HUAWEI-UPS-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
16
Rows
16
Columns
188
.1.3.6.1.4.1.2011.6.174.1.2.100 · 1 row entry · 11 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwUpsDeviceIdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-UPS-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-UPS-MIB::hwUpsDeviceIdentTable'
The device identification table. Use this table to get device ID, and to get device type,
the soft version, the iner prot version, the ESN, the rating power of device, 
the parallel system index of device. This table's index is hwUpsDeviceId.
hwUpsDeviceIdentEntry row .1.3.6.1.4.1.2011.6.174.1.2.100.1
The device identification table. Use this table to get device ID, and to get device type,
the soft version, the iner prot version, the ESN, the rating power of device,
the parallel system index of device. This table's …
Indexes
Column Syntax OID
Rack ID, ranging from 1 to 100. This node is referenced as an index node
by hwUpsDeviceIdentTable, hwUpsDeviceOperInfoTable, hwUpsInputTable,
hwUpsOutputTable,hwUpsBypassTable, hwUpsBatteryTable, hwUpsControlTable,
a…
Unsigned32
Constraints:
range: 1-100
.1.3.6.1.4.1.2011.6.174.1.2.100.1.1
Device model. A string of characters.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.2011.6.174.1.2.100.1.2
Device software version number. A string of characters.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.2011.6.174.1.2.100.1.3
Interface protocol version number for the current device. A string of characters.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.2011.6.174.1.2.100.1.4
ESN. A string of characters.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.2011.6.174.1.2.100.1.5
System capacity. Enumeration type. The default value is 5. The unit is kVA.
Value 1 indicates 80 kVA
Value 2 indicates 100 kVA.
Value 3 indicates 120 kVA.
Value 4 indicates 160 kVA.
Value 5 indicates 200 kVA.
Enumeration
Enumerated Values:
1level80
2level100
3level120
4level160
5level200
6level30
7level40
8level60
9level240
10level250
11level280
12level300
.1.3.6.1.4.1.2011.6.174.1.2.100.1.6
ID of the parallel system that the current device belongs to. An integer ranging from 0 to 63.
Unsigned32
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.174.1.2.100.1.7
System grant.An integer ranging from 0 to 10000.
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.2.100.1.8
Monitor software version number. A string of characters.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.2011.6.174.1.2.100.1.9
Power software version number A string of characters.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.2011.6.174.1.2.100.1.10
RowStatus of UPS device Identification table.
RowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.174.1.2.100.1.100
.1.3.6.1.4.1.2011.6.174.1.2.101 · 1 row entry · 12 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwUpsDeviceOperInfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-UPS-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-UPS-MIB::hwUpsDeviceOperInfoTable'
Device running information table. It's index is hwUpsDeviceId
hwUpsDeviceOperInfoEntry row .1.3.6.1.4.1.2011.6.174.1.2.101.1
Device running information table. It's index is hwUpsDeviceId
Indexes
Column Syntax OID
Device power supply mode. Enumeration type.
Value 1 indicates no power supply.
Value 2 indicates bypass mode.
Value 3 indicates normal mode.
Value 4 indicates battery mode.
Value 5 indicates combined mode.
Value 6 indic…
Enumeration
Enumerated Values:
1noOutput
2bypass
3normal
4battery
5sourceShare
6normalECO
7batteryECO
.1.3.6.1.4.1.2011.6.174.1.2.101.1.1
UPS operating status. Enumeration type.
Value 1 indicates that a single UPS is operating.
Value 2 indicates that the parallel system is operating.
Value 3 indicates that a single UPS is operating in ECO mode.
Value 4 in…
Enumeration
Enumerated Values:
1single
2parallel
3singleECO
4parallelECO
5aging
.1.3.6.1.4.1.2011.6.174.1.2.101.1.2
Battery status. Enumeration type.
Value 1 indicates that no battery is connected.
Value 2 indicates that the battery is not charging or discharging.
Value 3 indicates hibernation.
Value 4 indicates float charging.
Value…
Enumeration
Enumerated Values:
1notExist
2temperaryMode
3sleep
4floatCharge
5boostCharge
6discharge
.1.3.6.1.4.1.2011.6.174.1.2.101.1.3
Maximum temperature of the modules in the current device. An integer ranging from 0 to 300.
Unsigned32
Constraints:
range: 0-3000
.1.3.6.1.4.1.2011.6.174.1.2.101.1.4
Current flow status. An integer ranging from 0 to 70000.
Unsigned32
Constraints:
range: 0-70000
.1.3.6.1.4.1.2011.6.174.1.2.101.1.5
Redundant number of the parallel system. An integer ranging from 0 to 3.
Unsigned32
Constraints:
range: 0-3
.1.3.6.1.4.1.2011.6.174.1.2.101.1.6
Delay to shutdown state. An integer ranging from 0 to 4294967295
Unsigned32
Constraints:
range: 0-4294967295
.1.3.6.1.4.1.2011.6.174.1.2.101.1.7
Delay to shutdown state. Enumeration type.
Value 1 indicates invalid.
Value 2 indicates valid.
Enumeration
Enumerated Values:
1invalid
2valid
.1.3.6.1.4.1.2011.6.174.1.2.101.1.8
Work Mode. Enumeration type.
Value 1 indicates that normal mode.
Value 2 indicates that eco mode.
Value 3 indicates that self load mode.
Value 4 indicates that converter mode.
Enumeration
Enumerated Values:
1normalMode
2ecoMode
3selfloadMode
4converterMode
.1.3.6.1.4.1.2011.6.174.1.2.101.1.9
Smart Power Mode.Enumeration type.
Value 1 indicates that disable.
