convention is an extension of the
InterfaceIndex convention. The latter defines a greater
than zero value used to identify an interface or interface
sub-layer in the managed system. This extension permits…
.1.3.6.1.4.1.10418.17.2.5.7.1.1
Name of the group of outlets.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.7.1.2
Status of the group of outlet.
Enumeration
Enumerated Values:
1off
2on
.1.3.6.1.4.1.10418.17.2.5.7.1.3
A set value of power*(2-4) will send command to PDU.
noAction(1) = always returned in a GET. Does nothing if SET.
powerOn(2) = when SET the power On command is sent to PDU.
powerOff(3) = when SET the power Off command …
Enumerationr/w
Enumerated Values:
1noAction
2powerOn
3powerOff
4powerCycle
.1.3.6.1.4.1.10418.17.2.5.7.1.4
.1.3.6.1.4.1.10418.17.2.5.9 · 1 row entry · 34 columns
Uses the vertiv variant from /opt/observium/mibs/vertiv.
Command help
Walk pmPowerMgmtPhasesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PM-MIB' -M '/opt/observium/mibs/vertiv:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PM-MIB::pmPowerMgmtPhasesTable'
This table contains the information about phases.
pmPowerMgmtPhasesTableEntry row .1.3.6.1.4.1.10418.17.2.5.9.1
each entry has the information about the phases.
Column Syntax OID
Serial Port number.
IF-MIBInterfaceIndex
Type Constraints:
range: 1..2147483647
Description:
A unique value, greater than zero, for each interface or
interface sub-layer in the managed system. It is
recommended that values are assigned contiguously starting
from 1. The value for each interface sub-layer must …
.1.3.6.1.4.1.10418.17.2.5.9.1.1
Index.
IF-MIBInterfaceIndex
Type Constraints:
range: 1..2147483647
Description:
A unique value, greater than zero, for each interface or
interface sub-layer in the managed system. It is
recommended that values are assigned contiguously starting
from 1. The value for each interface sub-layer must …
.1.3.6.1.4.1.10418.17.2.5.9.1.2
Number of the phase in the PDU.
IF-MIBInterfaceIndex
Type Constraints:
range: 1..2147483647
Description:
A unique value, greater than zero, for each interface or
interface sub-layer in the managed system. It is
recommended that values are assigned contiguously starting
from 1. The value for each interface sub-layer must …
.1.3.6.1.4.1.10418.17.2.5.9.1.3
Name of the phase.
Returns N/A if not applicable.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.9.1.4
Serial Port Name where the PDU is connected.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.9.1.5
PDU identification.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.9.1.6
Show the phase alarm status.
Returns 0 if not supported.
Enumeration
Enumerated Values:
1normal
2blow-fuse
3hw-ocp
4high-critical
5high-warning
6low-warning
7low-critical
.1.3.6.1.4.1.10418.17.2.5.9.1.45
Actual value of current in the phase (A x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.9.1.50
Maximum value of current in the phase (A x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.9.1.51
Minimum value of current in the phase (A x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.9.1.52
Average value of current in the phase (A x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.9.1.53
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU.
Enumerationr/w
Enumerated Values:
1noAction
2reset
.1.3.6.1.4.1.10418.17.2.5.9.1.54
Actual value of power in the phase (W x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.9.1.60
Maximum value of power in the phase (W x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.9.1.61
Minimum value of power in the phase (W x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.9.1.62
Average value of power in the phase (W x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.9.1.63
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU.
Enumerationr/w
Enumerated Values:
1noAction
2reset
.1.3.6.1.4.1.10418.17.2.5.9.1.64
Type of power values.
Returns 0 if not supported.
Enumeration
Enumerated Values:
0none-sensor
1estimated
2measured
.1.3.6.1.4.1.10418.17.2.5.9.1.65
Actual value of voltage in the phase (V).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.9.1.70
Maximum value of voltage in the phase (V).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.9.1.71
Minimum value of voltage in the phase (V).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.9.1.72
Average value of voltage in the phase (V).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.9.1.73
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU.
