ELECTROLINE-DHT-BATTERIES-CONTROLLER-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
9
Rows
9
Columns
62
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2 · 1 row entry · 17 columns
Uses the electroline variant from /opt/observium/mibs/electroline.
Command help
Walk battManDeviceTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ELECTROLINE-DHT-BATTERIES-CONTROLLER-MIB' -M '/opt/observium/mibs/electroline:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ELECTROLINE-DHT-BATTERIES-CONTROLLER-MIB::battManDeviceTable'
Table containing information about the individual
battery manager being monitored.
battManDeviceEntry row .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1
List of information about each battery manager being monitored.
Column Syntax OID
Index into the battManDeviceTable.Address of this device on the RS-485 path
Integer32
Constraints:
range: 17-127
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.1
Version of the protocol implemented in the monitored equipment.
Integer32
Constraints:
range: 1-254
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.2
The content of this field is vendor specific. The intent is to provide
a text representation of the monitored device system software
version. Any printable ASCII characters can be included in this field.
NULL (0x00) c…
OctetString
Constraints:
range: 8-8
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.3
The content of this field is vendor specific. The intent is to provide
manufacturer and/or product specific ASCII text information.
OctetString
Constraints:
range: 32-32
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.4
The content of this field is vendor specific. The intent is to provide
a text representation of the battery manager vendor identity. Any
printable ASCII characters can be included in this field. NULL (0x00)
characters …
OctetString
Constraints:
range: 10-10
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.5
Current string voltage configuration.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.6
Current number of batteries.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.7
Current number of strings.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.8
Current number of batteries per string.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.9
Defines if the voltage measurement is supported
1 = No support.
2 = Field is supported in this installation.
Enumeration
Enumerated Values:
1none
2supported
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.10
Defines if the temperature measurement is supported
1 = No support.
2 = Field is supported in this installation.
Enumeration
Enumerated Values:
1none
2supported
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.11
Defines if the impedance measurement is supported
1 = No support.
2 = Field is supported in this installation.
Enumeration
Enumerated Values:
1none
2supported
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.12
Defines if the equlization percent measurement is supported
1 = No support.
2 = Field is supported in this installation.
Enumeration
Enumerated Values:
1none
2supported
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.13
Defines if the battery status monitoring is supported
1 = No support.
2 = Field is supported in this installation.
Enumeration
Enumerated Values:
1none
2supported
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.14
Defines if the battery manager modules diagnostics monitoring is supported
1 = No support.
2 = Field is supported in this installation.
Enumeration
Enumerated Values:
1none
2supported
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.15
Defines if the battery manager environment data is supported
1 = No support.
2 = The Environment Data table is supported in this installation.
Enumeration
Enumerated Values:
1none
2supported
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.16
Defines if the battery manager manualy triggered measurement is supported
1 = No support.
2 = The Manual Measurement table is supported in this installation.
Enumeration
Enumerated Values:
1none
2supported
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.17
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.3 · 1 row entry · 4 columns
Uses the electroline variant from /opt/observium/mibs/electroline.
Command help
Walk battManStringTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ELECTROLINE-DHT-BATTERIES-CONTROLLER-MIB' -M '/opt/observium/mibs/electroline:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ELECTROLINE-DHT-BATTERIES-CONTROLLER-MIB::battManStringTable'
Table containing strings data
battManStringEntry row .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.3.1
List of information about each string. Indexed by string number
Column Syntax OID
Index into the battManStringTable. Corresponds to battManDeviceAddress in battManDeviceTable
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.3.1.1
Index into the battManStringTable.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.3.1.2
number of batteries.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.3.1.3
Scaled representation of an individual string total voltage in 1/100 Volts