Value 2 indicates that enable.
Enumeration
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2011.6.174.1.2.101.1.10
BSC system status. Enumeration type.
Value 1: Not activated
Value 2: BSC master mode
Value 3: BSC slave mode
Enumeration
Enumerated Values:
1notExist
2masterMode
3slaveMode
.1.3.6.1.4.1.2011.6.174.1.2.101.1.11
RowStatus of UPS device running information table.
RowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.174.1.2.101.1.101
.1.3.6.1.4.1.2011.6.174.1.3.100 · 1 row entry · 14 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwUpsInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-UPS-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-UPS-MIB::hwUpsInputTable'
UPS input information table. It's index is hwUpsDeviceId
hwUpsInputEntry row .1.3.6.1.4.1.2011.6.174.1.3.100.1
UPS input information table. It's index is hwUpsDeviceId
Indexes
Column Syntax OID
Input voltage phase A. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is V.
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.3.100.1.1
Input voltage phase B. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is V.
VUnsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.3.100.1.2
Input voltage phase C. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is V.
VUnsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.3.100.1.3
Input frequency. The value ranges from 0 to 10000.
The value is accurate to two decimal place on the NetEco. The unit is Hz.
HzUnsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.3.100.1.4
Input current phase A. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is A.
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.3.100.1.5
Input current phase B. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is A.
AUnsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.3.100.1.6
Input current phase C. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is A.
AUnsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.3.100.1.7
Phase A input power factor. The value ranges from -100 to 100.
The value is accurate to one decimal place on the NetEco.
Integer32
Constraints:
range: -100-100
.1.3.6.1.4.1.2011.6.174.1.3.100.1.8
Phase B input power factor. The value ranges from -100 to 100.
The value is accurate to one decimal place on the NetEco.
Integer32
Constraints:
range: -100-100
.1.3.6.1.4.1.2011.6.174.1.3.100.1.9
Phase C input power factor. The value ranges from -100 to 100.
The value is accurate to one decimal place on the NetEco.
Integer32
Constraints:
range: -100-100
.1.3.6.1.4.1.2011.6.174.1.3.100.1.10
Input Line voltage AB. The value ranges from 0 to 20000.
The value is accurate to one decimal place on the NetEco. The unit is V.
Unsigned32
Constraints:
range: 0-20000
.1.3.6.1.4.1.2011.6.174.1.3.100.1.11
Input Line voltage BC. The value ranges from 0 to 20000.
The value is accurate to one decimal place on the NetEco. The unit is V.
Unsigned32
Constraints:
range: 0-20000
.1.3.6.1.4.1.2011.6.174.1.3.100.1.12
Input Line voltage CA. The value ranges from 0 to 20000.
The value is accurate to one decimal place on the NetEco. The unit is V.
Unsigned32
Constraints:
range: 0-20000
.1.3.6.1.4.1.2011.6.174.1.3.100.1.13
RowStatus of UPS input information table.
RowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.174.1.3.100.1.100
.1.3.6.1.4.1.2011.6.174.1.4.100 · 1 row entry · 28 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwUpsOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-UPS-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-UPS-MIB::hwUpsOutputTable'
UPS output information table. It's index is hwUpsDeviceId.
hwUpsOutputEntry row .1.3.6.1.4.1.2011.6.174.1.4.100.1
UPS output information table. It's index is hwUpsDeviceId.
Indexes
Column Syntax OID
Rack phase A output voltage. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is V.
VUnsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.4.100.1.1
Rack phase B output voltage. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is V.
VUnsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.4.100.1.2
Rack phase C output voltage. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is V.
VUnsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.4.100.1.3
Rack phase A output current. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is A.
AUnsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.4.100.1.4
Rack phase B output current. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is A.
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.4.100.1.5
Rack phase C output current. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is A.
AUnsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.4.100.1.6
Rack output frequency. The value ranges from 0 to 10000.
The value is accurate to two decimal place on the NetEco. The unit is Hz.
HzUnsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.4.100.1.7
Rack phase A output active power. The value ranges from -12000 to 12000.
The value is accurate to one decimal place on the NetEco. The unit is kW.
kWInteger32
Constraints:
range: -12000-12000
.1.3.6.1.4.1.2011.6.174.1.4.100.1.8
Rack phase B output active power. The value ranges from -12000 to 12000.
The value is accurate to one decimal place on the NetEco. The unit is kW.
kWInteger32
Constraints:
range: -12000-12000
.1.3.6.1.4.1.2011.6.174.1.4.100.1.9
Rack phase C output active power. The value ranges from -12000 to 12000.
The value is accurate to one decimal place on the NetEco. The unit is kW.
kWInteger32
Constraints:
range: -12000-12000
.1.3.6.1.4.1.2011.6.174.1.4.100.1.10
Rack phase A output apparent power. The value ranges from -12000 to 12000.
The value is accurate to one decimal place on the NetEco. The unit is kVA.
kVAInteger32
Constraints:
range: -12000-12000
.1.3.6.1.4.1.2011.6.174.1.4.100.1.11
Rack phase B output apparent power. The value ranges from -12000 to 12000.
The value is accurate to one decimal place on the NetEco. The unit is kVA.
kVAInteger32
Constraints:
range: -12000-12000
.1.3.6.1.4.1.2011.6.174.1.4.100.1.12
Rack phase C output apparent power. The value ranges from -12000 to 12000.
The value is accurate to one decimal place on the NetEco. The unit is kVA.
kVAInteger32
Constraints:
range: -12000-12000
.1.3.6.1.4.1.2011.6.174.1.4.100.1.13
Rack phase A output load ratio. The value ranges from 0 to 5000 The value is accurate to one decimal place on the NetEco.
