CPQRPM-MIB

Imported Objects

compaqCPQHOST-MIB
OBJECT-TYPERFC-1212
TRAP-TYPERFC-1215
DisplayString, sysNameRFC1213-MIB

Objects

cpqRPM .1.3.6.1.4.1.232.154
cpqRPMTrapInfo .1.3.6.1.4.1.232.154.1
cpqRPMTrapDescription mandatory .1.3.6.1.4.1.232.154.1.1
cpqRPMTrapDeviceId mandatory .1.3.6.1.4.1.232.154.1.2
cpqRPMTrapDeviceName mandatory .1.3.6.1.4.1.232.154.1.3
cpqRPMTrapDeviceAddress mandatory .1.3.6.1.4.1.232.154.1.4
cpqRPMTrapType mandatory .1.3.6.1.4.1.232.154.1.5
cpqRPMTrapSeverity mandatory .1.3.6.1.4.1.232.154.1.6
cpqRPMTrapCode mandatory .1.3.6.1.4.1.232.154.1.7
cpqRPMTrapURL mandatory .1.3.6.1.4.1.232.154.1.8
cpqRPMTraps .1.3.6.1.4.1.232.154.2
cpqPMTraps .1.3.6.1.4.1.232.154.3

Notifications/Traps

NameOIDDescription
cpqRPMTrapDeviceConnected








.1.3.6.1.4.1.232.154.2.0.1
ce is reporting a Connection Lost due to one of the following.
          
1. The serial cable connected to the UPS has been unplugged.
2. The Network cable connected to the UPS has been unplugged.
          
Recommendations:
          
1. Insure all cables are seated properly.
2. check you network to insure it is functioning properly.
3. If the UPS is serially connected insure that the Serial
   Relay Agent is installed and running.
cpqRPMTrapCMCTemp1BelowMin








.1.3.6.1.4.1.232.154.2.0.10001
A CMC device is reporting temperature 1 below minimum threshold.
cpqRPMTrapCMCTemp1AboveWarn








.1.3.6.1.4.1.232.154.2.0.10002
A CMC device is reporting temperature 1 above warning threshold.
cpqRPMTrapCMCTemp1AboveMax








.1.3.6.1.4.1.232.154.2.0.10003
A CMC device is reporting temperature 1 above maximum threshold.
cpqRPMTrapCMCTemp1Normal








.1.3.6.1.4.1.232.154.2.0.10004
ce is reporting temperature 1 has returned to a normal
temperature.
cpqRPMTrapCMCTemp2BelowMin








.1.3.6.1.4.1.232.154.2.0.10005
A CMC device is reporting temperature 2 below minimum threshold.
cpqRPMTrapCMCTemp2AboveWarn








.1.3.6.1.4.1.232.154.2.0.10006
A CMC device is reporting temperature 2 above warning threshold.
cpqRPMTrapCMCTemp2AboveMax








.1.3.6.1.4.1.232.154.2.0.10007
A CMC device is reporting temperature 2 above maximum threshold.
cpqRPMTrapCMCTemp2Normal








.1.3.6.1.4.1.232.154.2.0.10008
ce is reporting temperature 2 has returned to a normal
temperature.
cpqRPMTrapCMCVoltUnder








.1.3.6.1.4.1.232.154.2.0.10011
A CMC device is reporting voltage below minimum threshold.
cpqRPMTrapCMCVoltOver








.1.3.6.1.4.1.232.154.2.0.10012
A CMC device is reporting voltage above maximum threshold.
cpqRPMTrapCMCVoltNormal








.1.3.6.1.4.1.232.154.2.0.10013
A CMC device is reporting voltage has returned to normal.
cpqRPMTrapCMCHmdtUnder








.1.3.6.1.4.1.232.154.2.0.10021
A CMC device is reporting humidity below minimum threshold.
cpqRPMTrapCMCHmdtOver








.1.3.6.1.4.1.232.154.2.0.10022
A CMC device is reporting humidity above maximum threshold.
cpqRPMTrapCMCHmdtNormal








.1.3.6.1.4.1.232.154.2.0.10023
A CMC device is reporting humidity has returned to normal.
cpqRPMTrapCMCSmokeDetected








.1.3.6.1.4.1.232.154.2.0.10031
A CMC device is reporting smoke detected.
cpqRPMTrapCMCSmokeCleared








.1.3.6.1.4.1.232.154.2.0.10032
A CMC device is reporting smoke cleared.
cpqRPMTrapCMCShockDetected








.1.3.6.1.4.1.232.154.2.0.10041
A CMC device is reporting shock detected.
cpqRPMTrapCMCShockCleared








.1.3.6.1.4.1.232.154.2.0.10042
A CMC device is reporting shock cleared.
cpqRPMTrapCMCAux1Alarm








.1.3.6.1.4.1.232.154.2.0.10051
A CMC device has entered an alarm condition for auxiliary input 1.
cpqRPMTrapCMCAux1Cleared








.1.3.6.1.4.1.232.154.2.0.10052
A CMC device is reporting auxiliary input 1 alarm cleared.
cpqRPMTrapCMCAux2Alarm








.1.3.6.1.4.1.232.154.2.0.10053
A CMC device has entered an alarm condition for auxiliary input 2.
cpqRPMTrapCMCAux2Cleared








.1.3.6.1.4.1.232.154.2.0.10054
A CMC device is reporting auxiliary input 2 alarm cleared.
cpqRPMTrapCMCInput1Opened








.1.3.6.1.4.1.232.154.2.0.10101
A CMC device is reporting input 1 has been opened.
cpqRPMTrapCMCInput1Closed








.1.3.6.1.4.1.232.154.2.0.10102
A CMC device is reporting input 1 has been closed.
cpqRPMTrapCMCInput2Opened