This item requires an entry in the properties MIB.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.3.1.4
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4 · 1 row entry · 12 columns
Uses the electroline variant from /opt/observium/mibs/electroline.
Command help
Walk battManBatteryTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ELECTROLINE-DHT-BATTERIES-CONTROLLER-MIB' -M '/opt/observium/mibs/electroline:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ELECTROLINE-DHT-BATTERIES-CONTROLLER-MIB::battManBatteryTable'
Table containing batteries data
battManBatteryEntry row .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1
List of information about each battery. Indexed by battery number
Column Syntax OID
Index into the battManBatteryTable. Corresponds to battManDeviceAddress in battManDeviceTable
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.1
Index into the battManBatteryTable.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.2
id of the string that this battery belongs to.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.3
battery module version.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.4
The content of this field is vendor specific. The intent is to provide
a text representation of the battery system hardware version. Any printable
ASCII characters can be included in this field. NULL (0x00) characters …
OctetString .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.5
The content of this field is vendor specific. The intent is to provide
a text representation of the battery system software version. Any printable
ASCII characters can be included in this field. NULL (0x00) characters …
OctetString .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.6
Scaled representation of an individual battery voltage in 1/100 Volts
with a range of 0 to 16.000 volts

This item requires an entry in the properties MIB.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.7
Scaled representation of temperature in degrees C
with a range of -40 to + 80 degrees C.

This item requires an entry in the properties MIB.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.8
Scaled representation of an individual battery impedance in 1/100 mOhm
with a range of 0 to 99.99 mOhm.

This item requires an entry in the properties MIB.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.9
Reports the battery equalization percent with a range of 0 to 100%.

This item requires an entry in the properties MIB.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.10
Reports the status of the battery

1. ok
2. alarm

This item requires an entry in the discrete properties MIB.
Enumeration
Enumerated Values:
1ok
2alarm
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.11
The DatasetID of the measurement done for this battery.
Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.12
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.5 · 1 row entry · 4 columns
Uses the electroline variant from /opt/observium/mibs/electroline.
Command help
Walk battManBatteryDiagTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ELECTROLINE-DHT-BATTERIES-CONTROLLER-MIB' -M '/opt/observium/mibs/electroline:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ELECTROLINE-DHT-BATTERIES-CONTROLLER-MIB::battManBatteryDiagTable'
Table containing battery diagnostic data
battManBatteryDiagEntry row .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.5.1
List of diagnostic information about each battery. Indexed by battery number
Column Syntax OID
Index into the battManBatteryDiagTable. Corresponds to battManDeviceAddress in battManDeviceTable
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.5.1.1
Index into the battManBatteryDiagTable.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.5.1.2
the data page number.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.5.1.3
The content of this field is vendor specific. The intent is to provide
a text representation of the particular information of the identified module.
when an invalid page number is requested, this field will be returned…
OctetString
Constraints:
range: 20-20
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.5.1.4
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.6 · 1 row entry · 4 columns
Uses the electroline variant from /opt/observium/mibs/electroline.
Command help
Walk battManControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ELECTROLINE-DHT-BATTERIES-CONTROLLER-MIB' -M '/opt/observium/mibs/electroline:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ELECTROLINE-DHT-BATTERIES-CONTROLLER-MIB::battManControlTable'
Table containing battery managers control settings.
battManControlEntry row .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.6.1
List of controls about each battery manager. Indexed by battManControlDeviceAddress
Column Syntax OID
Index into the battManControlStatusTable. Corresponds to battManDeviceAddress in battManDeviceTable
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.6.1.1
Represents the equalization status.

1 means equalization activated
2 means equalization deactivated
Enumerationr/w
Enumerated Values:
1activated
2deactivated
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.6.1.2
Represents the period (in hours) used to take automated measurements
The value 0 deactivates the automated measurements
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.6.1.3
Restart the sensors. Reading the object returns false(2), and has no effect on the unit.
Enumerationr/w
Enumerated Values:
1true
2false
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.6.1.4
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.7 · 1 row entry · 2 columns
Uses the electroline variant from /opt/observium/mibs/electroline.
Command help
Walk battManStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ELECTROLINE-DHT-BATTERIES-CONTROLLER-MIB' -M '/opt/observium/mibs/electroline:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ELECTROLINE-DHT-BATTERIES-CONTROLLER-MIB::battManStatusTable'
Table containing battery managers status data.
battManStatusEntry row .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.7.1
List of status information about each battery manager. Indexed by battManEnvDeviceAddress
Column Syntax OID
Index into the battManStatusTable. Corresponds to battManDeviceAddress in battManDeviceTable
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.7.1.1
Indicates the remaining time (in seconds) before next automated measurement.
If the automated measurement is deactivated, then the return value is always 0.
Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.7.1.2
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.8 · 1 row entry · 4 columns
Uses the electroline variant from /opt/observium/mibs/electroline.
Command help
Walk battManEnvStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ELECTROLINE-DHT-BATTERIES-CONTROLLER-MIB' -M '/opt/observium/mibs/electroline:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ELECTROLINE-DHT-BATTERIES-CONTROLLER-MIB::battManEnvStatusTable'
Table containing battery manager's Environmental Status data.
battManEnvStatusEntry row .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.8.1
List of Environmental Status information about each battery manager. Indexed by battManEnvDeviceAddress
Column Syntax OID
Index into the battManEnvStatusTable. Corresponds to battManDeviceAddress in battManDeviceTable
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.8.1.1
Scaled representation of battery manager temperature in degrees C