Enumerationr/w
Enumerated Values:
1noAction
2reset
.1.3.6.1.4.1.10418.17.2.5.9.1.74
Type of voltage values.
Returns 0 if not supported.
Enumeration
Enumerated Values:
0none-sensor
1estimated
2measured
.1.3.6.1.4.1.10418.17.2.5.9.1.75
Actual value of power factor in the phase (Pf x 100).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.9.1.80
Maximum value of power factor in the phase (Pf x 100).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.9.1.81
Minimum value of power factor in the phase (Pf x 100).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.9.1.82
Average value of power factor in the phase (Pf x 100).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.9.1.83
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU.
Enumerationr/w
Enumerated Values:
1noAction
2reset
.1.3.6.1.4.1.10418.17.2.5.9.1.84
Type of power factor values.
Returns 0 if not supported.
Enumeration
Enumerated Values:
0none-sensor
1estimated
2measured
.1.3.6.1.4.1.10418.17.2.5.9.1.85
phase high critical (alarm) current threshold (A x 10).
Set fails if value is lower that CurrentHighWarning.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.9.1.100
phase high warning current threshold (A x 10).
Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.9.1.101
phase low warning current threshold (A x 10).
Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.9.1.102
phase low critical current threshold (A x 10).
Set fails if value is higher than CurrentLowWarning.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.9.1.103
.1.3.6.1.4.1.10418.17.2.5.11 · 1 row entry · 37 columns
Uses the vertiv variant from /opt/observium/mibs/vertiv.
Command help
Walk pmPowerMgmtBanksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PM-MIB' -M '/opt/observium/mibs/vertiv:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PM-MIB::pmPowerMgmtBanksTable'
This table contains the information about banks.
pmPowerMgmtBanksTableEntry row .1.3.6.1.4.1.10418.17.2.5.11.1
each entry has the information about the banks.
Column Syntax OID
Serial Port number.
IF-MIBInterfaceIndex
Type Constraints:
range: 1..2147483647
Description:
A unique value, greater than zero, for each interface or
interface sub-layer in the managed system. It is
recommended that values are assigned contiguously starting
from 1. The value for each interface sub-layer must …
.1.3.6.1.4.1.10418.17.2.5.11.1.1
Index.
IF-MIBInterfaceIndex
Type Constraints:
range: 1..2147483647
Description:
A unique value, greater than zero, for each interface or
interface sub-layer in the managed system. It is
recommended that values are assigned contiguously starting
from 1. The value for each interface sub-layer must …
.1.3.6.1.4.1.10418.17.2.5.11.1.2
Number of the bank in the PDU.
IF-MIBInterfaceIndex
Type Constraints:
range: 1..2147483647
Description:
A unique value, greater than zero, for each interface or
interface sub-layer in the managed system. It is
recommended that values are assigned contiguously starting
from 1. The value for each interface sub-layer must …
.1.3.6.1.4.1.10418.17.2.5.11.1.3
Name of the bank.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.11.1.4
Serial Port Name where the PDU is connected.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.11.1.5
PDU identification.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.11.1.6
Show the bank alarm status.
Returns 0 if not supported.
Enumeration
Enumerated Values:
1normal
2blow-fuse
3hw-ocp
4high-critical
5high-warning
6low-warning
7low-critical
.1.3.6.1.4.1.10418.17.2.5.11.1.45
Actual value of current in the bank (A x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.11.1.50
Maximum value of current in the bank (A x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.11.1.51
Minimum value of current in the bank (A x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.11.1.52
Average value of current in the bank (A x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.11.1.53
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU.
Enumerationr/w
Enumerated Values:
1noAction
2reset
.1.3.6.1.4.1.10418.17.2.5.11.1.54
Actual value of power in the bank (W x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.11.1.60
Maximum value of power in the bank (W x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.11.1.61
Minimum value of power in the bank (W x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.11.1.62
Average value of power in the bank (W x 10).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.11.1.63
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU.