%Unsigned32
Constraints:
range: 0-999
.1.3.6.1.4.1.2011.6.174.1.4.100.1.14
Rack phase B output load ratio. The value ranges from 0 to 5000 The value is accurate to one decimal place on the NetEco.
%Unsigned32
Constraints:
range: 0-999
.1.3.6.1.4.1.2011.6.174.1.4.100.1.15
Rack phase C output load ratio. The value ranges from 0 to 5000 The value is accurate to one decimal place on the NetEco.
Unsigned32
Constraints:
range: 0-999
.1.3.6.1.4.1.2011.6.174.1.4.100.1.16
Rated output voltage (system voltage level). Enumeration type. The default value is 6. The unit is V.
Value 1 indicates 200 V.
Value 2 indicates 208 V.
Value 3 indicates 220 V.
Value 4 indicates 380 V.
Value 5 indicate…
Enumeration
Enumerated Values:
1level200
2level208
3level220
4level380
5level400
6level415
7level480
8level600
9level690
.1.3.6.1.4.1.2011.6.174.1.4.100.1.17
Rated output frequency. Enumeration type. The default value is 2. The unit is Hz.
Value 1 indicates 50 Hz.
Value 2 indicates 60 Hz.
Enumeration
Enumerated Values:
1level50
2level60
.1.3.6.1.4.1.2011.6.174.1.4.100.1.18
Rack phase A output power factor.
The value ranges from -100 to 100 The value is accurate to two decimal place on the NetEco.
Integer32
Constraints:
range: -100-100
.1.3.6.1.4.1.2011.6.174.1.4.100.1.19
Rack phase B output power factor.
The value ranges from -100 to 100 The value is accurate to two decimal place on the NetEco.
Integer32
Constraints:
range: -100-100
.1.3.6.1.4.1.2011.6.174.1.4.100.1.20
Rack phase C output power factor.
The value ranges from -100 to 100 The value is accurate to two decimal place on the NetEco.
Integer32
Constraints:
range: -100-100
.1.3.6.1.4.1.2011.6.174.1.4.100.1.21
Rack Line AB output voltage. The value ranges from 0 to 20000.
The value is accurate to one decimal place on the NetEco. The unit is V.
Unsigned32
Constraints:
range: 0-20000
.1.3.6.1.4.1.2011.6.174.1.4.100.1.22
Rack Line BC output voltage. The value ranges from 0 to 20000.
The value is accurate to one decimal place on the NetEco. The unit is V.
Unsigned32
Constraints:
range: 0-20000
.1.3.6.1.4.1.2011.6.174.1.4.100.1.23
Rack Line CA output voltage. The value ranges from 0 to 20000.
The value is accurate to one decimal place on the NetEco. The unit is V.
Unsigned32
Constraints:
range: 0-20000
.1.3.6.1.4.1.2011.6.174.1.4.100.1.24
Rack A Out Peak Ratio. The value ranges from 0 to 1000.
The value is accurate to one decimal place on the NetEco. The unit is %.
Unsigned32
Constraints:
range: 0-1000
.1.3.6.1.4.1.2011.6.174.1.4.100.1.25
Rack B Out Peak Ratio. The value ranges from 0 to 1000.
The value is accurate to one decimal place on the NetEco. The unit is %.
Unsigned32
Constraints:
range: 0-1000
.1.3.6.1.4.1.2011.6.174.1.4.100.1.26
Rack C Out Peak Ratio. The value ranges from 0 to 1000.
The value is accurate to one decimal place on the NetEco. The unit is %.
Unsigned32
Constraints:
range: 0-1000
.1.3.6.1.4.1.2011.6.174.1.4.100.1.27
RowStatus of UPS output information table.
RowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.174.1.4.100.1.100
.1.3.6.1.4.1.2011.6.174.1.5.100 · 1 row entry · 11 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwUpsBypassTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-UPS-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-UPS-MIB::hwUpsBypassTable'
UPS bypass information table. It's index is hwUpsDeviceId.
hwUpsBypassEntry row .1.3.6.1.4.1.2011.6.174.1.5.100.1
UPS bypass information table. It's index is hwUpsDeviceId.
Indexes
Column Syntax OID
Bypass input voltage phase A. The value ranges from 0 to 10000
The value is accurate to one decimal place on the NetEco. The unit is V.
VUnsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.5.100.1.1
Bypass input voltage phase B. The value ranges from 0 to 10000
The value is accurate to one decimal place on the NetEco. The unit is V.
VUnsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.5.100.1.2
Bypass input voltage phase C. The value ranges from 0 to 10000
The value is accurate to one decimal place on the NetEco. The unit is V.
VUnsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.5.100.1.3
Bypass input frequency. The value ranges from 0 to 10000
The value is accurate to two decimal place on the NetEco. The unit is Hz.
HzUnsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.5.100.1.4
Bypass input current phase A. The value ranges from 0 to 60000
The value is accurate to one decimal place on the NetEco. The unit is A.
Unsigned32
Constraints:
range: 0-60000
.1.3.6.1.4.1.2011.6.174.1.5.100.1.5
Bypass input current phase B. The value ranges from 0 to 60000
The value is accurate to one decimal place on the NetEco. The unit is A.
Unsigned32
Constraints:
range: 0-60000
.1.3.6.1.4.1.2011.6.174.1.5.100.1.6
Bypass input current phase C. The value ranges from 0 to 60000
The value is accurate to one decimal place on the NetEco. The unit is A.
Unsigned32
Constraints:
range: 0-60000
.1.3.6.1.4.1.2011.6.174.1.5.100.1.7
Bypass Input Line voltage AB. The value ranges from 0 to 20000.
