INFRATEC-RMS-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
18
Rows
18
Columns
94

digitalInTable

table mandatory
.1.3.6.1.4.1.1909.10.2.1 · 1 row entry · 5 columns
Uses the infratec variant from /opt/observium/mibs/infratec.
Command help
Walk digitalInTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'INFRATEC-RMS-MIB' -M '/opt/observium/mibs/infratec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'INFRATEC-RMS-MIB::digitalInTable'
The digitalInTable contains all information about 
physical inputs Digital In 1-8.
digitalInEntry row .1.3.6.1.4.1.1909.10.2.1.1
Each entry contains information for each input
Indexes
Column Syntax OID
Index of Digital Input
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.2.1.1.1
Descriptive name of Digital Input
r/w .1.3.6.1.4.1.1909.10.2.1.1.2
Current state of Digital Input
Enumeration
Enumerated Values:
1off
2on
.1.3.6.1.4.1.1909.10.2.1.1.3
Timestamp of last change
RFC1155-SMITimeTicks
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.1909.10.2.1.1.4
How many times the input changed since system startup
RFC1155-SMICounter
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.1909.10.2.1.1.5

alertInTable

table mandatory
.1.3.6.1.4.1.1909.10.2.2 · 1 row entry · 6 columns
Uses the infratec variant from /opt/observium/mibs/infratec.
Command help
Walk alertInTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'INFRATEC-RMS-MIB' -M '/opt/observium/mibs/infratec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'INFRATEC-RMS-MIB::alertInTable'
The alertInTable contains all information about 
physical inputs Alert In 1-4.
alertInEntry row .1.3.6.1.4.1.1909.10.2.2.1
Each entry contains the values for an alert input
Indexes
Column Syntax OID
alertInIndexmandatory
Index of Alert Input
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.2.2.1.1
alertInDescrmandatory
Descriptive name of Alert Input
r/w .1.3.6.1.4.1.1909.10.2.2.1.2
alertInStatemandatory
Current state of Alert Input
Enumeration
Enumerated Values:
1off
2on
.1.3.6.1.4.1.1909.10.2.2.1.3
Timestamp of last change
RFC1155-SMITimeTicks
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.1909.10.2.2.1.4
How many times the input changed since system startup
RFC1155-SMICounter
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.1909.10.2.2.1.5
alertInResetmandatory
Reset an Alert In by writing 2 in here.
Most sensors use to store an alarm, which only can be
deleted by resetting the sensor respectively the whole
signalling line. This is achieved by powering-off this
signalling …
Enumerationr/w
Enumerated Values:
1default
2alertIn-reset
.1.3.6.1.4.1.1909.10.2.2.1.6

upsInTable

table mandatory
.1.3.6.1.4.1.1909.10.2.3 · 1 row entry · 5 columns
Uses the infratec variant from /opt/observium/mibs/infratec.
Command help
Walk upsInTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'INFRATEC-RMS-MIB' -M '/opt/observium/mibs/infratec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'INFRATEC-RMS-MIB::upsInTable'
The upsInputTable contains all information about 
physical inputs UPS In 1-2.
upsInEntry row .1.3.6.1.4.1.1909.10.2.3.1
Each entry contains the values for an UPS input
Indexes
Column Syntax OID
upsInIndexmandatory
Index of UPS Input
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.2.3.1.1
upsInDescrmandatory
Name of UPS Input
r/w .1.3.6.1.4.1.1909.10.2.3.1.2
upsInStatemandatory
Current state of UPS Input
Enumeration
Enumerated Values:
1off
2on
.1.3.6.1.4.1.1909.10.2.3.1.3
Timestamp of last change
RFC1155-SMITimeTicks
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.1909.10.2.3.1.4
upsInChangesmandatory
How many times the input changed since system startup
RFC1155-SMICounter
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.1909.10.2.3.1.5

