ICT-MODULAR-POWER-MIB

Monitored by Observium
Observium actively monitors this MIB
Observium uses this MIB in discovery or polling workflows on applicable devices.
Device identity Sensors Status
Explore Observium network monitoring
Source file
ICT-MODULAR-POWER-MIB
Last revised
Not declared
Imported Objects
RFC-1212 OBJECT-TYPE (no object page)
RFC-1215 TRAP-TYPE (no object page)
RFC1155-SMI enterprises IpAddress
RFC1213-MIB DisplayString
Objects (34)
12 directly used by Observium
.1.3.6.1.4.1.39145
.1.3.6.1.4.1.39145.13
deviceModel OBS ✓ mandatory
.1.3.6.1.4.1.39145.13.1
moduleTable mandatory
.1.3.6.1.4.1.39145.13.10
moduleEntry mandatory
.1.3.6.1.4.1.39145.13.10.1
moduleNumber mandatory
Integer32
.1.3.6.1.4.1.39145.13.10.1.1
moduleControlB mandatory r/w
Enumeration
.1.3.6.1.4.1.39145.13.10.1.10
moduleControlC mandatory r/w
Enumeration
.1.3.6.1.4.1.39145.13.10.1.11
moduleControlD mandatory r/w
Enumeration
.1.3.6.1.4.1.39145.13.10.1.12
moduleStatus OBS ✓ mandatory
Enumeration
.1.3.6.1.4.1.39145.13.10.1.2
moduleType mandatory
Enumeration
.1.3.6.1.4.1.39145.13.10.1.3
moduleVoltage OBS ✓ mandatory
.1.3.6.1.4.1.39145.13.10.1.4
moduleCurrentA OBS ✓ mandatory
.1.3.6.1.4.1.39145.13.10.1.5
moduleCurrentB OBS ✓ mandatory
.1.3.6.1.4.1.39145.13.10.1.6
moduleCurrentC OBS ✓ mandatory
.1.3.6.1.4.1.39145.13.10.1.7
moduleCurrentD OBS ✓ mandatory
.1.3.6.1.4.1.39145.13.10.1.8
moduleControlA mandatory r/w
Enumeration
.1.3.6.1.4.1.39145.13.10.1.9
alarmTable mandatory
.1.3.6.1.4.1.39145.13.11
alarmEntry mandatory
.1.3.6.1.4.1.39145.13.11.1
alarmNumber mandatory
Integer32
.1.3.6.1.4.1.39145.13.11.1.1
alarmName mandatory
.1.3.6.1.4.1.39145.13.11.1.2
alarmStatus mandatory
Enumeration
.1.3.6.1.4.1.39145.13.11.1.3
batteryTemperature mandatory
.1.3.6.1.4.1.39145.13.12
batterySoc mandatory
Integer32
.1.3.6.1.4.1.39145.13.13
batteryNetAh mandatory
.1.3.6.1.4.1.39145.13.14
batteryRunTime mandatory
.1.3.6.1.4.1.39145.13.15
deviceName mandatory
.1.3.6.1.4.1.39145.13.2
deviceHardware mandatory
Integer32
.1.3.6.1.4.1.39145.13.3
deviceFirmware OBS ✓ mandatory
.1.3.6.1.4.1.39145.13.4
deviceMacAddress mandatory
.1.3.6.1.4.1.39145.13.5
inputVoltage OBS ✓ mandatory
.1.3.6.1.4.1.39145.13.6
outputVoltage OBS ✓ mandatory
.1.3.6.1.4.1.39145.13.7
outputCurrent OBS ✓ mandatory
.1.3.6.1.4.1.39145.13.8
outputEnable OBS ✓ mandatory r/w
Enumeration
.1.3.6.1.4.1.39145.13.9
Dependencies (7) 4 direct · 3 transitive Show tree and compile order Hide dependency details

Each imported module is resolved in the importing module's source directory first, then through the normal default-variant rules.

Dependency tree
Dependency-first compile order
  1. RFC-1212rfc
  2. RFC-1215rfc
  3. RFC1155-SMIrfc
  4. SNMPv2-SMIrfc
  5. SNMPv2-TCrfc
  6. IANAifType-MIBrfc
  7. RFC1213-MIBrfc
  8. ICT-MODULAR-POWER-MIBictselected
Notifications / Traps (13)
NameOIDDescription
.1.3.6.1.4.1.39145.13.0.101
Trap generated when a Module Alarm is triggered
.1.3.6.1.4.1.39145.13.0.102
Trap generated when an Alarm Input is activated
.1.3.6.1.4.1.39145.13.0.103
Trap generated when the AC Failure Alarm is triggered
.1.3.6.1.4.1.39145.13.0.104
Trap generated when the System Current Limit Alarm is triggered
.1.3.6.1.4.1.39145.13.0.111
Trap generated when a Module Alarm is cleared
.1.3.6.1.4.1.39145.13.0.112
Trap generated when an Alarm Input is cleared
.1.3.6.1.4.1.39145.13.0.113
Trap generated when the AC Failure Alarm is cleared
.1.3.6.1.4.1.39145.13.0.114
Trap generated when the System Current Limit Alarm is cleared
.1.3.6.1.4.1.39145.13.0.121
Trap generated when a Battery Discharge Test is started
.1.3.6.1.4.1.39145.13.0.122
Trap generated when a Battery Discharge Test completes successfully
.1.3.6.1.4.1.39145.13.0.123
Trap generated when a Battery Discharge Test fails
.1.3.6.1.4.1.39145.13.0.124
Trap generated when a Battery Equalise Charge is started
.1.3.6.1.4.1.39145.13.0.125
Trap generated when a Battery Equalise Charge completes