GEIST-V4-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
9
Rows
9
Columns
80
.1.3.6.1.4.1.21239.5.1.2 · 1 row entry · 12 columns
Internal sensors for units
internalEntry entry .1.3.6.1.4.1.21239.5.1.2.1
Entry in the internalTable table: each entry contains an index and other sensor details
Indexes
internalIndex
Column Syntax OID
internalIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.1.2.1.1
internalSerial
Serial Number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.2.1.2
internalName
Friendly Name
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.2.1.3
internalAvail
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.2.1.4
internalTemp
Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
0.1 DegreesInteger32
Constraints:
range: -40-200
.1.3.6.1.4.1.21239.5.1.2.1.5
internalHumidity
Humidity reading
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.1.2.1.6
internalDewPoint
Current reading for Dew-point in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
0.1 DegreesInteger32
Constraints:
range: -40-200
.1.3.6.1.4.1.21239.5.1.2.1.7
internalIO1
Current reading for Analog Input 1
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.1.2.1.8
internalIO2
Current reading for Analog Input 2
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.1.2.1.9
internalIO3
Current reading for Analog Input 3
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.1.2.1.10
internalIO4
Current reading for Analog Input 4
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.1.2.1.11
internalRelayState
Is the relay on?
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.2.1.12
.1.3.6.1.4.1.21239.5.1.4 · 1 row entry · 5 columns
Remote Temperature Sensor
tempSensorEntry entry .1.3.6.1.4.1.21239.5.1.4.1
Entry in the tempSensorTable table: each entry contains an index and other sensor details
Indexes
tempSensorIndex
Column Syntax OID
tempSensorIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.1.4.1.1
tempSensorSerial
Serial Number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.4.1.2
tempSensorName
Friendly Name
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.4.1.3
tempSensorAvail
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.4.1.4
tempSensorTemp
Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
0.1 DegreesInteger32
Constraints:
range: -40-200
.1.3.6.1.4.1.21239.5.1.4.1.5
.1.3.6.1.4.1.21239.5.1.5 · 1 row entry · 8 columns
Remote Airflow, Humidity, Temperature and Dewpoint Sensor
airFlowSensorEntry entry .1.3.6.1.4.1.21239.5.1.5.1
Entry in the airFlowSensorTable table: each entry contains an index and other sensor details
Indexes
airFlowSensorIndex
Column Syntax OID
airFlowSensorIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.1.5.1.1
airFlowSensorSerial
Serial Number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.5.1.2
airFlowSensorName
Friendly Name
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.5.1.3
airFlowSensorAvail
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.5.1.4
airFlowSensorTemp
Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
0.1 DegreesInteger32
Constraints:
range: -40-200
.1.3.6.1.4.1.21239.5.1.5.1.5
airFlowSensorFlow
AFHT3 Airflow reading
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.1.5.1.6
airFlowSensorHumidity
AFHT3 Humidity reading
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.1.5.1.7
airFlowSensorDewPoint
Current reading for Dew Point in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
0.1 DegreesInteger32
Constraints:
range: -40-200
.1.3.6.1.4.1.21239.5.1.5.1.8
.1.3.6.1.4.1.21239.5.1.6 · 1 row entry · 7 columns
Remote Dew Point sensor
dewPointSensorEntry entry .1.3.6.1.4.1.21239.5.1.6.1
Entry in the dewPointSensorTable table: each entry contains an index and other sensor details
Indexes
dewPointSensorIndex
Column Syntax OID
dewPointSensorIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.1.6.1.1
dewPointSensorSerial
Serial Number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.6.1.2
dewPointSensorName
Friendly Name
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.6.1.3
dewPointSensorAvail
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.6.1.4
dewPointSensorTemp
Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
0.1 DegreesInteger32
Constraints:
range: -40-200
.1.3.6.1.4.1.21239.5.1.6.1.5
dewPointSensorHumidity
Humidity reading
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.1.6.1.6
dewPointSensorDewPoint
Current reading for Dew-point in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
0.1 DegreesInteger32
Constraints:
range: -40-200
.1.3.6.1.4.1.21239.5.1.6.1.7
.1.3.6.1.4.1.21239.5.1.7 · 1 row entry · 7 columns
Remote CCAT sensor
ccatSensorEntry entry .1.3.6.1.4.1.21239.5.1.7.1
Entry in the ccatSensorTable table: each entry contains an index and other sensor details
Indexes
ccatSensorIndex
Column Syntax OID
ccatSensorIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.1.7.1.1
ccatSensorSerial
Serial Number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.7.1.2
ccatSensorName
Friendly Name
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.7.1.3
ccatSensorAvail
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.7.1.4
ccatSensorValue
CCAT sensor reading
Integer32
Constraints:
range: -100-5000
.1.3.6.1.4.1.21239.5.1.7.1.5
ccatSensorType
CCAT sensor type
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.7.1.6
ccatSensorDescription
CCAT sensor value description
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.7.1.7
.1.3.6.1.4.1.21239.5.1.8 · 1 row entry · 14 columns
Remote Temperature x 3, Humidity and Dewpoint Sensor
t3hdSensorEntry entry .1.3.6.1.4.1.21239.5.1.8.1
Entry in the t3hdSensorTable table: each entry contains an index and other sensor details