outputTable

table mandatory
.1.3.6.1.4.1.1909.10.3.1 · 1 row entry · 7 columns
Uses the infratec variant from /opt/observium/mibs/infratec.
Command help
Walk outputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'INFRATEC-RMS-MIB' -M '/opt/observium/mibs/infratec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'INFRATEC-RMS-MIB::outputTable'
The table used for describing the digital outputs
outputEntry row .1.3.6.1.4.1.1909.10.3.1.1
Each entry contains the description of an digital output
Indexes
Column Syntax OID
outputIndexmandatory
Index of digital output
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.3.1.1.1
outputDescrmandatory
Descriptive Name of one digital output
r/w .1.3.6.1.4.1.1909.10.3.1.1.2
outputEffectmandatory
Determines the way the physical digital output is
influenced by one or more filter results.
For this the result of the logical output block can be
passed thru (thru) or inverted (invert).
Furthermore it is possible to…
Enumerationr/w
Enumerated Values:
1off
2on
3thru
4invert
.1.3.6.1.4.1.1909.10.3.1.1.3
Timestamp of last change
RFC1155-SMITimeTicks
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.1909.10.3.1.1.4
outputChangesmandatory
How many times an output changed since system startup
RFC1155-SMICounter
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.1909.10.3.1.1.5
outputLogicmandatory
Each output can be controlled by a couple of filters, which
are combined in a boolean operation. The logic operation
(and/or) can be set up with this entry.
Enumerationr/w
Enumerated Values:
1and
2or
.1.3.6.1.4.1.1909.10.3.1.1.6
outputStatemandatory
Current state of digital output
Enumeration
Enumerated Values:
1open
2short
.1.3.6.1.4.1.1909.10.3.1.1.7

outputLogicTable

table mandatory
.1.3.6.1.4.1.1909.10.3.2 · 1 row entry · 3 columns
Uses the infratec variant from /opt/observium/mibs/infratec.
Command help
Walk outputLogicTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'INFRATEC-RMS-MIB' -M '/opt/observium/mibs/infratec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'INFRATEC-RMS-MIB::outputLogicTable'
The table used for describing the list of filters,
which effect an output.
outputLogicEntry row .1.3.6.1.4.1.1909.10.3.2.1
Each entry contains the description of one logic and/or
element
Column Syntax OID
Index of the output
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.3.2.1.1
Index of the filter
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.3.2.1.2
Determines, if this filter works on the logical and/or
element. Default is off.
Enumerationr/w
Enumerated Values:
1off
2on
.1.3.6.1.4.1.1909.10.3.2.1.3

tempTable

table mandatory
.1.3.6.1.4.1.1909.10.4.1 · 1 row entry · 3 columns
Uses the infratec variant from /opt/observium/mibs/infratec.
Command help
Walk tempTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'INFRATEC-RMS-MIB' -M '/opt/observium/mibs/infratec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'INFRATEC-RMS-MIB::tempTable'
Table to hold the information about temperature inputs
tempEntry row .1.3.6.1.4.1.1909.10.4.1.1
Each entry contains information about one temperature
input
Indexes
Column Syntax OID
tempIndexmandatory
Index of temperature input
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.4.1.1.1
tempDescrmandatory
Descriptive name of temperature input
r/w .1.3.6.1.4.1.1909.10.4.1.1.2
tempValuemandatory
Current temperature in degree celsius.
If 655 no sensor is connected.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.4.1.1.3

humidTable

table mandatory
.1.3.6.1.4.1.1909.10.5.1 · 1 row entry · 3 columns
Uses the infratec variant from /opt/observium/mibs/infratec.
Command help
Walk humidTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'INFRATEC-RMS-MIB' -M '/opt/observium/mibs/infratec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'INFRATEC-RMS-MIB::humidTable'
Table to hold the information about humidity inputs
humidEntry row .1.3.6.1.4.1.1909.10.5.1.1
Each entry contains information about one humidity
input
Indexes
Column Syntax OID
humidIndexmandatory
Index of humidity input
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.5.1.1.1
humidDescrmandatory
Descriptive name of the humidity input
r/w .1.3.6.1.4.1.1909.10.5.1.1.2
humidValuemandatory
Current humidity in percent rel. humidity.
If 255 no sensor is connected.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.5.1.1.3

