EATON-EPDU-MA-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
3
Rows
3
Columns
33

outletTable

table
.1.3.6.1.4.1.534.6.6.6.1.2.2 · 1 row entry · 11 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk outletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MA-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MA-MIB::outletTable'
A list of outlet entries. The number of
entries is given by the value of outletCount.
outletEntry row .1.3.6.1.4.1.534.6.6.6.1.2.2.1
An outlet entry containing objects at the
for a particular outlet.
Indexes
Column Syntax OID
A unique value for each outlet. Its value
ranges between 1 and the value of outletCount.
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.534.6.6.6.1.2.2.1.1
A textual string containing information
about the outlet.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.534.6.6.6.1.2.2.1.2
A value for each outlet which describes the
operational state of the outlet. It is also
used to set the operational state of the outlet
Enumerationr/w
Enumerated Values:
-1error
0off
1on
2cycling
.1.3.6.1.4.1.534.6.6.6.1.2.2.1.3
A unique value for the current sensor
attached to the outlet. This value is
reported in milliamps (1/1000th of an amp)
MilliAmps .1.3.6.1.4.1.534.6.6.6.1.2.2.1.4
A unique value for the max. current sensor
attached to the outlet. This value is
reported in milliamps (1/1000th of an amp)
MilliAmps .1.3.6.1.4.1.534.6.6.6.1.2.2.1.5
A unique value for the voltage sensor
attached to the outlet.This value is
reported in millivolts (1/1000th of a volt)
MilliVolts .1.3.6.1.4.1.534.6.6.6.1.2.2.1.6
A unique value for the active power sensor
attached to the outlet. This value is
reported in Watts.
Watts .1.3.6.1.4.1.534.6.6.6.1.2.2.1.7
A unique value for the apparent power sensor
attached to the outlet. This value is
reported in Volt-Amps
VoltAmps .1.3.6.1.4.1.534.6.6.6.1.2.2.1.8
A unique value for the power factor
of the outlet. The reading represents a
percentage in the range of 0% to 100%.
PowerFactorPercentage
Type Constraints:
range: 0..100
.1.3.6.1.4.1.534.6.6.6.1.2.2.1.9
The value of the upper warning (non-critical)
current threshold for the outlet. This value is
reported in milliamps (1/1000th of an amp)
MilliAmpsr/w .1.3.6.1.4.1.534.6.6.6.1.2.2.1.21
The value of the upper critical current
threshold for the outlet. This value is
reported in milliamps (1/1000th of an amp)
MilliAmpsr/w .1.3.6.1.4.1.534.6.6.6.1.2.2.1.23
.1.3.6.1.4.1.534.6.6.6.2.2 · 1 row entry · 11 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk tempSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MA-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MA-MIB::tempSensorTable'
A list of temperature sensor entries. The number of
entries is given by the value of tempSensorCount.
tempSensorEntry row .1.3.6.1.4.1.534.6.6.6.2.2.1
An entry containing sensor reading and threshold
settings for a particular temperature sensor.
Indexes
Column Syntax OID
A unique value for each temperature sensor. Its value
ranges between 1 and tempSensorCount.
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.534.6.6.6.2.2.1.1
A settable human-readable label for the external temperature
sensor. One possible use for this label is to convey sensor
location.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.534.6.6.6.2.2.1.2
The value of the external temperature sensor reported
in degrees celsius.
DegreesCelsius .1.3.6.1.4.1.534.6.6.6.2.2.1.3
The value of the lower warning (non-critical) threshold.
DegreesCelsiusr/w .1.3.6.1.4.1.534.6.6.6.2.2.1.4
The value of the upper warning (non-critical) threshold.
DegreesCelsiusr/w .1.3.6.1.4.1.534.6.6.6.2.2.1.5
The value of the lower critical threshold.
DegreesCelsiusr/w .1.3.6.1.4.1.534.6.6.6.2.2.1.6
The value of the upper critical threshold.
DegreesCelsiusr/w .1.3.6.1.4.1.534.6.6.6.2.2.1.7
The value of the lower warning (non-critical) reset/hysteresis value.
DegreesCelsiusr/w .1.3.6.1.4.1.534.6.6.6.2.2.1.8
The value of the upper warning (non-critical) reset/hysteresis value.
DegreesCelsiusr/w .1.3.6.1.4.1.534.6.6.6.2.2.1.9
The value of the lower critical reset/hysteresis value.
DegreesCelsiusr/w .1.3.6.1.4.1.534.6.6.6.2.2.1.10
The value of the upper critical reset/hysteresis value.
DegreesCelsiusr/w .1.3.6.1.4.1.534.6.6.6.2.2.1.11
.1.3.6.1.4.1.534.6.6.6.2.4 · 1 row entry · 11 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk humiditySensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MA-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MA-MIB::humiditySensorTable'
A list of humidity sensor entries. The number of
entries is given by the value of humiditySensorCount.
humiditySensorEntry row .1.3.6.1.4.1.534.6.6.6.2.4.1
An entry containing sensor reading and threshold
settings for a particular humidity sensor.
Column Syntax OID
A unique value for each humidity sensor. Its value
ranges between 1 and humiditySensorCount.
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.534.6.6.6.2.4.1.1
A settable human-readable label for the external humidity
sensor. One possible use for this label is to convey sensor
location.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.534.6.6.6.2.4.1.2
The value of the external humidity sensor reported
as relative humidity (a percentage).
RelativeHumidity
Type Constraints:
range: 0..100
.1.3.6.1.4.1.534.6.6.6.2.4.1.3
The value of the lower warning (non-critical) threshold.
RelativeHumidityr/w
Type Constraints:
range: 0..100
.1.3.6.1.4.1.534.6.6.6.2.4.1.4
The value of the upper warning (non-critical) threshold.
RelativeHumidityr/w
Type Constraints:
range: 0..100
.1.3.6.1.4.1.534.6.6.6.2.4.1.5
The value of the lower critical threshold.
RelativeHumidityr/w
Type Constraints:
range: 0..100
.1.3.6.1.4.1.534.6.6.6.2.4.1.6
The value of the upper critical threshold.
RelativeHumidityr/w
Type Constraints:
range: 0..100
.1.3.6.1.4.1.534.6.6.6.2.4.1.7
The value of the lower warning (non-critical) reset/hysteresis value.
RelativeHumidityr/w
Type Constraints:
range: 0..100
.1.3.6.1.4.1.534.6.6.6.2.4.1.8
The value of the upper warning (non-critical) reset/hysteresis value.
RelativeHumidityr/w
Type Constraints:
range: 0..100
.1.3.6.1.4.1.534.6.6.6.2.4.1.9
The value of the lower critical reset/hysteresis value.
RelativeHumidityr/w
Type Constraints:
range: 0..100
.1.3.6.1.4.1.534.6.6.6.2.4.1.10
The value of the upper critical reset/hysteresis value.
RelativeHumidityr/w
Type Constraints:
range: 0..100
.1.3.6.1.4.1.534.6.6.6.2.4.1.11