Enumerationr/w
Enumerated Values:
1noAction
2reset
.1.3.6.1.4.1.10418.17.2.5.11.1.64
Type of power values.
Returns 0 if not supported.
Enumeration
Enumerated Values:
0none-sensor
1estimated
2measured
.1.3.6.1.4.1.10418.17.2.5.11.1.65
Actual value of voltage in the bank (V).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.11.1.70
Maximum value of voltage in the bank (V).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.11.1.71
Minimum value of voltage in the bank (V).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.11.1.72
Average value of voltage in the bank (V).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.11.1.73
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU.
Enumerationr/w
Enumerated Values:
1noAction
2reset
.1.3.6.1.4.1.10418.17.2.5.11.1.74
Type of voltage values.
Returns 0 if not supported.
Enumeration
Enumerated Values:
0none-sensor
1estimated
2measured
.1.3.6.1.4.1.10418.17.2.5.11.1.75
Actual value of power factor in the bank (Pf x 100).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.11.1.80
Maximum value of power factor in the bank (Pf x 100).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.11.1.81
Minimum value of power factor in the bank (Pf x 100).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.11.1.82
Average value of power factor in the bank (Pf x 100).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.11.1.83
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU.
Enumerationr/w
Enumerated Values:
1noAction
2reset
.1.3.6.1.4.1.10418.17.2.5.11.1.84
Type of power factor values.
Returns 0 if not supported.
Enumeration
Enumerated Values:
0none-sensor
1estimated
2measured
.1.3.6.1.4.1.10418.17.2.5.11.1.85
bank high critical (alarm) current threshold (A x 10).
Set fails if value is lower that CurrentHighWarning.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.11.1.100
bank high warning current threshold (A x 10).
Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.11.1.101
bank low warning current threshold (A x 10).
Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.11.1.102
bank low critical current threshold (A x 10).
Set fails if value is higher than CurrentLowWarning.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.11.1.103
bank energy value (Wh).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.11.1.105
time at which energy calculation commenced (ISO8601 format).
Returns N/A if not applicable.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.11.1.106
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU.
Enumerationr/w
Enumerated Values:
1noAction
2reset
.1.3.6.1.4.1.10418.17.2.5.11.1.107
.1.3.6.1.4.1.10418.17.2.5.13 · 1 row entry · 30 columns
Uses the vertiv variant from /opt/observium/mibs/vertiv.
Command help
Walk pmPowerMgmtSensorsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PM-MIB' -M '/opt/observium/mibs/vertiv:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PM-MIB::pmPowerMgmtSensorsTable'
This table contains the information about sensors.
pmPowerMgmtSensorsTableEntry row .1.3.6.1.4.1.10418.17.2.5.13.1
each entry has the information about the sensors.
Column Syntax OID
Serial Port number.
IF-MIBInterfaceIndex
Type Constraints:
range: 1..2147483647
Description:
A unique value, greater than zero, for each interface or
interface sub-layer in the managed system. It is
recommended that values are assigned contiguously starting
from 1. The value for each interface sub-layer must …
.1.3.6.1.4.1.10418.17.2.5.13.1.1
Index.
IF-MIBInterfaceIndex
Type Constraints:
range: 1..2147483647
Description:
A unique value, greater than zero, for each interface or
interface sub-layer in the managed system. It is
recommended that values are assigned contiguously starting
from 1. The value for each interface sub-layer must …
.1.3.6.1.4.1.10418.17.2.5.13.1.2
Number of the sensor in the PDU.
IF-MIBInterfaceIndex
Type Constraints:
range: 1..2147483647
Description:
A unique value, greater than zero, for each interface or
interface sub-layer in the managed system. It is
recommended that values are assigned contiguously starting
from 1. The value for each interface sub-layer must …
.1.3.6.1.4.1.10418.17.2.5.13.1.3
Name of the sensor.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.13.1.4
Serial Port Name where the PDU is connected.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.13.1.5
PDU identification.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.13.1.6
The type of environmental monitor.