mainsTable

table mandatory
.1.3.6.1.4.1.1909.10.6.1 · 1 row entry · 3 columns
Uses the infratec variant from /opt/observium/mibs/infratec.
Command help
Walk mainsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'INFRATEC-RMS-MIB' -M '/opt/observium/mibs/infratec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'INFRATEC-RMS-MIB::mainsTable'
Table to hold the information about the mains inputs
mainsEntry row .1.3.6.1.4.1.1909.10.6.1.1
Each entry contains information about one mains input
Indexes
Column Syntax OID
mainsIndexmandatory
Index of mains input
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.6.1.1.1
mainsDescrmandatory
Descriptive name of the mains input
r/w .1.3.6.1.4.1.1909.10.6.1.1.2
mainsValuemandatory
Current voltage of mains input in volt.
If 13 or 255 no voltage is detected.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.6.1.1.3

filterTable

table mandatory
.1.3.6.1.4.1.1909.10.7.1 · 1 row entry · 11 columns
Uses the infratec variant from /opt/observium/mibs/infratec.
Command help
Walk filterTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'INFRATEC-RMS-MIB' -M '/opt/observium/mibs/infratec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'INFRATEC-RMS-MIB::filterTable'
Table containing all information about the defined filters
filterEntry row .1.3.6.1.4.1.1909.10.7.1.1
Each entry contains the description of one filter
Indexes
Column Syntax OID
filterIndexmandatory
Index of the filter entry
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.1.1.1
filterDescrmandatory
Descriptive name of filter
r/w .1.3.6.1.4.1.1909.10.7.1.1.2
filterResultmandatory
Current filter result, i.e. result of all 'or'ed inputs
- see block diagram
Enumeration
Enumerated Values:
1false
2true
.1.3.6.1.4.1.1909.10.7.1.1.3
filterEffectmandatory
Determines the way the filter is used for further operation
Can be switched off, passed thru or inverted.
Enumerationr/w
Enumerated Values:
1off
2thru
3invert
.1.3.6.1.4.1.1909.10.7.1.1.4
filterTrapmandatory
Determines the way of trap notification to management
station(s) in case of filter events. Traps can be off,
sent once (when filter becomes true) or sent repeatedly
(as long as filter is true).
Enumerationr/w
Enumerated Values:
1no
2once
3repeat
.1.3.6.1.4.1.1909.10.7.1.1.5
filterLEDmandatory
When set to yes(2) a filter event will be signalled
by the warning LED on front of RMS
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.1909.10.7.1.1.6
filterBuzzermandatory
When set to yes(2) a filter event will be signalled
by the build-in buzzer
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.1909.10.7.1.1.7
If set to priority-warning(2) or priority-critical(3),
a filter event will be logged in the message log an on
all defined log server(s) with the corresponding priority.
This priority has only informational character.
Enumerationr/w
Enumerated Values:
1no-message
2priority-warning
3priority-critical
.1.3.6.1.4.1.1909.10.7.1.1.8
If set to enabled(1), it is possible to confirme a true
filter. This can be done on front panel of RMS, via telnet
or via SNMP (see also variable filterConfirm).
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.1909.10.7.1.1.9
Time after which a confirmed filter will be reactivated
automatically
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.1.1.10
filterConfirmmandatory
A true filter can be confimed by writing confirmed(2)
in here (provided filter confirmation is enabled -
see variable filterConfirmation). By doing this the effect
of this filter will be suspended until the time speci…
Enumerationr/w
Enumerated Values:
1not-confirmed
2confirmed
.1.3.6.1.4.1.1909.10.7.1.1.11

