GUDEADS-PDU8311-MIB

Download MIB Monitored by Observium
Observium actively monitors this MIB Visit Observium
Observium uses this MIB in discovery or polling workflows on applicable devices.
Counters Sensors
Source file
GUDEADS-PDU8311-MIB
Last revised
Identity
gudeads
Base OID
1.3.6.1.4.1.28507
Objects
2 scalars · 33 columns
Tables
3 tables
Net-SNMP examples using the gude MIB directory

These commands use the standard Observium installation path and load the selected MIB variant before the RFC and Net-SNMP directories.

Translate the module identity
/usr/bin/snmptranslate -Pud -Ir -On -m 'GUDEADS-PDU8311-MIB' -M '/opt/observium/mibs/gude:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'GUDEADS-PDU8311-MIB::gudeads'
Walk the MIB subtree
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'GUDEADS-PDU8311-MIB' -M '/opt/observium/mibs/gude:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'GUDEADS-PDU8311-MIB::gudeads'
Command help
Imported Objects
SNMPv2-CONF NOTIFICATION-GROUP (no object page) OBJECT-GROUP (no object page)
SNMPv2-SMI enterprises Integer32 MODULE-IDENTITY (no object page) NOTIFICATION-TYPE (no object page) OBJECT-TYPE (no object page) Unsigned32

Objects

OBS ✓11

Scalarspdu8311SNMPaccess

pdu8311CommonConfig · .1.3.6.1.4.1.28507.62.1.1.1
Object Syntax OID
pdu8311TrapCtrlInteger32r/w.1.3.6.1.4.1.28507.62.1.1.1.1
.1.3.6.1.4.1.28507.62.1.1.1.2 · 2 columns
OID Tree

list of all Trap receiver

pdu8311TrapIPEntry .1.3.6.1.4.1.28507.62.1.1.1.2.1
Column Syntax OID
pdu8311TrapIPIndexInteger32.1.3.6.1.4.1.28507.62.1.1.1.2.1.1
pdu8311TrapAddrOctetStringr/w.1.3.6.1.4.1.28507.62.1.1.1.2.1.2

Scalarspdu8311PowerChan

pdu8311IntSensors · .1.3.6.1.4.1.28507.62.1.5.1
Object Syntax OID
pdu8311ActivePowerChanUnsigned32.1.3.6.1.4.1.28507.62.1.5.1.1
.1.3.6.1.4.1.28507.62.1.5.1.2 · 24 columns
OID Tree

All available Channel Interfaces.

