KohlerGCon-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
2
Rows
2
Columns
9

gconTable

table mandatory
.1.3.6.1.4.1.22978.1.3.1.1 · 1 row entry · 4 columns
Uses the kohler variant from /opt/observium/mibs/kohler.
Command help
Walk gconTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'KohlerGCon-MIB' -M '/opt/observium/mibs/kohler:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'KohlerGCon-MIB::gconTable'
Table of generator controller data.
gconEntry row .1.3.6.1.4.1.22978.1.3.1.1.1
Generator controller table entries.
Indexes
Column Syntax OID
gconTypemandatory
Generator controller type.
Integer32
Constraints:
range: 0-65535
.1.3.6.1.4.1.22978.1.3.1.1.1.1
gconAddrmandatory
Generator controller address.
Integer32
Constraints:
range: 1-255
.1.3.6.1.4.1.22978.1.3.1.1.1.2
gconStatusmandatory
Generator controller comm status.
Enumeration
Enumerated Values:
0unknown
1good
2error
.1.3.6.1.4.1.22978.1.3.1.1.1.3
gconRemoteCmdmandatory
Generator controller remote start/stop.
Enumerationr/w
Enumerated Values:
0none
1start
2stop
.1.3.6.1.4.1.22978.1.3.1.1.1.4

gconAlarmTable

table mandatory
.1.3.6.1.4.1.22978.1.3.1.2 · 1 row entry · 5 columns
Uses the kohler variant from /opt/observium/mibs/kohler.
Command help
Walk gconAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'KohlerGCon-MIB' -M '/opt/observium/mibs/kohler:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'KohlerGCon-MIB::gconAlarmTable'
Table of generator controller alarm data.
gconAlarmEntry row .1.3.6.1.4.1.22978.1.3.1.2.1
Generator controller alarm table entries.
Column Syntax OID
gconAlarmAddrmandatory
Generator controller address.
Integer32
Constraints:
range: 1-255
.1.3.6.1.4.1.22978.1.3.1.2.1.1
gconAlarmIdxmandatory
Generator alarm index.
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.22978.1.3.1.2.1.2
gconAlarmCodemandatory
Generator alarm code.
Integer32
Constraints:
range: 0-65535
.1.3.6.1.4.1.22978.1.3.1.2.1.3
Generator controller alarm severity.
Enumeration
Enumerated Values:
1nfpaShutdown
2nfpaWarning
3nfpaAlarmStatus
4shutdown
5warning
6alarmStatus
.1.3.6.1.4.1.22978.1.3.1.2.1.4
Generator controller alarm description.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.22978.1.3.1.2.1.5