filterDigitalInTable

table mandatory
.1.3.6.1.4.1.1909.10.7.2 · 1 row entry · 3 columns
Uses the infratec variant from /opt/observium/mibs/infratec.
Command help
Walk filterDigitalInTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'INFRATEC-RMS-MIB' -M '/opt/observium/mibs/infratec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'INFRATEC-RMS-MIB::filterDigitalInTable'
Table containing all information about the filter inputs 
Digital 1-8 of each filter
filterDigitalInEntry row .1.3.6.1.4.1.1909.10.7.2.1
Each entry contains the description of one digital input
Column Syntax OID
Index of the filter
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.2.1.1
Index of the digital input
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.2.1.2
Determines the way the digital input effects the filter.
Can be switched off(1), inverted(3) or passed thru(2).
Enumerationr/w
Enumerated Values:
1off
2thru
3invert
.1.3.6.1.4.1.1909.10.7.2.1.3

filterAlertInTable

table mandatory
.1.3.6.1.4.1.1909.10.7.3 · 1 row entry · 3 columns
Uses the infratec variant from /opt/observium/mibs/infratec.
Command help
Walk filterAlertInTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'INFRATEC-RMS-MIB' -M '/opt/observium/mibs/infratec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'INFRATEC-RMS-MIB::filterAlertInTable'
Table containing all information about the filter inputs 
Alert In 1-4 of each filter
filterAlertInEntry row .1.3.6.1.4.1.1909.10.7.3.1
Each entry contains information of one alert input
Column Syntax OID
Index of the filter
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.3.1.1
Index of the alert input
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.3.1.2
Determines the way the alert input effects the filter.
Can be switched off(1), inverted(3) or passed thru(2).
Enumerationr/w
Enumerated Values:
1off
2thru
3invert
.1.3.6.1.4.1.1909.10.7.3.1.3

filterUPSInTable

table mandatory
.1.3.6.1.4.1.1909.10.7.4 · 1 row entry · 3 columns
Uses the infratec variant from /opt/observium/mibs/infratec.
Command help
Walk filterUPSInTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'INFRATEC-RMS-MIB' -M '/opt/observium/mibs/infratec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'INFRATEC-RMS-MIB::filterUPSInTable'
Table containing all information about the filter inputs 
UPS In 1-2 of each filter
filterUPSInEntry row .1.3.6.1.4.1.1909.10.7.4.1
Each entry contains the description of one ups input
Column Syntax OID
Index of the filter
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.4.1.1
Index of the UPS input
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.4.1.2
Determines the way the UPS input effects the filter.
Can be switched off(1), inverted(3) or passed thru(2).
Enumerationr/w
Enumerated Values:
1off
2thru
3invert
.1.3.6.1.4.1.1909.10.7.4.1.3

filterTempTable

table mandatory
.1.3.6.1.4.1.1909.10.7.5 · 1 row entry · 7 columns
Uses the infratec variant from /opt/observium/mibs/infratec.
Command help
Walk filterTempTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'INFRATEC-RMS-MIB' -M '/opt/observium/mibs/infratec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'INFRATEC-RMS-MIB::filterTempTable'
Table containing information about temperature inputs of
each filter, i.e. thresholds and compare operations
filterTempEntry row .1.3.6.1.4.1.1909.10.7.5.1
Each entry contains the description of one filter temp input
Column Syntax OID
Index of the filter
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.5.1.1
Index of the temp input
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.5.1.2
Determines the way the result of temp input comparison
effects on the filter. Can be switched off(1), inverted (3)
or passed thru(3).
Enumerationr/w
Enumerated Values:
1off
2thru
3invert
.1.3.6.1.4.1.1909.10.7.5.1.3
Threshold of temp input part A
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.5.1.4
Determines the operating mode of comparison operation A.
Can be set to greater(2) ' >', less(3) '<' or turned off(1),
if not needed
Enumerationr/w
Enumerated Values:
1off
2greater
3less
.1.3.6.1.4.1.1909.10.7.5.1.5
Threshold of temp input part B
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.5.1.6
Determines the operating mode of comparison operation B.
Can be set to greater(2) ' >', less(3) '<' or turned off(1),
if not needed
Enumerationr/w
Enumerated Values:
1off
2greater
3less
.1.3.6.1.4.1.1909.10.7.5.1.7