pdu8311PowerEntry .1.3.6.1.4.1.28507.62.1.5.1.2.1
Column Syntax OID
pdu8311PowerIndexInteger32.1.3.6.1.4.1.28507.62.1.5.1.2.1.1
pdu8311ChanStatusInteger32.1.3.6.1.4.1.28507.62.1.5.1.2.1.2
pdu8311AbsEnergyActiveOBS ✓WhSNMPv2-SMIUnsigned32.1.3.6.1.4.1.28507.62.1.5.1.2.1.3
pdu8311PowerActiveOBS ✓WSNMPv2-SMIInteger32.1.3.6.1.4.1.28507.62.1.5.1.2.1.4
pdu8311CurrentOBS ✓mASNMPv2-SMIUnsigned32.1.3.6.1.4.1.28507.62.1.5.1.2.1.5
pdu8311VoltageOBS ✓VSNMPv2-SMIUnsigned32.1.3.6.1.4.1.28507.62.1.5.1.2.1.6
pdu8311FrequencyOBS ✓0.01 hzSNMPv2-SMIUnsigned32.1.3.6.1.4.1.28507.62.1.5.1.2.1.7
pdu8311PowerFactorOBS ✓0.001SNMPv2-SMIInteger32.1.3.6.1.4.1.28507.62.1.5.1.2.1.8
pdu8311Pangle0.1 degreeSNMPv2-SMIInteger32.1.3.6.1.4.1.28507.62.1.5.1.2.1.9
pdu8311PowerApparentOBS ✓VASNMPv2-SMIInteger32.1.3.6.1.4.1.28507.62.1.5.1.2.1.10
pdu8311PowerReactiveOBS ✓VARSNMPv2-SMIInteger32.1.3.6.1.4.1.28507.62.1.5.1.2.1.11
pdu8311AbsEnergyReactiveVARhSNMPv2-SMIUnsigned32.1.3.6.1.4.1.28507.62.1.5.1.2.1.12
pdu8311AbsEnergyActiveResettableWhSNMPv2-SMIUnsigned32r/w.1.3.6.1.4.1.28507.62.1.5.1.2.1.13
pdu8311AbsEnergyReactiveResettableVARhSNMPv2-SMIUnsigned32.1.3.6.1.4.1.28507.62.1.5.1.2.1.14
pdu8311ResetTimesSNMPv2-SMIUnsigned32.1.3.6.1.4.1.28507.62.1.5.1.2.1.15
pdu8311ForwEnergyActiveWhSNMPv2-SMIUnsigned32.1.3.6.1.4.1.28507.62.1.5.1.2.1.16
pdu8311ForwEnergyReactiveVARhSNMPv2-SMIUnsigned32.1.3.6.1.4.1.28507.62.1.5.1.2.1.17
pdu8311ForwEnergyActiveResettableWhSNMPv2-SMIUnsigned32.1.3.6.1.4.1.28507.62.1.5.1.2.1.18
pdu8311ForwEnergyReactiveResettableVARhSNMPv2-SMIUnsigned32.1.3.6.1.4.1.28507.62.1.5.1.2.1.19
pdu8311RevEnergyActiveWhSNMPv2-SMIUnsigned32.1.3.6.1.4.1.28507.62.1.5.1.2.1.20
pdu8311RevEnergyReactiveVARhSNMPv2-SMIUnsigned32.1.3.6.1.4.1.28507.62.1.5.1.2.1.21
pdu8311RevEnergyActiveResettableWhSNMPv2-SMIUnsigned32.1.3.6.1.4.1.28507.62.1.5.1.2.1.22
pdu8311RevEnergyReactiveResettableVARhSNMPv2-SMIUnsigned32.1.3.6.1.4.1.28507.62.1.5.1.2.1.23
pdu8311ResidualCurrentOBS ✓mASNMPv2-SMIUnsigned32.1.3.6.1.4.1.28507.62.1.5.1.2.1.24
.1.3.6.1.4.1.28507.62.1.6.1 · 7 columns
OID Tree
pdu8311SensorEntry .1.3.6.1.4.1.28507.62.1.6.1.1
Column Syntax OID
pdu8311SensorIndexInteger32.1.3.6.1.4.1.28507.62.1.6.1.1.1
pdu8311TempSensorOBS ✓0.1 degree CelsiusSNMPv2-SMIInteger32.1.3.6.1.4.1.28507.62.1.6.1.1.2
pdu8311HygroSensorOBS ✓0.1 percent humiditySNMPv2-SMIInteger32.1.3.6.1.4.1.28507.62.1.6.1.1.3
pdu8311InputSensorEnumeration.1.3.6.1.4.1.28507.62.1.6.1.1.4
pdu8311AirPressure1 hPA (hectopascal) ~ 1 milibarSNMPv2-SMIInteger32.1.3.6.1.4.1.28507.62.1.6.1.1.5
pdu8311DewPoint0.1 degree CelsiusSNMPv2-SMIInteger32.1.3.6.1.4.1.28507.62.1.6.1.1.6
pdu8311DewPointDiff0.1 degree CelsiusSNMPv2-SMIInteger32.1.3.6.1.4.1.28507.62.1.6.1.1.7

Notifications / Traps (6)

Conformance Groups (2)

pdu8311BasicGroup .1.3.6.1.4.1.28507.62.2.1.1 Members (35)
pdu8311NotificationGroup .1.3.6.1.4.1.28507.62.2.1.2 Notifications (6)
Dependencies (2) 2 direct Show tree and compile order Hide dependency details

Each imported module is resolved in the importing module's source directory first, then through the normal default-variant rules.

Dependency tree
Dependency-first compile order
  1. SNMPv2-SMIrfc
  2. SNMPv2-CONFrfc