Indexes
t3hdSensorIndex
Column Syntax OID
t3hdSensorIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.1.8.1.1
t3hdSensorSerial
Serial Number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.8.1.2
t3hdSensorName
Friendly Name
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.8.1.3
t3hdSensorAvail
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.8.1.4
t3hdSensorIntName
T3HD Sensor Internal Friendly Name
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.8.1.5
t3hdSensorIntTemp
Current reading for Internal Temperature in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo
0.1 DegreesInteger32
Constraints:
range: -40-200
.1.3.6.1.4.1.21239.5.1.8.1.6
t3hdSensorIntHumidity
T3HD Sensor Internal Humidity
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.1.8.1.7
t3hdSensorIntDewPoint
Current reading for Internal DewPoint in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo
0.1 DegreesInteger32
Constraints:
range: -40-200
.1.3.6.1.4.1.21239.5.1.8.1.8
t3hdSensorExtAAvail
T3HD External A status: 0 = Unavailable, 1 = Available
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.8.1.9
t3hdSensorExtAName
T3HD External A Friendly Name
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.8.1.10
t3hdSensorExtATemp
Current reading for External Temperature A in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo
0.1 DegreesInteger32
Constraints:
range: -40-200
.1.3.6.1.4.1.21239.5.1.8.1.11
t3hdSensorExtBAvail
T3HD External B status: 0 = Unavailable, 1 = Available
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.8.1.12
t3hdSensorExtBName
T3HD External B Friendly Name
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.8.1.13
t3hdSensorExtBTemp
Current reading for External Temperature B in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo
0.1 DegreesInteger32
Constraints:
range: -40-200
.1.3.6.1.4.1.21239.5.1.8.1.14
.1.3.6.1.4.1.21239.5.1.9 · 1 row entry · 7 columns
Remote Temperature, Humidity and Dewpoint Sensor
thdSensorEntry entry .1.3.6.1.4.1.21239.5.1.9.1
Entry in the thdSensorTable table: each entry contains an index and other sensor details
Indexes
thdSensorIndex
Column Syntax OID
thdSensorIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.1.9.1.1
thdSensorSerial
Serial Number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.9.1.2
thdSensorName
Friendly Name
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.9.1.3
thdSensorAvail
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.9.1.4
thdSensorTemp
Current reading for Temperature in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo
0.1 DegreesInteger32
Constraints:
range: -40-200
.1.3.6.1.4.1.21239.5.1.9.1.5
thdSensorHumidity
THD Sensor Humidity
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.1.9.1.6
thdSensorDewPoint
Current reading for DewPoint in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo
0.1 DegreesInteger32
Constraints:
range: -40-200
.1.3.6.1.4.1.21239.5.1.9.1.7
.1.3.6.1.4.1.21239.5.1.10 · 1 row entry · 15 columns
Remote Power Manager Sensor
rpmSensorEntry entry .1.3.6.1.4.1.21239.5.1.10.1
Entry in the rpmSensorTable table: each entry contains an index and other sensor details
Indexes
rpmSensorIndex
Column Syntax OID
rpmSensorIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.1.10.1.1
rpmSensorSerial
Serial Number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.10.1.2
rpmSensorName
Friendly Name
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.10.1.3
rpmSensorAvail
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.10.1.4
rpmSensorEnergy
RPM Sensor Accumulated Energy
kWhSNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.10.1.5
rpmSensorVoltage
RPM Sensor Voltage
Volts (rms)SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.10.1.6
rpmSensorVoltageMax
RPM Sensor Voltage (Max)
Volts (rms)SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.10.1.7
rpmSensorVoltageMin
RPM Sensor Voltage (Min)
Volts (rms)SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.10.1.8
rpmSensorVoltagePeak
RPM Sensor Voltage (Peak)
VoltsSNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.10.1.9
rpmSensorCurrent
RPM Sensor Current reading in deciAmps
0.1 Amps (rms)SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.10.1.10
rpmSensorRealPower
RPM Sensor Real Power
WattsSNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.10.1.11
rpmSensorApparentPower
RPM Sensor Apparent Power
Volt-AmpsSNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.10.1.12
rpmSensorPowerFactor
RPM Sensor Power Factor
%SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.10.1.13
rpmSensorOutlet1
RPM Sensor Outlet 1 State: 0 = off, 1 = on
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.10.1.14
rpmSensorOutlet2
RPM Sensor Outlet 2 State: 0 = off, 1 = on
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.10.1.15
.1.3.6.1.4.1.21239.5.1.11 · 1 row entry · 5 columns
Analog Measurement Sensor (Voltage, Current, or Dry Contact)
a2DSensorEntry entry .1.3.6.1.4.1.21239.5.1.11.1
Entry in the a2dSensorTable table: each entry contains an index and other sensor details
Indexes
a2dSensorIndex
Column Syntax OID
a2dSensorIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.1.11.1.1
a2dSensorSerial
Serial Number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.11.1.2
a2dSensorName
Friendly Name
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.11.1.3
a2dSensorAvail
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.11.1.4
a2dSensorValue
Current analog measurement reading within either a user defined or preset range depending on device mode.
Integer32
Constraints:
range: -1000000-1000000
.1.3.6.1.4.1.21239.5.1.11.1.5