NetBotz50-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
28
Rows
28
Columns
243
.1.3.6.1.4.1.52674.500.2.1 · 1 row entry · 7 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk enclosureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::enclosureTable'
A list of enclosures (base enclosure and pods).
enclosureEntry row .1.3.6.1.4.1.52674.500.2.1.1
Enclosure entry.
Indexes
Column Syntax OID
The id of the physical enclosure.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.2.1.1.1
The operational status of the enclosure.
OperStatus
Type Values:
0disconnected
1error
2normal
.1.3.6.1.4.1.52674.500.2.1.1.2
The error status of the enclosure. If there are no error conditions
reported for the enclosure, the status is normal. Otherwise, the status is
reported as the severity value of the highest severity error condition
tha…
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.2.1.1.3
The unique label assigned to the enclosure (or pod).
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.2.1.1.4
The id of the parent enclosure this enclosure is attached to.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.2.1.1.5
The serial number of this enclosure.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.2.1.1.6
The index of the physical enclosure.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.2.1.1.7
.1.3.6.1.4.1.52674.500.2.2.1 · 1 row entry · 7 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk alinkSensorCountTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::alinkSensorCountTable'
A count of alink-related sensors.
alinkSensorCountEntry row .1.3.6.1.4.1.52674.500.2.2.1.1
A count-of-sensors entry.
Column Syntax OID
The unique id of the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.2.2.1.1.1
The number of known connected sensors.
Integer32
Constraints:
range: 0-65535
.1.3.6.1.4.1.52674.500.2.2.1.1.2
The unique label assigned to the sensor count.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.2.2.1.1.3
The id of the physical enclosure represented by the sensor count.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.2.2.1.1.4
The sensor count value shown as a string.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.2.2.1.1.5
The sensor count as integer value.
Integer32
Constraints:
range: 0-6554
.1.3.6.1.4.1.52674.500.2.2.1.1.6
The index of the sensor counter.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.2.2.1.1.7
.1.3.6.1.4.1.52674.500.3.10 · 1 row entry · 5 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk otherPortTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::otherPortTable'
A list of other port entries.
otherPortEntry row .1.3.6.1.4.1.52674.500.3.10.1
Other port entry.
Indexes
Column Syntax OID
The unique id of the port.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.3.10.1.1
The operational status of the port.
OperStatus
Type Values:
0disconnected
1error
2normal
.1.3.6.1.4.1.52674.500.3.10.1.2
The unique label assigned to the port.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.3.10.1.3
The id of the physical enclosure containing the port.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.3.10.1.4
The index of the port.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.3.10.1.5
.1.3.6.1.4.1.52674.500.4.1.1 · 1 row entry · 10 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk tempSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::tempSensorTable'
A list of temperature sensor entries.
tempSensorEntry row .1.3.6.1.4.1.52674.500.4.1.1.1
A temperature sensor entry.
Indexes
Column Syntax OID
The unique id of the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.1.1.1
The temperature measured by the sensor in tenths of a degree Celsius.
Integer32
Constraints:
range: -500-1000
.1.3.6.1.4.1.52674.500.4.1.1.1.2
The error status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is
reported as the severity value of the highest severity error condition
that is n…
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.4.1.1.1.3
The unique label assigned to the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.1.1.4
The id of the physical enclosure containing the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.1.1.5
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port).
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.1.1.6
The temperature reading, in degrees celsius, shown as a string (or empty string
if it is not plugged into a port).
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.1.1.7
The temperature measured by the sensor in degree Celsius.
Integer32
Constraints:
range: -50-100
.1.3.6.1.4.1.52674.500.4.1.1.1.8
The temperature measured by the sensor in degree Farenheit.
Integer32
Constraints:
range: -50-212
.1.3.6.1.4.1.52674.500.4.1.1.1.9
The index of the sensor.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.4.1.1.1.10
.1.3.6.1.4.1.52674.500.4.1.2 · 1 row entry · 9 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk humiSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::humiSensorTable'
A list of humidity sensor entries.
humiSensorEntry row .1.3.6.1.4.1.52674.500.4.1.2.1
A humidity sensor entry.