The value is accurate to one decimal place on the NetEco. The unit is V.
Unsigned32
Constraints:
range: 0-20000
.1.3.6.1.4.1.2011.6.174.1.5.100.1.8
Bypass Input Line voltage BC. The value ranges from 0 to 20000.
The value is accurate to one decimal place on the NetEco. The unit is V.
Unsigned32
Constraints:
range: 0-20000
.1.3.6.1.4.1.2011.6.174.1.5.100.1.9
Bypass Input Line voltage CA. The value ranges from 0 to 20000.
The value is accurate to one decimal place on the NetEco. The unit is V.
Unsigned32
Constraints:
range: 0-20000
.1.3.6.1.4.1.2011.6.174.1.5.100.1.10
RowStatus of UPS bypass information table.
RowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.174.1.5.100.1.100
.1.3.6.1.4.1.2011.6.174.1.6.100 · 1 row entry · 8 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwUpsBatteryTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-UPS-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-UPS-MIB::hwUpsBatteryTable'
UPS battery information table. It's index is hwUpsDeviceId.
hwUpsBatteryEntry row .1.3.6.1.4.1.2011.6.174.1.6.100.1
UPS battery information table. It's index is hwUpsDeviceId.
Indexes
Column Syntax OID
Battery Voltage. It is a real-time analog parameter.
Value range: 0 to 20000, Unit: V, and the value is accurate to one decimal place (.1).
VUnsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.6.100.1.1
Battery Total Current. It is a real-time analog parameter.
Value range: -60000 to 60000, Unit: A, and the value is accurate to one decimal place (.1).
AInteger32
Constraints:
range: -60000-60000
.1.3.6.1.4.1.2011.6.174.1.6.100.1.2
Battery Capacity Left. Value range: 0 to 100, Unit: %, and the value is an integer.
%Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.174.1.6.100.1.3
Battery Backup Time. Value range: 0 to 172800, Unit: S, and the value is an integer.
SUnsigned32
Constraints:
range: 0-172800
.1.3.6.1.4.1.2011.6.174.1.6.100.1.4
Battery group number.Value range: 1 to 240,and the value is an integer.
Unsigned32
Constraints:
range: 1-240
.1.3.6.1.4.1.2011.6.174.1.6.100.1.5
Battery temperature.Value range: -20 to 80, Unit:C, and the value is accurate to one decimal place (.1)
CUnsigned32
Constraints:
range: 800-18446744073709551416
.1.3.6.1.4.1.2011.6.174.1.6.100.1.6
Description.
Enumeration
Enumerated Values:
1good
2requiringMaintenance
3repalceBatt
.1.3.6.1.4.1.2011.6.174.1.6.100.1.7
RowStatus of UPS battery information table.
RowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.174.1.6.100.1.100
.1.3.6.1.4.1.2011.6.174.1.10.1 · 1 row entry · 11 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwUpsParaSysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-UPS-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-UPS-MIB::hwUpsParaSysTable'
/
hwUpsParaSysEntry row .1.3.6.1.4.1.2011.6.174.1.10.1.1
/
Indexes
Column Syntax OID
ID of the parallel system that the current rack belongs to.
Unsigned32
Constraints:
range: 0-127
.1.3.6.1.4.1.2011.6.174.1.10.1.1.1
System phase A output active power.The value ranges from -12000 to 12000,
The value is accurate to one decimal place on the NetEco. The unit is kW.
Integer32
Constraints:
range: -120000-120000
.1.3.6.1.4.1.2011.6.174.1.10.1.1.2
System phase B output active power.The value ranges from -12000 to 12000,
The value is accurate to one decimal place on the NetEco. The unit is kW.
Integer32
Constraints:
range: -120000-120000
.1.3.6.1.4.1.2011.6.174.1.10.1.1.3
System phase C output active power.The value ranges from -12000 to 12000,
The value is accurate to one decimal place on the NetEco. The unit is kW.
Integer32
Constraints:
range: -120000-120000
.1.3.6.1.4.1.2011.6.174.1.10.1.1.4
System phase A output apparent power.The value ranges from -12000 to 12000,
The value is accurate to one decimal place on the NetEco. The unit is kVA.
Integer32
Constraints:
range: -120000-120000
.1.3.6.1.4.1.2011.6.174.1.10.1.1.5
System phase B output apparent power.The value ranges from -12000 to 12000,
The value is accurate to one decimal place on the NetEco. The unit is kVA.
Integer32
Constraints:
range: -120000-120000
.1.3.6.1.4.1.2011.6.174.1.10.1.1.6
System phase C output apparent power.The value ranges from -12000 to 12000,
The value is accurate to one decimal place on the NetEco. The unit is kVA.
Integer32
Constraints:
range: -120000-120000
.1.3.6.1.4.1.2011.6.174.1.10.1.1.7
System A output load factor.The value ranges from 0 to 500,
The value is accurate to one decimal place on the NetEco. The unit is %
Unsigned32
Constraints:
range: 0-5000
.1.3.6.1.4.1.2011.6.174.1.10.1.1.8
System B output load factor.The value ranges from 0 to 500,
The value is accurate to one decimal place on the NetEco. The unit is %.
Unsigned32
Constraints:
range: 0-5000
.1.3.6.1.4.1.2011.6.174.1.10.1.1.9
System C output load factor.The value ranges from 0 to 500,
The value is accurate to one decimal place on the NetEco. The unit is %.
Unsigned32
Constraints:
range: 0-5000
.1.3.6.1.4.1.2011.6.174.1.10.1.1.10
RowStatus of ups parallel System Identification table.
RowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.174.1.10.1.1.100
.1.3.6.1.4.1.2011.6.174.1.13.1 · 1 row entry · 11 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwUpsActiveAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-UPS-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-UPS-MIB::hwUpsActiveAlarmTable'
UPS active alarm table. It's indexs are hwUpsActiveAlarmDeviceId and hwUpsActiveAlarmSeqId
hwUpsActiveAlarmEntry row .1.3.6.1.4.1.2011.6.174.1.13.1.1
UPS active alarm table. It's indexs are hwUpsActiveAlarmDeviceId and hwUpsActiveAlarmSeqId
Column Syntax OID
ID of the device on which the active alarm is generated. An integer ranging from 1 to 100.
Unsigned32
Constraints:
range: 1-100
.1.3.6.1.4.1.2011.6.174.1.13.1.1.1
Sequence number of an active alarm, ranging from 1 to 4294967295.
Unsigned32
Constraints:
range: 1-4294967295
.1.3.6.1.4.1.2011.6.174.1.13.1.1.2
Active alarm module ID, ranging from 1 to 10000.
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.13.1.1.3
ID of an active alarm, ranging from 0 to 4294967295.
Unsigned32
Constraints:
range: 0-4294967295
.1.3.6.1.4.1.2011.6.174.1.13.1.1.4
Reason ID of an active alarm, ranging from 1 to 100.
Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.174.1.13.1.1.5
English name of an active alarm. A string of characters.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.2011.6.174.1.13.1.1.6
Severity of an active alarm. Enumeration type.
Value 1 indicates a critical alarm.
Value 2 indicates a major alarm.
Value 3 indicates a minor alarm.
Value 4 indicates a warning.
Enumeration
Enumerated Values:
1critical
2major
3minor
4warning
.1.3.6.1.4.1.2011.6.174.1.13.1.1.7
Flag bit of an active alarm. Enumeration type.
Value 1 indicates that an active alarm is generated.
Value 2 indicates that an active alarm is cleared.
Enumeration
Enumerated Values:
1occur
2resume
.1.3.6.1.4.1.2011.6.174.1.13.1.1.8
Active alarm synchronization ID, ranging from 0 to 4294967295.
Unsigned32
Constraints:
range: 0-4294967295
.1.3.6.1.4.1.2011.6.174.1.13.1.1.9
Time when an active alarm is generated, ranging from 0 to 4294967295. The unit is seconds.
Unsigned32
Constraints:
range: 0-4294967295
.1.3.6.1.4.1.2011.6.174.1.13.1.1.10
RowStatus of ups active alarm table.
RowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.174.1.13.1.1.11
.1.3.6.1.4.1.2011.6.174.1.102.100 · 1 row entry · 22 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwUpsControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-UPS-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-UPS-MIB::hwUpsControlTable'
UPS control table. It's index is hwUpsRackId.
hwUpsControlEntry row .1.3.6.1.4.1.2011.6.174.1.102.100.1
UPS control table. It's index is hwUpsRackId.
Indexes
Column Syntax OID
ECO settings. Enumeration type. The default value is 1.
Value 1 indicates ECO mode.
Value 2 indicates Non ECO mode.
Enumeration
Enumerated Values:
1noECO
2eco
.1.3.6.1.4.1.2011.6.174.1.102.100.1.1
Power on settings. Enumeration type.
Value 1 indicates power on .
Value 2 indicates unknow.
Enumeration
Enumerated Values:
1powerOn
255unknown
.1.3.6.1.4.1.2011.6.174.1.102.100.1.2
Power off settings. Enumeration type.
Value 1 indicates power off .
Value 2 indicates unknow.
Enumeration
Enumerated Values:
1powerOff
255unknown
.1.3.6.1.4.1.2011.6.174.1.102.100.1.3
Delay power off.The value ranges from 0 to 120000000 . The unit is S.
SUnsigned32
Constraints:
range: 0-120000000
.1.3.6.1.4.1.2011.6.174.1.102.100.1.4
Battery capacity, ranging from 5 to 3000.
Unsigned32
Constraints:
range: 5-3000
.1.3.6.1.4.1.2011.6.174.1.102.100.1.5
Battery type.ECO settings. Enumeration type. The default value is 1.
Value 1 indicates VRLA batteries.
Enumeration
Enumerated Values:
1vrla
.1.3.6.1.4.1.2011.6.174.1.102.100.1.6
Model type,Enumeration type.
Value 17 indicates 6K.
Value 33 indicates 10K.
Value 65 indicates 20K.
Enumeration
Enumerated Values:
17model6K
33mode110K
65model20K
.1.3.6.1.4.1.2011.6.174.1.102.100.1.7
Input Standard,Enumeration type.
Value 1 indicates single phase.
Value 2 indicates three phase.
Enumeration
Enumerated Values:
1singlePhase
2threePhase
.1.3.6.1.4.1.2011.6.174.1.102.100.1.8
Power On State,Enumeration type.
Value 1 indicates power off.
Value 2 indicates booting.
Value 3 indicates failed to power on.
Value 4 indicates succeed tp power on.
Enumeration
Enumerated Values:
1powerOff
2powerOn
3powerOnFail
4powerOnComplete
.1.3.6.1.4.1.2011.6.174.1.102.100.1.10
Battery Change to Boost Charge State,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates disabled.
Enumeration
Enumerated Values:
1enable
2disable
.1.3.6.1.4.1.2011.6.174.1.102.100.1.11
Battery Change to Float Charge State,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates disabled.
Enumeration
Enumerated Values:
1enable
2disable
.1.3.6.1.4.1.2011.6.174.1.102.100.1.12
Battery Change to Test State,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates disabled.
