ats2TrapCommunicationLost | .1.3.6.1.4.1.534.10.2.10.1 | Communication with the ATS failed. |
ats2TrapSource1OutOfRange | .1.3.6.1.4.1.534.10.2.10.10 | Source 1 out of range. |
ats2TrapSource2Normal | .1.3.6.1.4.1.534.10.2.10.11 | Source 2 returns to normal. |
ats2TrapSource2OutOfRange | .1.3.6.1.4.1.534.10.2.10.12 | Source 2 out of range. |
ats2TrapSourceDesynchronized | .1.3.6.1.4.1.534.10.2.10.13 | Source 1 and Source 2 phase are desynchronized. |
ats2TrapSourceSynchronized | .1.3.6.1.4.1.534.10.2.10.14 | Source 1 and Source 2 phase are synchronized. |
ats2TrapOutputPoweredBySource1 | .1.3.6.1.4.1.534.10.2.10.15 | Source 1 powers the output. |
ats2TrapOutputPoweredBySource2 | .1.3.6.1.4.1.534.10.2.10.16 | Source 2 powers the output. |
ats2TrapCommunicationRecovered | .1.3.6.1.4.1.534.10.2.10.2 | Communication with the ATS recovered. |
ats2TrapRemoteTempLow | .1.3.6.1.4.1.534.10.2.10.20 | The remote temperature, ats2EnvRemoteTemp, has fallen below
the set lower limit, ats2EnvRemoteTempLowerLimit. |
ats2TrapRemoteTempHigh | .1.3.6.1.4.1.534.10.2.10.21 | The remote temperature, ats2EnvRemoteTemp, has risen above
the set upper limit, xupsEnvRemoteTempUpperLimit. |
ats2TrapRemoteTempNormal | .1.3.6.1.4.1.534.10.2.10.22 | The remote temperature, ats2EnvRemoteTemp, is inside the interval
defined by the lower limit and the upper limit. |
ats2TrapRemoteHumidityLow | .1.3.6.1.4.1.534.10.2.10.23 | The remote humidity, ats2EnvRemoteHumidity, has fallen below
the set lower limit, ats2EnvRemoteHumidityLowerLimit. |
ats2TrapRemoteHumidityHigh | .1.3.6.1.4.1.534.10.2.10.24 | The remote humidity, ats2EnvRemoteHumidity, has risen above
the set upper limit, ats2EnvRemoteHumidityUpperLimit. |
ats2TrapRemoteHumidityNormal | .1.3.6.1.4.1.534.10.2.10.25 | The remote humidity, ats2EnvRemoteHumidity, is inside the interval
defined by the lower limit and the upper limit. |
ats2Contact1ActiveNotice | .1.3.6.1.4.1.534.10.2.10.26 | The Contact 1 is in its Active state.
The following are the situations that generate this trap:
For ats2ContactType: and ats2ContactState:
normallyOpen(1) and closedWithNotice(4)
normallyClosed(2) and openWithNotice(3)
anyChange(3) and openWithNotice(3) or closedWithNotice(4) |
ats2Contact1InactiveNotice | .1.3.6.1.4.1.534.10.2.10.27 | The Contact 1 has changed to its Inactive state. |
ats2Contact2ActiveNotice | .1.3.6.1.4.1.534.10.2.10.28 | The Contact 2 is in its Active state.
The following are the situations that generate this trap:
For ats2ContactType: and ats2ContactState:
normallyOpen(1) and closedWithNotice(4)
normallyClosed(2) and openWithNotice(3)
anyChange(3) and openWithNotice(3) or closedWithNotice(4) |
ats2Contact2InactiveNotice | .1.3.6.1.4.1.534.10.2.10.29 | The Contact 2 has changed to its Inactive state. |
ats2TrapOutputPowered | .1.3.6.1.4.1.534.10.2.10.3 | The ATS powers the load. |
ats2TrapOutputNotPowered | .1.3.6.1.4.1.534.10.2.10.4 | The ATS does not powers the load. |
ats2TestTrap | .1.3.6.1.4.1.534.10.2.10.40 | Sent whenever the trap test feature is used by the communication card. |
ats2TrapOverload | .1.3.6.1.4.1.534.10.2.10.5 | The ATS has sensed a critical overload. |
ats2TrapNoOverLoad | .1.3.6.1.4.1.534.10.2.10.6 | The critical overload disappeared. |
ats2TrapInternalFailure | .1.3.6.1.4.1.534.10.2.10.7 | The ATS has an internal failure (sum of all HW internal failure). |
ats2TrapNoInternalFailure | .1.3.6.1.4.1.534.10.2.10.8 | The ATS internal failure disappeared. |
ats2TrapSource1Normal | .1.3.6.1.4.1.534.10.2.10.9 | Source 1 returns to normal. |