Indexes
Column Syntax OID
The unique id of the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.2.1.1
The relative humidity measured by the sensor in tenths of a percent.
Integer32
Constraints:
range: 0-1000
.1.3.6.1.4.1.52674.500.4.1.2.1.2
The error status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is
reported as the severity value of the highest severity error condition
that is n…
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.4.1.2.1.3
The unique label assigned to the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.2.1.4
The id of the physical enclosure containing the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.2.1.5
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port).
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.2.1.6
The humidity reading, in percent, shown as a string (or empty string
if it is not plugged into a port).
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.2.1.7
The relative humidity measured by the sensor in percent.
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.52674.500.4.1.2.1.8
The index of the sensor.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.4.1.2.1.9
.1.3.6.1.4.1.52674.500.4.1.3 · 1 row entry · 10 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk dewPointSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::dewPointSensorTable'
A list of dew point sensor entries.
dewPointSensorEntry row .1.3.6.1.4.1.52674.500.4.1.3.1
A dew point sensor entry.
Column Syntax OID
The unique id of the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.3.1.1
The dew point value measured by the sensor in tenths of a degree Celsius.
Integer32
Constraints:
range: -500-1000
.1.3.6.1.4.1.52674.500.4.1.3.1.2
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is
reported as the severity value of the highest severity error condition
tha…
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.4.1.3.1.3
The unique label assigned to the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.3.1.4
The id of the physical enclosure containing the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.3.1.5
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port).
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.3.1.6
The dew point reading, in degrees celsius, shown as a string (or empty string
if it is not plugged into a port).
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.3.1.7
The dew point value measured by the sensor in degrees Celsius.
Integer32
Constraints:
range: -50-100
.1.3.6.1.4.1.52674.500.4.1.3.1.8
The dew point reading in degrees Farenheit, measured by the sensor.
Integer32
Constraints:
range: -40-122
.1.3.6.1.4.1.52674.500.4.1.3.1.9
The index of the sensor.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.4.1.3.1.10
.1.3.6.1.4.1.52674.500.4.1.5 · 1 row entry · 9 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk airFlowSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::airFlowSensorTable'
A list of airflow sensor entries.
airFlowSensorEntry row .1.3.6.1.4.1.52674.500.4.1.5.1
An air flow sensor entry.
Column Syntax OID
The unique id of the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.5.1.1
The air flow measured by the sensor in tenths of a meter per minute.
Integer32
Constraints:
range: 0-10000
.1.3.6.1.4.1.52674.500.4.1.5.1.2
The error status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is
reported as the severity value of the highest severity error condition
that is n…
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.4.1.5.1.3
The unique label assigned to the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.5.1.4
The id of the physical enclosure containing the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.5.1.5
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port).
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.5.1.6
The airflow reading, in meters per minute, shown as a string (or empty string
if it is not plugged into a port).
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.5.1.7
The air flow measured by the sensor in meters per minute.
Integer32
Constraints:
range: 0-1000
.1.3.6.1.4.1.52674.500.4.1.5.1.8
The index of the sensor.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.4.1.5.1.9
.1.3.6.1.4.1.52674.500.4.1.6 · 1 row entry · 9 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk ampDetectSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::ampDetectSensorTable'
A list of amp detect sensor entries.
ampDetectSensorEntry row .1.3.6.1.4.1.52674.500.4.1.6.1
An ampere sensor entry.
Column Syntax OID
The unique id of the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.6.1.1
The value measured by the sensor in tenths of an ampere.
Integer32
Constraints:
range: 0-65535
.1.3.6.1.4.1.52674.500.4.1.6.1.2
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is
reported as the severity value of the highest severity error condition
tha…
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.4.1.6.1.3
The unique label assigned to the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.6.1.4
The id of the physical enclosure containing the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.6.1.5
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port).
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.6.1.6
The amp detect reading, in amperes, shown as a string (or empty string
if it is not plugged into a port).
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.6.1.7
The value measured by the sensor in amperes.