Returns 0 if not supported.
Enumeration
Enumerated Values:
1temp-internal
2temperature
3humidity
4air-flow
5smoke
6dry-concact
7water-level
8motion
9unplugged
10unknown
.1.3.6.1.4.1.10418.17.2.5.13.1.7
Status of digital sensors: Dry-Contact, Water level, Smoke sensor, Motion sensor.
Returns 0 if not supported.
Enumeration
Enumerated Values:
1normal
2triggered
3not-applicable
4opened
5closed
.1.3.6.1.4.1.10418.17.2.5.13.1.8
Actual value of the sensor.
Returns N/A if not applicable.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.13.1.20
Maximum value of the sensor.
Returns N/A if not applicable.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.13.1.21
Minimum value of the sensor.
Returns N/A if not applicable.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.13.1.22
Average value of the sensor.
Returns N/A if not applicable.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.10418.17.2.5.13.1.23
Actual value of the sensor.
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.13.1.25
Maximum value of the sensor.
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.13.1.26
Minimum value of the sensor.
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.13.1.27
Average value of the sensor.
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.13.1.28
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to sensor.
Enumerationr/w
Enumerated Values:
1noAction
2reset
.1.3.6.1.4.1.10418.17.2.5.13.1.30
sensor high critical (alarm) threshold (unit x 10) - use unit as returned by pmPowerMgmtSensorsTableUnit.
Set fails if value is lower that CurrentHighWarning.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.13.1.40
sensor high warning threshold (unit x 10) - use unit as returned by pmPowerMgmtSensorsTableUnit.
Set fails if value is higher than HighCritical or lower than LowWarning.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.13.1.41
sensor low warning threshold (unit x 10) - use unit as returned by pmPowerMgmtSensorsTableUnit.
Set fails if value is higher than HighWarning or lower than LowCritical.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.13.1.42
sensor low critical threshold (unit x 10) - use unit as returned by pmPowerMgmtSensorsTableUnit.
Set fails if value is higher than LowWarning.
Returns 0 if not supported.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.13.1.43
sensor unit.
Returns 0 if not supported.
Enumerationr/w
Enumerated Values:
1undefined
2fahrenheit
3celsius
4percent
5afu
.1.3.6.1.4.1.10418.17.2.5.13.1.45
sensor high critical (alarm) threshold (Celcius x 10).
to SET: use pmPowerMgmtSensorsTableHighCritical in proper units (pmPowerMgmtSensorsTableUnit).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.13.1.50
sensor high warning threshold (Celcius x 10).
to SET: use pmPowerMgmtSensorsTableHighWarning in proper units (pmPowerMgmtSensorsTableUnit).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.13.1.51
sensor low warning threshold (Celcius x 10).
to SET: use pmPowerMgmtSensorsTableLowWarning in proper units (pmPowerMgmtSensorsTableUnit).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.13.1.52
sensor low critical threshold (Celcius x 10).
to SET: use pmPowerMgmtSensorsTableLowCritical in proper units (pmPowerMgmtSensorsTableUnit).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.13.1.53
sensor high critical (alarm) threshold (Fahrenheit x 10).
to SET: use pmPowerMgmtSensorsTableHighCritical in proper units (pmPowerMgmtSensorsTableUnit).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.13.1.60
sensor high warning threshold (Fahrenheit x 10).
to SET: use pmPowerMgmtSensorsTableHighWarning in proper units (pmPowerMgmtSensorsTableUnit).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.13.1.61
sensor low warning threshold (Fahrenheit x 10).
to SET: use pmPowerMgmtSensorsTableLowWarning in proper units (pmPowerMgmtSensorsTableUnit).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.13.1.62
sensor low critical threshold (Fahrenheit x 10).
to SET: use pmPowerMgmtSensorsTableLowCritical in proper units (pmPowerMgmtSensorsTableUnit).
Returns 0 if not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.10418.17.2.5.13.1.63