Enumeration
Enumerated Values:
1enable
2disable
3shallow
.1.3.6.1.4.1.2011.6.174.1.102.100.1.13
Battery Stop Test State,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates disabled.
Enumeration
Enumerated Values:
1enable
2disable
.1.3.6.1.4.1.2011.6.174.1.102.100.1.14
Battery Manual to Boost Charge,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates disabled.
Enumeration
Enumerated Values:
1toBoostCharge
255unknown
.1.3.6.1.4.1.2011.6.174.1.102.100.1.15
Battery Manual to Float Charge,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates unknown
Enumeration
Enumerated Values:
1toFloatCharge
255unknown
.1.3.6.1.4.1.2011.6.174.1.102.100.1.16
Battery Shallow Test,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates unknown
Enumeration
Enumerated Values:
1toShallowTest
255unknown
.1.3.6.1.4.1.2011.6.174.1.102.100.1.17
Battery Verify Cap Test,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates unknown
Enumeration
Enumerated Values:
1toVerifyCapTest
255unknown
.1.3.6.1.4.1.2011.6.174.1.102.100.1.18
Battery End Test,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates unknown
Enumeration
Enumerated Values:
1toEndTest
255unknown
.1.3.6.1.4.1.2011.6.174.1.102.100.1.19
Model Capacity.The value ranges from 0 to 200, The value is accurate to one decimal place on the NetEco. The unit is kVA.
Unsigned32
Constraints:
range: 0-200
.1.3.6.1.4.1.2011.6.174.1.102.100.1.20
hwUpsCtrlEPOobsolete
EPO. Enumeration type.
Value 1 indicates EPO .
Value 255 indicates unknown.
Enumeration
Enumerated Values:
1epo
2unknown
.1.3.6.1.4.1.2011.6.174.1.102.100.1.21
Smart Parallel Sleep Mode.Enumeration type.The default value is 0.
Value 0 indicates disable.
Value 1 indicates enable.
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2011.6.174.1.102.100.1.22
RowStatus of UPS rack control table.
RowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.174.1.102.100.1.100
.1.3.6.1.4.1.2011.6.174.1.103.101 · 1 row entry · 7 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwUpsBattScheduleTestTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-UPS-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-UPS-MIB::hwUpsBattScheduleTestTable'
Battery schedule test table. It's index is hwUpsDeviceId.
hwUpsBattScheduleTestEntry row .1.3.6.1.4.1.2011.6.174.1.103.101.1
Battery schedule test table. It's index is hwUpsDeviceId.
Indexes
Column Syntax OID
Scheduled shallow discharge test enabled or disabled. Enumeration value.
The value 1 indicates that the test is disabled.
The value 2 indicates that the test is enabled.
Enumerationr/w
Enumerated Values:
1disable
2enalbe
.1.3.6.1.4.1.2011.6.174.1.103.101.1.1
Scheduled shallow discharge test time. Enumeration value.
Value 1 indicates 00:00 to 06:00.
Value 2 indicates 06:00 to 12:00.
Value 3 indicates 12:00 to 18:00.
Value 4 indicates 18:00 to 00:00.
Enumerationr/w
Enumerated Values:
1from0to6
2from6to12
3from12to18
4from18to24
.1.3.6.1.4.1.2011.6.174.1.103.101.1.2
Scheduled shallow discharge test interval. An integer ranging from 30 to 90. The unit is days.
DayUnsigned32r/w
Constraints:
range: 30-90
.1.3.6.1.4.1.2011.6.174.1.103.101.1.3
Shallow discharge test discharge ratio. An integer ranging from 10 to 50. .
Unsigned32r/w
Constraints:
range: 10-50
.1.3.6.1.4.1.2011.6.174.1.103.101.1.4
Maximum battery discharge time. An integer ranging from 160 to 195. The value is accurate to one decimal place on the NetEco. The unit is V/Cell.
Unsigned32r/w
Constraints:
range: 160-195
.1.3.6.1.4.1.2011.6.174.1.103.101.1.5
If you set the value to shallowDsgTest(4), you can perform a shallow discharge test; if you set the value to verifyDsgTest(5), you can perform a capacity test; if you set the value to stopTest(2), you can stop the test.…
Enumeration
Enumerated Values:
1noTestInit
2stopTest
3scheduleTest
4shallowDsgTest
5verufyDsgTest
.1.3.6.1.4.1.2011.6.174.1.103.101.1.6
RowStatus of UPS Battery control table.
RowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.174.1.103.101.1.100
.1.3.6.1.4.1.2011.6.174.1.107.1 · 1 row entry · 13 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwUpsModuleTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-UPS-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-UPS-MIB::hwUpsModuleTable'
Description.
hwUpsModuleEntry row .1.3.6.1.4.1.2011.6.174.1.107.1.1
Description.
Column Syntax OID
Ups Rack Id.Range from 1 to 6.This node is referenced as an index node
by hwUpsModuleTable.
Unsigned32
Constraints:
range: 1-6
.1.3.6.1.4.1.2011.6.174.1.107.1.1.1
Ups Power Module Id.Range from 1 to 20.This node is referenced as an index node
by hwUpsModuleTable.
Unsigned32
Constraints:
range: 1-20
.1.3.6.1.4.1.2011.6.174.1.107.1.1.2
Inv C Cap Life.Value range: 0 to 10000, Unit: Y, and the value is accurate to one decimal place (.1).
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.107.1.1.3
Inv A Current.Value range: 0 to 10000.The value is accurate to one decimal place (.1).The unit is A.
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.107.1.1.4
Inv B Current.Value range: 0 to 10000.The value is accurate to one decimal place (.1).The unit is A.