Integer32
Constraints:
range: 0-6554
.1.3.6.1.4.1.52674.500.4.1.6.1.8
The index of the sensor.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.4.1.6.1.9
.1.3.6.1.4.1.52674.500.4.1.10 · 1 row entry · 12 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk otherNumericSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::otherNumericSensorTable'
A list of other numeric sensor entries.
otherNumericSensorEntry row .1.3.6.1.4.1.52674.500.4.1.10.1
Other numeric sensor entry.
Column Syntax OID
The unique id of the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.10.1.1
The value measured by the sensor in tenths of the unit of measure.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.52674.500.4.1.10.1.2
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is
reported as the severity value of the highest severity error condition
tha…
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.4.1.10.1.3
The unique label assigned to the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.10.1.4
The id of the physical enclosure containing the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.10.1.5
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port).
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.10.1.6
The sensor reading shown as a string (or empty string
if it is not plugged into a port).
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.10.1.7
The value measured by the sensor in the unit of measure (1/10 of otherNumericSensorValue)
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.52674.500.4.1.10.1.8
The unit of measure for the sensor value.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.10.1.9
The value measured by the sensor in thousandths of the unit of measure (100 times otherNumericSensorValue)
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.52674.500.4.1.10.1.10
The value measured by the sensor in millionths of the unit of measure (100000 times otherNumericSensorValue)
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.52674.500.4.1.10.1.11
The index of the sensor.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.4.1.10.1.12
.1.3.6.1.4.1.52674.500.4.1.11 · 1 row entry · 10 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk rssiSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::rssiSensorTable'
A list of wireless network RSSI entries.
rssiSensorEntry row .1.3.6.1.4.1.52674.500.4.1.11.1
RSSI sensor entry.
Indexes
Column Syntax OID
The unique id of the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.11.1.1
The value measured by the sensor in tenths of the unit of measure.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.52674.500.4.1.11.1.2
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is
reported as the severity value of the highest severity error condition
tha…
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.4.1.11.1.3
The unique label assigned to the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.11.1.4
The id of the physical enclosure containing the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.11.1.5
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port).
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.11.1.6
The sensor reading shown as a string (or empty string
if it is not plugged into a port).
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.11.1.7
The value measured by the sensor in the unit of measure (1/10 of rssiSensorValue)
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.52674.500.4.1.11.1.8
The unit of measure for the sensor value.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.11.1.9
The index of the sensor.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.4.1.11.1.10
.1.3.6.1.4.1.52674.500.4.1.12 · 1 row entry · 12 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk currentInputSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::currentInputSensorTable'
A list of current input sensor entries.
currentInputSensorEntry row .1.3.6.1.4.1.52674.500.4.1.12.1
Current Input sensor entry.
Column Syntax OID
The unique id of the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.12.1.1
The value measured by the sensor in tenths of the unit of measure.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.52674.500.4.1.12.1.2
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is
reported as the severity value of the highest severity error condition
tha…
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.4.1.12.1.3
The unique label assigned to the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.12.1.4
The id of the physical enclosure containing the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.12.1.5
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port).
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.12.1.6
The sensor reading shown as a string (or empty string
if it is not plugged into a port).
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.12.1.7
The value measured by the sensor in the unit of measure (1/10 of currentInputSensorValue)
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.52674.500.4.1.12.1.8
The unit of measure for the sensor value.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.12.1.9
The value measured by the sensor in thousandths of the unit of measure (100 times currentInputSensorValue)
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.52674.500.4.1.12.1.10
The value measured by the sensor in millionths of the unit of measure (100000 times currentInputSensorValue)
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.52674.500.4.1.12.1.11
The index of the sensor.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.4.1.12.1.12
.1.3.6.1.4.1.52674.500.4.1.13 · 1 row entry · 12 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk voltageSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::voltageSensorTable'
A list of current input sensor entries.
voltageSensorEntry row .1.3.6.1.4.1.52674.500.4.1.13.1
Voltage sensor entry.