filterHumidityTable

table mandatory
.1.3.6.1.4.1.1909.10.7.6 · 1 row entry · 7 columns
Uses the infratec variant from /opt/observium/mibs/infratec.
Command help
Walk filterHumidityTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'INFRATEC-RMS-MIB' -M '/opt/observium/mibs/infratec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'INFRATEC-RMS-MIB::filterHumidityTable'
Table containing information about humidity inputs of
each filter, i.e. thresholds and compare operations
filterHumidityEntry row .1.3.6.1.4.1.1909.10.7.6.1
Each entry contains the description of one filter
Column Syntax OID
Index of the filter
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.6.1.1
Index of the humidity input
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.6.1.2
Determines the way the result of humidity input comparison
effects the filter. Can be switched off(1), inverted(3) or
passed thru(2), if not needed.
Enumerationr/w
Enumerated Values:
1off
2thru
3invert
.1.3.6.1.4.1.1909.10.7.6.1.3
Threshold of humidity input part A
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.6.1.4
Determines the operating mode of comparison operation A.
Can be set to greater(2) ' >', less(3) '<' or turned off(1),
if not needed
Enumerationr/w
Enumerated Values:
1off
2greater
3less
.1.3.6.1.4.1.1909.10.7.6.1.5
Threshold of humidity input part B
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.6.1.6
Determines the operating mode of comparison operation B.
Can be set to greater(2) ' >', less(3) '<' or turned off(1),
if not needed
Enumerationr/w
Enumerated Values:
1off
2greater
3less
.1.3.6.1.4.1.1909.10.7.6.1.7

filterMainsTable

table mandatory
.1.3.6.1.4.1.1909.10.7.7 · 1 row entry · 7 columns
Uses the infratec variant from /opt/observium/mibs/infratec.
Command help
Walk filterMainsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'INFRATEC-RMS-MIB' -M '/opt/observium/mibs/infratec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'INFRATEC-RMS-MIB::filterMainsTable'
Table containing information about mains inputs of
each filter, i.e. thresholds and compare operations
filterMainsEntry row .1.3.6.1.4.1.1909.10.7.7.1
Each entry contains the description of one filter
Column Syntax OID
Index of the filter
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.7.1.1
Index of the mains sensor
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.7.1.2
Determines the way the result of mains input comparison
effects on the filter. Can be switched off(1), inverted(3)
or passed thru (2).
Enumerationr/w
Enumerated Values:
1off
2thru
3invert
.1.3.6.1.4.1.1909.10.7.7.1.3
Threshold of mains input part B
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.7.1.4
Determines the operating mode of comparison operation A.
Can be set to greater(2) ' >', less(3) '<' or turned off(1),
if not needed
Enumerationr/w
Enumerated Values:
1off
2greater
3less
.1.3.6.1.4.1.1909.10.7.7.1.5
Threshold of mains input part B
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.7.1.6
Determines the operating mode of comparison operation B.
Can be set to greater(2) ' >', less(3) '<' or turned off(1),
if not needed
Enumerationr/w
Enumerated Values:
1off
2greater
3less
.1.3.6.1.4.1.1909.10.7.7.1.7