This item requires an entry in the properties MIB.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.8.1.2
Scaled representation of battery manager humidity percent.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.8.1.3
bit map that indicates the state of the dry contacts. bit set means the corresponding dry contact is closed
Bits Dry Contact
0 dry contact1
1 dry contact2
2 dry contact3
3 dry contact4
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.8.1.4
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.9 · 1 row entry · 6 columns
Uses the electroline variant from /opt/observium/mibs/electroline.
Command help
Walk battManManualMeasTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ELECTROLINE-DHT-BATTERIES-CONTROLLER-MIB' -M '/opt/observium/mibs/electroline:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ELECTROLINE-DHT-BATTERIES-CONTROLLER-MIB::battManManualMeasTable'
Table containing battery manager's Manual Measurement trigger command and response data.
battManManualMeasEntry row .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.9.1
List of ManualMeasurement Status information about each battery manager. Indexed by battManEnvDeviceAddress
Column Syntax OID
Index into the battManManualMeasStatusTable. Corresponds to battManDeviceAddress in battManDeviceTable
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.9.1.1
Short phrase describing the manual measurement status.
OctetString
Constraints:
range: 80-80
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.9.1.2
0: Taking measurement now.
1: Equalizer on, the measurement will be ready in 5 minutes.
2: NACK, cannot take measurement now.
3: Waiting for controller information
Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.9.1.3
Dataset ID of this measurement (When Status code 0 and 1 was returned by the trigger command). Reset to negative value when not applicable.
Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.9.1.4
(When Status code 2 was returned by the trigger command): remaining time in seconds before a measurement can be done. Reset to negative value when not applicable.
Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.9.1.5
Measurement manual trigger command. Then check the battManManualMeasTimeToMeasurement. When read always returns false(2).
Enumerationr/w
Enumerated Values:
1true
2false
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.9.1.6
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11 · 1 row entry · 9 columns
Uses the electroline variant from /opt/observium/mibs/electroline.
Command help
Walk battManBatteryLogTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ELECTROLINE-DHT-BATTERIES-CONTROLLER-MIB' -M '/opt/observium/mibs/electroline:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ELECTROLINE-DHT-BATTERIES-CONTROLLER-MIB::battManBatteryLogTable'
Table containing batteries data
battManBatteryLogEntry row .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1
List of information about each battery. Indexed by battery number
Column Syntax OID
Index into the battManBatteryLog. Corresponds to battManDeviceAddress in battManDeviceTable
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.1
The DatasetID of the measurement done for this battery.
Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.2
Index into the battManBatteryLog.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.3
id of the string that this battery belongs to.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.4
Scaled representation of an individual battery voltage in 1/100 Volts
with a range of 0 to 16.000 volts

This item requires an entry in the properties MIB.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.5
Scaled representation of temperature in degrees C
with a range of -40 to + 80 degrees C.

This item requires an entry in the properties MIB.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.6
Scaled representation of an individual battery impedance in 1/100 mOhm
with a range of 0 to 99.99 mOhm.

This item requires an entry in the properties MIB.
HundredthmOhm .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.7
Scaled representation of an individual battery cell conductance in in 1/100 of Siemens
with a range of 6000 to 60000 Siemens (tbd)

This item requires an entry in the properties MIB.
HundredthkS .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.8
Date and time when the measurement was taken.

This item requires an entry in the discrete properties MIB.
SNMPv2-TCDateAndTime
Type Constraints:
range: 8
range: 11
Description:
A date-time specification.

field octets contents range
----- ------ -------- -----
1 1-2 year* 0..65536
2 3 month …
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.9