Column Syntax OID
The unique id of the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.13.1.1
The value measured by the sensor in tenths of the unit of measure.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.52674.500.4.1.13.1.2
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is
reported as the severity value of the highest severity error condition
tha…
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.4.1.13.1.3
The unique label assigned to the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.13.1.4
The id of the physical enclosure containing the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.13.1.5
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port).
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.13.1.6
The sensor reading shown as a string (or empty string
if it is not plugged into a port).
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.13.1.7
The value measured by the sensor in the unit of measure (1/10 of voltageSensorValue)
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.52674.500.4.1.13.1.8
The unit of measure for the sensor value.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.13.1.9
The value measured by the sensor in thousandths of the unit of measure (100 times voltageSensorValue)
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.52674.500.4.1.13.1.10
The value measured by the sensor in millionths of the unit of measure (100000 times voltageSensorValue)
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.52674.500.4.1.13.1.11
The index of the sensor.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.4.1.13.1.12
.1.3.6.1.4.1.52674.500.4.1.14 · 1 row entry · 12 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk batterySensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::batterySensorTable'
A list of current input sensor entries.
batterySensorEntry row .1.3.6.1.4.1.52674.500.4.1.14.1
Battery sensor entry.
Column Syntax OID
The unique id of the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.14.1.1
The value measured by the sensor in tenths of the unit of measure.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.52674.500.4.1.14.1.2
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is
reported as the severity value of the highest severity error condition
tha…
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.4.1.14.1.3
The unique label assigned to the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.14.1.4
The id of the physical enclosure containing the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.14.1.5
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port).
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.1.14.1.6
The sensor reading shown as a string (or empty string
if it is not plugged into a port).
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.14.1.7
The value measured by the sensor in the unit of measure (1/10 of batterySensorValue)
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.52674.500.4.1.14.1.8
The unit of measure for the sensor value.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.1.14.1.9
The value measured by the sensor in thousandths of the unit of measure (100 times batterySensorValue)
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.52674.500.4.1.14.1.10
The value measured by the sensor in millionths of the unit of measure (100000 times batterySensorValue)
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.52674.500.4.1.14.1.11
The index of the sensor.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.4.1.14.1.12
.1.3.6.1.4.1.52674.500.4.2.1 · 1 row entry · 8 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk dryContactSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::dryContactSensorTable'
A list of dry contact sensor entries.
dryContactSensorEntry row .1.3.6.1.4.1.52674.500.4.2.1.1
Dry contact sensor entry.
Column Syntax OID
The unique id of the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.1.1.1
Whether the dry sensor contact is open or closed.
Enumeration
Enumerated Values:
-1undefined
0open
1closed
.1.3.6.1.4.1.52674.500.4.2.1.1.2
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is
reported as the severity value of the highest severity error condition
tha…
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.4.2.1.1.3
The unique label assigned to the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.2.1.1.4
The id of the physical enclosure containing the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.1.1.5
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port).
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.1.1.6
The enum value label for the state reported by the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.2.1.1.7
The index of the sensor.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.4.2.1.1.8
.1.3.6.1.4.1.52674.500.4.2.2 · 1 row entry · 8 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk doorSwitchSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::doorSwitchSensorTable'
A list of door switch sensor entries.
doorSwitchSensorEntry row .1.3.6.1.4.1.52674.500.4.2.2.1
Door switch sensor entry.
Column Syntax OID
The unique id of the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.2.1.1
Whether the door is open or closed.
Enumeration
Enumerated Values:
-1undefined
0open
1closed
.1.3.6.1.4.1.52674.500.4.2.2.1.2
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is
reported as the severity value of the highest severity error condition
tha…
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.4.2.2.1.3
The unique label assigned to the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.2.2.1.4
The id of the physical enclosure containing the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.2.1.5
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port).
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.2.1.6
The enum value label for the state reported by the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.2.2.1.7
The index of the sensor.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.4.2.2.1.8
.1.3.6.1.4.1.52674.500.4.2.3 · 1 row entry · 8 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk cameraMotionSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::cameraMotionSensorTable'
A list of camera motion sensor entries.
cameraMotionSensorEntry row .1.3.6.1.4.1.52674.500.4.2.3.1
Camera motion sensor entry.