filterFeedbackTable

table mandatory
.1.3.6.1.4.1.1909.10.7.8 · 1 row entry · 7 columns
Uses the infratec variant from /opt/observium/mibs/infratec.
Command help
Walk filterFeedbackTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'INFRATEC-RMS-MIB' -M '/opt/observium/mibs/infratec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'INFRATEC-RMS-MIB::filterFeedbackTable'
Table containing information about feedback inputs
filterFeedbackEntry row .1.3.6.1.4.1.1909.10.7.8.1
Each entry contains the description of one filter
Column Syntax OID
Index of the filter
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.8.1.1
Index of the feedback input
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.8.1.2
Number of the filter which is connected
to this feedback input
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.8.1.3
Delay time to wait until signal is forwarded
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.8.1.4
Determines the way an incoming signal is forwarded to the
filter structure.
If set to thru(1), all incoming signals are straight
forwarded.
If set to conditional(2), an incoming signal only will be
forwarded, if aft…
Enumerationr/w
Enumerated Values:
1thru
2conditional
.1.3.6.1.4.1.1909.10.7.8.1.5
Determines the time the passed signal will be held up, after
the falling edge of the original trigger signal.
See timing diagram in manual for further details.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.8.1.6
Determines the way the result of feedback input effects
the filter. Can be switched off(1), inverted(3) or passed
thru (2).
Enumerationr/w
Enumerated Values:
1off
2on
3invert
.1.3.6.1.4.1.1909.10.7.8.1.7

messageTable

table mandatory
.1.3.6.1.4.1.1909.10.8.1 · 1 row entry · 6 columns
Uses the infratec variant from /opt/observium/mibs/infratec.
Command help
Walk messageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'INFRATEC-RMS-MIB' -M '/opt/observium/mibs/infratec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'INFRATEC-RMS-MIB::messageTable'
The message table contains the logged filter events
messageEntry row .1.3.6.1.4.1.1909.10.8.1.1
Each entry contains information of one message
Indexes
Column Syntax OID
messageIndexmandatory
Index of message line
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.8.1.1.1
messageFiltermandatory
Number of filter which caused the message
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.8.1.1.2
Name of the filter which caused the message
.1.3.6.1.4.1.1909.10.8.1.1.3
messageTimemandatory
Timestamp of event
RFC1155-SMITimeTicks
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.1909.10.8.1.1.4
Priority of the message. If set to no-priority(1) no message
will be logged. The Priority has only informational character
and doesn't affect the way it is handled
Enumeration
Enumerated Values:
1no-priority
2warning
3critical
.1.3.6.1.4.1.1909.10.8.1.1.5
Displays, if event was acknoledged already. Has only
informational character for operator
Enumerationr/w
Enumerated Values:
1not-acknowledged
2acknowledged
.1.3.6.1.4.1.1909.10.8.1.1.6

userTable

table mandatory
.1.3.6.1.4.1.1909.10.9.1 · 1 row entry · 5 columns
Uses the infratec variant from /opt/observium/mibs/infratec.
Command help
Walk userTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'INFRATEC-RMS-MIB' -M '/opt/observium/mibs/infratec:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'INFRATEC-RMS-MIB::userTable'
Some infos about all registered users, e.g.
name, right and chipcard key (if reader installed)
userEntry row .1.3.6.1.4.1.1909.10.9.1.1
Each entry contains information about one user
Indexes
Column Syntax OID
userIndexmandatory
Index of user. Is dynamically filled from 1..n
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.9.1.1.1
userNamemandatory
name of one user
.1.3.6.1.4.1.1909.10.9.1.1.2
userRightmandatory
Access right of one user
Enumeration
Enumerated Values:
1readonly
2readwrite
.1.3.6.1.4.1.1909.10.9.1.1.3
Displays the chipcard key of this user -
only available, if optional chipcard reader installed.
.1.3.6.1.4.1.1909.10.9.1.1.4
Holds the status of the last access try via
chipcard reader. In case of failure a rmsChipcardTrap
will be sent.
Enumeration
Enumerated Values:
1denied
2granted
.1.3.6.1.4.1.1909.10.9.1.1.5