GUDEADS-ETS8801-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
5
Rows
5
Columns
43
.1.3.6.1.4.1.28507.41.1.1.1.2 · 1 row entry · 2 columns
Uses the gude variant from /opt/observium/mibs/gude.
Command help
Walk ets8801TrapIPTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'GUDEADS-ETS8801-MIB' -M '/opt/observium/mibs/gude:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'GUDEADS-ETS8801-MIB::ets8801TrapIPTable'
list of all Trap receiver
ets8801TrapIPEntry row .1.3.6.1.4.1.28507.41.1.1.1.2.1
an entry containing management
informations regarding the list of trap
receivers
Column Syntax OID
A unique value, greater than zero, for each receiver slot.
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.28507.41.1.1.1.2.1.1
DNS name or IP address specifying one Trap receiver slot.
A port can optionally be specified: 'name:port' An empty
string disables this slot.
OctetStringr/w
Constraints:
range: 0-99
.1.3.6.1.4.1.28507.41.1.1.1.2.1.2
.1.3.6.1.4.1.28507.41.1.5.1.2 · 1 row entry · 25 columns
Uses the gude variant from /opt/observium/mibs/gude.
Command help
Walk ets8801PowerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'GUDEADS-ETS8801-MIB' -M '/opt/observium/mibs/gude:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'GUDEADS-ETS8801-MIB::ets8801PowerTable'
All available Channel Interfaces.
ets8801PowerEntry row .1.3.6.1.4.1.28507.41.1.5.1.2.1
An entry containing management information
applicable to a particular Power Channel.
Column Syntax OID
Index of Power Channel entries
Integer32
Constraints:
range: 1-1
.1.3.6.1.4.1.28507.41.1.5.1.2.1.1
0 = data not active, 1 = data valid
Integer32
Constraints:
range: 0-1
.1.3.6.1.4.1.28507.41.1.5.1.2.1.2
Absolute Active Energy counter.
WhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.41.1.5.1.2.1.3
Active Power
WSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.28507.41.1.5.1.2.1.4
Actual Curent on Power Channel.
mASNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.41.1.5.1.2.1.5
Actual Voltage on Power Channel
VSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.41.1.5.1.2.1.6
Frequency of Power Channel
0.01 hzSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.41.1.5.1.2.1.7
Power Factor of Channel between
-1.0 and 1.00
0.001SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.28507.41.1.5.1.2.1.8
Phase Angle between Voltage
and L Line Current between
-180.0 and 180.0
0.1 degreeSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.28507.41.1.5.1.2.1.9
L Line Mean Apparent Power
VASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.28507.41.1.5.1.2.1.10
L Line Mean Reactive Power
VARSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.28507.41.1.5.1.2.1.11
Absolute Reactive Energy counter.
VARhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.41.1.5.1.2.1.12
Resettable Absolute Active Energy counter.
Writing '0' resets all resettable counter.
WhSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.41.1.5.1.2.1.13
Resettable Absolute Reactive Energy counter.
VARhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.41.1.5.1.2.1.14
Time in seconds since last Energy
Counter reset.
sSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.41.1.5.1.2.1.15
Forward Active Energy counter.
WhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.41.1.5.1.2.1.16
Forward Reactive Energy counter.
VARhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.41.1.5.1.2.1.17
Resettable Forward Active Energy counter.
WhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.41.1.5.1.2.1.18
Resettable Forward Reactive Energy counter.
VARhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.41.1.5.1.2.1.19
Reverse Active Energy counter.
WhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.41.1.5.1.2.1.20
Reverse Reactive Energy counter.
VARhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.41.1.5.1.2.1.21
Resettable Reverse Active Energy counter.
WhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.41.1.5.1.2.1.22
Resettable Reverse Reactive Energy counter.
VARhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.41.1.5.1.2.1.23
Actual Residual Current on Power Channel.
According Typ A IEC 60755. Only visible on
models that support this feature.
0.1 mASNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.41.1.5.1.2.1.24
A textual string containing name of a
Line Sensor
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.28507.41.1.5.1.2.1.100
.1.3.6.1.4.1.28507.41.1.5.2 · 1 row entry · 2 columns
Uses the gude variant from /opt/observium/mibs/gude.
Command help
Walk ets8801FuseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'GUDEADS-ETS8801-MIB' -M '/opt/observium/mibs/gude:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'GUDEADS-ETS8801-MIB::ets8801FuseTable'
C13 Output Block Fuse Table
ets8801FuseEntry row .1.3.6.1.4.1.28507.41.1.5.2.1
Column Syntax OID
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.28507.41.1.5.2.1.1
shows the status of the
C13 Output Block Fuse
Enumeration
Enumerated Values:
0failure
1ok
2unknown
.1.3.6.1.4.1.28507.41.1.5.2.1.2
.1.3.6.1.4.1.28507.41.1.6.1 · 1 row entry · 8 columns
Uses the gude variant from /opt/observium/mibs/gude.
Command help
Walk ets8801SensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'GUDEADS-ETS8801-MIB' -M '/opt/observium/mibs/gude:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'GUDEADS-ETS8801-MIB::ets8801SensorTable'
ets8801SensorEntry row .1.3.6.1.4.1.28507.41.1.6.1.1
Column Syntax OID
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.28507.41.1.6.1.1.1
actual temperature
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.28507.41.1.6.1.1.2
actual humidity
0.1 percent humiditySNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.28507.41.1.6.1.1.3
logical state of input sensor
Enumeration
Enumerated Values:
0off
1on
.1.3.6.1.4.1.28507.41.1.6.1.1.4
actual air pressure
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.28507.41.1.6.1.1.5
dew point for actual temperature and humidity
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.28507.41.1.6.1.1.6
difference between dew point and actual
temperature (Temp - DewPoint)
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.28507.41.1.6.1.1.7
A textual string containing name of a
external Sensor
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.28507.41.1.6.1.1.32
.1.3.6.1.4.1.28507.41.1.6.2.2 · 1 row entry · 6 columns
Uses the gude variant from /opt/observium/mibs/gude.
Command help
Walk ets8801ExtInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'GUDEADS-ETS8801-MIB' -M '/opt/observium/mibs/gude:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'GUDEADS-ETS8801-MIB::ets8801ExtInputTable'
ets8801ExtInputEntry row .1.3.6.1.4.1.28507.41.1.6.2.2.1
Column Syntax OID
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.41.1.6.2.2.1.1
Input state of device
Enumeration
Enumerated Values:
0lo
1hi
.1.3.6.1.4.1.28507.41.1.6.2.2.1.2
Number of times the Input has changed its state.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.41.1.6.2.2.1.3
A textual string containing name of
the Input
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.28507.41.1.6.2.2.1.32
Number of external Sensor Port when value greater zero, else device built-in Input.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.28507.41.1.6.2.2.1.33
Either index of device built-in Input, or index of Input in external sensor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.28507.41.1.6.2.2.1.34