Column Syntax OID
The unique id of the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.3.1.1
Whether motion is detected by the camera sensor.
Enumeration
Enumerated Values:
-1undefined
0noMotion
1motionDetected
.1.3.6.1.4.1.52674.500.4.2.3.1.2
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is
reported as the severity value of the highest severity error condition
tha…
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.4.2.3.1.3
The unique label assigned to the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.2.3.1.4
The id of the physical enclosure containing the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.3.1.5
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port).
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.3.1.6
The enum value label for the state reported by the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.2.3.1.7
The index of the sensor.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.4.2.3.1.8
.1.3.6.1.4.1.52674.500.4.2.10 · 1 row entry · 8 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk otherStateSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::otherStateSensorTable'
A list of other state sensor entries.
otherStateSensorEntry row .1.3.6.1.4.1.52674.500.4.2.10.1
Other state sensor entry.
Column Syntax OID
The unique id of the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.10.1.1
State value reported by the sensor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.52674.500.4.2.10.1.2
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is
reported as the severity value of the highest severity error condition
tha…
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.4.2.10.1.3
The unique label assigned to the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.2.10.1.4
The id of the physical enclosure containing the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.10.1.5
The id of port the sensor is plugged into (or empty string
if it is not plugged into a port).
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.10.1.6
The enum value label for the state reported by the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.2.10.1.7
The index of the sensor.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.4.2.10.1.8
.1.3.6.1.4.1.52674.500.4.2.11 · 1 row entry · 8 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk vibrationSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::vibrationSensorTable'
A list of vibration sensor entries.
vibrationSensorEntry row .1.3.6.1.4.1.52674.500.4.2.11.1
Vibration sensor entry.
Column Syntax OID
The unique id of the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.11.1.1
Whether vibration is detected.
Enumeration
Enumerated Values:
-1undefined
0noVibration
1vibrationDetected
.1.3.6.1.4.1.52674.500.4.2.11.1.2
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is
reported as the severity value of the highest severity error condition
tha…
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.4.2.11.1.3
The unique label assigned to the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.2.11.1.4
The id of the physical enclosure containing the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.11.1.5
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port).
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.11.1.6
The enum value label for the state reported by the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.2.11.1.7
The index of the sensor.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.4.2.11.1.8
.1.3.6.1.4.1.52674.500.4.2.12 · 1 row entry · 8 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk smokeSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::smokeSensorTable'
A list of smoke sensor entries.
smokeSensorEntry row .1.3.6.1.4.1.52674.500.4.2.12.1
Smoke sensor entry.
Column Syntax OID
The unique id of the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.12.1.1
Whether smoke is detected.
Enumeration
Enumerated Values:
-1undefined
0noSmoke
1smokeDetected
.1.3.6.1.4.1.52674.500.4.2.12.1.2
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is
reported as the severity value of the highest severity error condition
tha…
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.4.2.12.1.3
The unique label assigned to the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.2.12.1.4
The id of the physical enclosure containing the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.12.1.5
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port).
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.12.1.6
The enum value label for the state reported by the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.2.12.1.7
The index of the sensor.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.4.2.12.1.8
.1.3.6.1.4.1.52674.500.4.2.13 · 1 row entry · 8 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk leakSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::leakSensorTable'
A list of leak sensor entries.
leakSensorEntry row .1.3.6.1.4.1.52674.500.4.2.13.1
Leak sensor entry.
Indexes
Column Syntax OID
The unique id of the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.13.1.1
Whether a leak is detected.
Enumeration
Enumerated Values:
-1undefined
0noLeak
1leakDetected
.1.3.6.1.4.1.52674.500.4.2.13.1.2
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is
reported as the severity value of the highest severity error condition
tha…
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.4.2.13.1.3
The unique label assigned to the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.2.13.1.4
The id of the physical enclosure containing the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.13.1.5
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port).
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.13.1.6
The enum value label for the state reported by the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.2.13.1.7
The index of the sensor.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.4.2.13.1.8

beaconTable

table
.1.3.6.1.4.1.52674.500.4.2.14 · 1 row entry · 8 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk beaconTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::beaconTable'
A list of beacon entries.
beaconEntry row .1.3.6.1.4.1.52674.500.4.2.14.1
Beacon entry.