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.107.1.1.5
Inv C Current.Value range: 0 to 10000.The value is accurate to one decimal place (.1).The unit is A.
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.107.1.1.6
Module A Uneven Flow.Value range: 0 to 10000,and the value is accurate to one decimal place (.1).
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.107.1.1.7
Module B Uneven Flow.Value range: 0 to 10000,and the value is accurate to one decimal place (.1).
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.107.1.1.8
Module C Uneven Flow.Value range: 0 to 10000,and the value is accurate to one decimal place (.1).
Unsigned32
Constraints:
range: 0-1000
.1.3.6.1.4.1.2011.6.174.1.107.1.1.9
Inv Power Stat.Enumeration type.
Value 0 indicates no power supply.
Value 1 indicates bypass mode.
Value 2 indicates normal mode.
Enumeration
Enumerated Values:
1noOutput
2bypass
3normal
.1.3.6.1.4.1.2011.6.174.1.107.1.1.10
Module uneven current value tag.range 0 to 1,0 indicates invalid,1 indicates valid.
Unsigned32
Constraints:
range: 0-1
.1.3.6.1.4.1.2011.6.174.1.107.1.1.11
Module Sleep State.Range 0 to 1,0 indicates not sleep,1 indicates sleep.
Unsigned32
Constraints:
range: 0-1
.1.3.6.1.4.1.2011.6.174.1.107.1.1.12
RowStatus of UPS module information table.
RowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.174.1.107.1.1.100
.1.3.6.1.4.1.2011.6.174.1.108.1 · 1 row entry · 13 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwUpsRackUnevenCurTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-UPS-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-UPS-MIB::hwUpsRackUnevenCurTable'
hwUpsRackUnevenCurEntry row .1.3.6.1.4.1.2011.6.174.1.108.1.1
Column Syntax OID
Ups Rack Id.Range from 1 to 6.This node is referenced as an index node
by hwUpsRackUnevenCurTable
Unsigned32
Constraints:
range: 1-6
.1.3.6.1.4.1.2011.6.174.1.108.1.1.1
System grant.An integer ranging from 0 to 10000.
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.108.1.1.2
Device power supply mode. Enumeration type.
Value 1 indicates no power supply.
Value 2 indicates bypass mode.
Value 3 indicates normal mode.
Value 4 indicates battery mode.
Value 5 indicates combined mode.
Value 6 indic…
Enumeration
Enumerated Values:
1noOutput
2bypass
3normal
4battery
5sourceShare
6normalECO
7batteryECO
.1.3.6.1.4.1.2011.6.174.1.108.1.1.3
Rack PowerOn Module Num.Range from 0 to 20.
Unsigned32
Constraints:
range: 0-20
.1.3.6.1.4.1.2011.6.174.1.108.1.1.4
Rack Sleep Module Num.Range from 0 to 20.
Unsigned32
Constraints:
range: 0-20
.1.3.6.1.4.1.2011.6.174.1.108.1.1.5
Rack phase A output current. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is A.
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.108.1.1.6
Rack phase B output current. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is A.
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.108.1.1.7
Rack phase C output current. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is A.
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.108.1.1.8
Rack phase A uneven current. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco.
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.108.1.1.9
Rack phase B uneven current. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco.
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.108.1.1.10
Rack phase C uneven current. The value ranges from 0 to 10000.
The value is accurate to one decimal place on the NetEco.
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.108.1.1.11
Rack uneven current value tag.range 0 to 1,0 indicates invalid,1 indicates valid.
Unsigned32
Constraints:
range: 0-1
.1.3.6.1.4.1.2011.6.174.1.108.1.1.12
RowStatus of UPS Rack Uneven Current table.
RowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.174.1.108.1.1.100
.1.3.6.1.4.1.2011.6.174.1.110.4 · 1 row entry · 7 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwUpsBatteryGroupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-UPS-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-UPS-MIB::hwUpsBatteryGroupTable'
UPS battery group table. It's index is hwUpsBatteryGroupNo.
hwUpsBatteryGroupEntry row .1.3.6.1.4.1.2011.6.174.1.110.4.1
UPS battery group table. It's index is hwUpsBatteryGroupNo.
Column Syntax OID
No of battery group,ranging from 1 to 4.This node is referenced as an index node
by hwUpsBatteryGroupTable.
Unsigned32
Constraints:
range: 1-4
.1.3.6.1.4.1.2011.6.174.1.110.4.1.1
The Voltage of battery group,ranging from 0 to 10000.
The value is accurate to one decimal place on the NetEco. The unit is V.
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.174.1.110.4.1.2
The Current of battery group,ranging from -30000 to 30000.
The value is accurate to one decimal place on the NetEco. The unit is A.
Integer32
Constraints:
range: -30000-30000
.1.3.6.1.4.1.2011.6.174.1.110.4.1.3
The SOC of battery group,ranging from 0 to 100.The unit is %.
Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.174.1.110.4.1.4
The Backup Time of battery group,ranging from 0 to 999.The unit is min.
Unsigned32
Constraints:
range: 0-999
.1.3.6.1.4.1.2011.6.174.1.110.4.1.5
The SOH of battery group. Enumeration type.
Value 0 indicates good.
Value 1 indicates requiring maintenance.
Value 2 indicates need replace batt.
Enumeration
Enumerated Values:
1good
2requiringMaintenance
3needReplaceBatt
.1.3.6.1.4.1.2011.6.174.1.110.4.1.6
Row status of hwUpsBatteryGroupTable.
RowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.174.1.110.4.1.100
.1.3.6.1.4.1.2011.6.174.1.110.5 · 1 row entry · 4 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwUpsiBOXTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-UPS-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-UPS-MIB::hwUpsiBOXTable'
CIM table. It's index is hwUpsCIMNo.
hwUpsiBOXEntry row .1.3.6.1.4.1.2011.6.174.1.110.5.1
CIM table. It's index is hwUpsCIMNo.
Indexes
Column Syntax OID
No of iBOX,ranging from 1 to 4.This node is referenced as an index node by hwUpsiBOXTable.
Unsigned32
Constraints:
range: 1-4
.1.3.6.1.4.1.2011.6.174.1.110.5.1.1
The software version of iBOX,ranging from 0 to 4294967295.
Unsigned32
Constraints:
range: 0-4294967295
.1.3.6.1.4.1.2011.6.174.1.110.5.1.2
iBAT number of one iBOX,ranging from 0 to 300.
Unsigned32
Constraints:
range: 0-300
.1.3.6.1.4.1.2011.6.174.1.110.5.1.3
Row status of hwUpsiBOXTable.
RowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.174.1.110.5.1.100
.1.3.6.1.4.1.2011.6.174.1.110.6 · 1 row entry · 5 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwUpsBattGroupRelaiBOXTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-UPS-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-UPS-MIB::hwUpsBattGroupRelaiBOXTable'
UPS battery group related CIM Table. It's index is hwUpsBattGrpNo and hwUpsBattGroupRelaCIMNo.
hwUpsBattGroupRelaiBOXEntry row .1.3.6.1.4.1.2011.6.174.1.110.6.1
UPS battery group related CIM Table. It's index is hwUpsBattGrpNo and hwUpsBattGroupRelaCIMNo.
Indexes
Column Syntax OID
No of battery group,ranging from 1 to 4.This node is referenced as an index node
by hwUpsBattGrpRelaiBOXTable.
Unsigned32
Constraints:
range: 1-4
.1.3.6.1.4.1.2011.6.174.1.110.6.1.1
No of iBOX,ranging from 1 to 4.This node is referenced as an index node
by hwUpsBattGrpRelaiBOXTable.
Unsigned32
Constraints:
range: 1-4
.1.3.6.1.4.1.2011.6.174.1.110.6.1.2
Ups Battery Group related iBAT start no,ranging from 1 to 300.
Unsigned32
Constraints:
range: 1-300
.1.3.6.1.4.1.2011.6.174.1.110.6.1.3
Ups Battery Group related iBAT end no,ranging from 1 to 300.
Unsigned32
Constraints:
range: 1-300
.1.3.6.1.4.1.2011.6.174.1.110.6.1.4
Row status of hwUpsBattGroupRelaiBOXTable.
RowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.174.1.110.6.1.100
.1.3.6.1.4.1.2011.6.174.1.110.7 · 1 row entry · 11 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwUpsiBATTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-UPS-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-UPS-MIB::hwUpsiBATTable'
BIM table. It's index is hwUpsBIMCIMNo and hwUpsBIMNo.
hwUpsiBATEntry row .1.3.6.1.4.1.2011.6.174.1.110.7.1
BIM table. It's index is hwUpsBIMCIMNo and hwUpsBIMNo.
Indexes
Column Syntax OID
No of iBOX,ranging from 1 to 4.This node is referenced as an index node
by hwUpsBIMTable.
Unsigned32
Constraints:
range: 1-4
.1.3.6.1.4.1.2011.6.174.1.110.7.1.1
No of iBAT,ranging from 1 to 300.
This node is referenced as an index node by hwUpsBIMTable.
Unsigned32
Constraints:
range: 1-300
.1.3.6.1.4.1.2011.6.174.1.110.7.1.2
Ups iBAT Temperature.The value ranges from -200 to 800.
The value is accurate to one decimal place on the NetEco. The unit is ??.
Integer32
Constraints:
range: -200-800
.1.3.6.1.4.1.2011.6.174.1.110.7.1.3
Ups iBAT Volt.The value ranges from 0 to 300.
The value is accurate to one decimal place on the NetEco. The unit is V.
Unsigned32
Constraints:
range: 0-300
.1.3.6.1.4.1.2011.6.174.1.110.7.1.4
Ups iBAT Resistance.The value ranges from 0 to 3000.
The value is accurate to one decimal place on the NetEco. The unit is m??.
Unsigned32
Constraints:
range: 0-3000
.1.3.6.1.4.1.2011.6.174.1.110.7.1.5
Ups iBAT Current.The value ranges from -30000 to 30000.
The value is accurate to one decimal place on the NetEco. The unit is A.
Integer32
Constraints:
range: -30000-30000
.1.3.6.1.4.1.2011.6.174.1.110.7.1.6
The SOC of iBAT,ranging from 0 to 100.The unit is %.
Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.174.1.110.7.1.7
The SOH of iBAT. Enumeration type.
Value 0 indicates good.
Value 1 indicates requiring maintenance.
Value 2 indicates need replace batt.
Enumeration
Enumerated Values:
1good
2requiringMaintenance
3needReplaceBatt
.1.3.6.1.4.1.2011.6.174.1.110.7.1.8
Ups iBAT Volt.The value ranges from 0 to 30000.
The value is accurate to two decimal place on the NetEco. The unit is V.
Unsigned32
Constraints:
range: 0-30000
.1.3.6.1.4.1.2011.6.174.1.110.7.1.9
Ups iBAT Resistance.The value ranges from 0 to 30000.
The value is accurate to two decimal place on the NetEco. The unit is m??.
Unsigned32
Constraints:
range: 0-30000
.1.3.6.1.4.1.2011.6.174.1.110.7.1.10
Row status of hwUpsiBATTable.
RowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.174.1.110.7.1.100