Indexes
Column Syntax OID
The unique id of the beacon.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.14.1.1
Whether the beacon is flashing.
Enumeration
Enumerated Values:
-1undefined
0off
1on
.1.3.6.1.4.1.52674.500.4.2.14.1.2
The operational status of the beacon. If there are no error conditions
reported for the beacon, the status is normal. Otherwise, the status is
reported as the severity value of the highest severity error condition
tha…
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.4.2.14.1.3
The unique label assigned to the beacon.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.2.14.1.4
The id of the physical enclosure containing the beacon.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.14.1.5
The id of the port the beacon is plugged into (or empty string
if it is not plugged into a port).
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.14.1.6
The enum value label for the state reported by the beacon.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.2.14.1.7
The index of the beacon.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.4.2.14.1.8
.1.3.6.1.4.1.52674.500.4.2.15 · 1 row entry · 8 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk switchedOutletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::switchedOutletTable'
A list of switched outlet entries.
switchedOutletEntry row .1.3.6.1.4.1.52674.500.4.2.15.1
Switched outlet entry.
Column Syntax OID
The unique id of the switched outlet.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.15.1.1
Whether the switched outlet is on or off.
Enumeration
Enumerated Values:
-1undefined
0off
1on
.1.3.6.1.4.1.52674.500.4.2.15.1.2
The operational status of the switched outlet. If there are no error conditions
reported for the switched outlet, the status is normal. Otherwise, the status is
reported as the severity value of the highest severity e…
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.4.2.15.1.3
The unique label assigned to the switched outlet.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.2.15.1.4
The id of the physical enclosure containing the switched outlet.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.15.1.5
The id of the port the switched outlet is plugged into (or empty string
if it is not plugged into a port).
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.15.1.6
The enum value label for the state reported by the switchedOutlet.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.2.15.1.7
The index of the switched outlet.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.4.2.15.1.8
.1.3.6.1.4.1.52674.500.4.2.16 · 1 row entry · 8 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk doorLockSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::doorLockSensorTable'
A list of door lock sensor entries.
doorLockSensorEntry row .1.3.6.1.4.1.52674.500.4.2.16.1
Door lock sensor entry.
Column Syntax OID
The unique id of the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.16.1.1
When setting this object only unlocked(0) or locked(1) is valid.
Enumerationr/w
Enumerated Values:
-1undefined
0unlocked
1locked
.1.3.6.1.4.1.52674.500.4.2.16.1.2
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is
reported as the severity value of the highest severity error condition
tha…
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.4.2.16.1.3
The unique label assigned to the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.2.16.1.4
The id of the physical enclosure containing the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.16.1.5
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port).
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.16.1.6
The enum value label for the state reported by the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.2.16.1.7
The index of the sensor.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.4.2.16.1.8
.1.3.6.1.4.1.52674.500.4.2.17 · 1 row entry · 8 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk rackHandleSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::rackHandleSensorTable'
A list of rack handle sensor entries.
rackHandleSensorEntry row .1.3.6.1.4.1.52674.500.4.2.17.1
Rack door handle sensor entry.
Column Syntax OID
The unique id of the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.17.1.1
Whether the door is open or closed.
Enumeration
Enumerated Values:
-1undefined
0open
1closed
.1.3.6.1.4.1.52674.500.4.2.17.1.2
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is
reported as the severity value of the highest severity error condition
tha…
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.4.2.17.1.3
The unique label assigned to the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.2.17.1.4
The id of the physical enclosure containing the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.17.1.5
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port).
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.17.1.6
The enum value label for the state reported by the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.2.17.1.7
The index of the sensor.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.4.2.17.1.8
.1.3.6.1.4.1.52674.500.4.2.18 · 1 row entry · 8 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk outputRelaySensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::outputRelaySensorTable'
A list of output relay entries.
outputRelaySensorEntry row .1.3.6.1.4.1.52674.500.4.2.18.1
Output relay sensor entry.
Column Syntax OID
The unique id of the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.18.1.1
Whether the relay is open or closed.
Enumeration
Enumerated Values:
-1undefined
0open
1closed
.1.3.6.1.4.1.52674.500.4.2.18.1.2
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is
reported as the severity value of the highest severity error condition
tha…
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.4.2.18.1.3
The unique label assigned to the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.2.18.1.4
The id of the physical enclosure containing the sensor.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.18.1.5
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port).
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.4.2.18.1.6
The enum value label for the state reported by the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.4.2.18.1.7
The index of the sensor.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.4.2.18.1.8
.1.3.6.1.4.1.52674.500.5.1 · 1 row entry · 12 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk errorCondTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::errorCondTable'
A list of active and resolved error conditions.
errorCondEntry row .1.3.6.1.4.1.52674.500.5.1.1
Error condition entry.
Indexes
Column Syntax OID
The unique id of the error condition.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.5.1.1.1
The relative severity of the error condition.
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.5.1.1.2
The error type id reported for the error condition.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.5.1.1.3
The start time of the error condition, in msec since 1/1/1970.
SNMPv2-TCDateAndTime
Type Constraints:
range: 8
range: 11
Description:
A date-time specification.

field octets contents range
----- ------ -------- -----
1 1-2 year* 0..65536
2 3 month …
.1.3.6.1.4.1.52674.500.5.1.1.4
The start time of the error condition, as ISO date-time formatted string (UTC).
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.5.1.1.5
Whether the error condition was resolved.
BoolValue
Type Values:
0no
1yes
2null
.1.3.6.1.4.1.52674.500.5.1.1.6
The time the error condition was resolved (if it was resolved), in msec since 1/1/1970.
SNMPv2-TCDateAndTime
Type Constraints:
range: 8
range: 11
Description:
A date-time specification.

field octets contents range
----- ------ -------- -----
1 1-2 year* 0..65536
2 3 month …
.1.3.6.1.4.1.52674.500.5.1.1.7
The time the error condition was resolved (if it was resolved), as ISO date-time formatted string (UTC).
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.5.1.1.8
The id of the physical enclosure associated with the error.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.5.1.1.9
The id of the port associated with the error (or empty string
if the error is not associated with a port).
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.5.1.1.10
The id of the sensor associated with the error (or empty string
if the error is not associated with a sensor.)
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.5.1.1.11
The index of the error condition.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.5.1.1.12

cameraTable

table
.1.3.6.1.4.1.52674.500.6.1 · 1 row entry · 8 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk cameraTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::cameraTable'
A list of configured camera's.
cameraEntry row .1.3.6.1.4.1.52674.500.6.1.1
Camera entry.
Indexes
Column Syntax OID
The id of the camera.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.6.1.1.1
The vendor of the camera.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.6.1.1.2
The model of the camera.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.6.1.1.3
The operational status of the camera.
OperStatus
Type Values:
0disconnected
1error
2normal
.1.3.6.1.4.1.52674.500.6.1.1.4
The error status of the camera. If there are no error conditions
reported for the camera, the status is normal. Otherwise, the status is
reported as the severity value of the highest severity error condition
that is n…
ErrorStatus
Type Values:
0normal
1info
2warning
3error
4critical
5failure
.1.3.6.1.4.1.52674.500.6.1.1.5
The unique label assigned to the camera.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.52674.500.6.1.1.6
The address or host name of the camera.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.6.1.1.7
The index of the physical enclosure.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.6.1.1.8
.1.3.6.1.4.1.52674.500.7.1 · 1 row entry · 3 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk firmwareTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NetBotz50-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NetBotz50-MIB::firmwareTable'
A list of firmware versions contained in the NetBotz distribution.
firmwareEntry row .1.3.6.1.4.1.52674.500.7.1.1
Firmware entry.
Indexes
Column Syntax OID
Name of of the firmware product.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.7.1.1.1
Version of of the firmware product.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.52674.500.7.1.1.2
The index of the firmware.
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.52674.500.7.1.1.3