.1.3.6.1.4.1.232.154.2.0.10103
A CMC device is reporting input 2 has been opened.
cpqRPMTrapCMCInput2Closed








.1.3.6.1.4.1.232.154.2.0.10104
A CMC device is reporting input 2 has been closed.
cpqRPMTrapCMCInput3Opened








.1.3.6.1.4.1.232.154.2.0.10105
A CMC device is reporting input 3 has been opened.
cpqRPMTrapCMCInput3Closed








.1.3.6.1.4.1.232.154.2.0.10106
A CMC device is reporting input 3 has been closed.
cpqRPMTrapCMCInput4Opened








.1.3.6.1.4.1.232.154.2.0.10107
A CMC device is reporting input 4 has been opened.
cpqRPMTrapCMCInput4Closed








.1.3.6.1.4.1.232.154.2.0.10108
A CMC device is reporting input 4 has been closed.
cpqRPMTrapCMCLockset1Unlocked








.1.3.6.1.4.1.232.154.2.0.10111
A CMC device is reporting lockset 1 has been unlocked.
cpqRPMTrapCMCLockset1FailedToLock








.1.3.6.1.4.1.232.154.2.0.10112
A CMC device is reporting lockset 1 has failed to lock.
cpqRPMTrapCMCLockset1Error








.1.3.6.1.4.1.232.154.2.0.10113
A CMC device is reporting an error with lockset 1.
cpqRPMTrapCMCLockset1Locked








.1.3.6.1.4.1.232.154.2.0.10114
A CMC device is reporting lockset 1 has been locked.
cpqRPMTrapCMCLockset2Unlocked








.1.3.6.1.4.1.232.154.2.0.10116
A CMC device is reporting lockset 2 has been unlocked.
cpqRPMTrapCMCLockset2FailedToLock








.1.3.6.1.4.1.232.154.2.0.10117
A CMC device is reporting lockset 2 has failed to lock.
cpqRPMTrapCMCLockset2Error








.1.3.6.1.4.1.232.154.2.0.10118
A CMC device is reporting an error with lockset 2.
cpqRPMTrapCMCLockset2Locked








.1.3.6.1.4.1.232.154.2.0.10119
A CMC device is reporting lockset 2 has been locked.
cpqRPMTrapCMCLockset1Normal








.1.3.6.1.4.1.232.154.2.0.10134
A CMC device is reporting lockset 2 is normal.
cpqRPMTrapCMCLockset2Normal








.1.3.6.1.4.1.232.154.2.0.10135
A CMC device is reporting lockset 2 is normal.
cpqRPMTrapConnectionLost








.1.3.6.1.4.1.232.154.2.0.2
ce is reporting a Connection Lost due to one of the following.
          
1. The serial cable connected to the UPS has been unplugged.
2. The Network cable connected to the UPS has been unplugged.
          
Recommendations:
          
1. Insure all cables are seated properly.
2. check you network to insure it is functioning properly.
3. If the UPS is serially connected insure that the Serial
   Relay Agent is installed and running.
cpqRPMTrapUPSInputVoltageBelowMin







.1.3.6.1.4.1.232.154.2.0.20001
A UPS device is reporting input voltage below minimum threshold.
cpqRPMTrapUPSInputVoltageAboveMax







.1.3.6.1.4.1.232.154.2.0.20002
A UPS device is reporting input voltage above maximum threshold.
cpqRPMTrapUPSInputVoltageNormal








.1.3.6.1.4.1.232.154.2.0.20003
ce is reporting input voltage is out of range.
          
Recommendations:
          
1. Check to make sure the UPS is plugged into an outlet supplied with utility power.
2. If the UPS remains on battery for an extended period of time it will not be able to sustain the load.
cpqRPMTrapUPSOutputVoltageBelowMin







.1.3.6.1.4.1.232.154.2.0.20011
A UPS device is reporting output voltage below minimum threshold.
cpqRPMTrapUPSOutputVoltageAboveMax







.1.3.6.1.4.1.232.154.2.0.20012
A UPS device is reporting output voltage above maximum threshold.
cpqRPMTrapUPSOutputOverload








.1.3.6.1.4.1.232.154.2.0.20014
ce is reporting an overload condition.
          
Recommendations:
          
1. Reduce the load on the UPS by moving some of the load to another UPS.
2. Consider moving to a larger UPS to support the current load.
cpqRPMTrapUPSOutputOverloadCleared








.1.3.6.1.4.1.232.154.2.0.20015
ce is reporting an overload condition.
          
Recommendations:
          
1. Reduce the load on the UPS by moving some of the load to another UPS.
2. Consider moving to a larger UPS to support the current load.
cpqRPMTrapUPSBatteryDepleted







.1.3.6.1.4.1.232.154.2.0.20022
A UPS device is a depleted battery.
cpqRPMTrapUPSBatteryLevelNormal








.1.3.6.1.4.1.232.154.2.0.20023
ce is reporting low battery.
          
Recommendations:
          
1. Check to make sure the UPS is plugged into an outlet supplied with utility power.
2. When utility power is restored, charge the battery to it's full capacity.
   If the battery level continues to decrease, the UPS will not be able to sustain the output load!
cpqRPMTrapUPSOnBypass







.1.3.6.1.4.1.232.154.2.0.20032
A UPS device is being bypassed.
cpqRPMTrapUPSTemperatureLow







.1.3.6.1.4.1.232.154.2.0.20101
A UPS device is reporting temperature blow minimum threshold.
cpqRPMTrapUPSTemperatureHigh







.1.3.6.1.4.1.232.154.2.0.20102
A UPS device is reporting temperature above maximum threshold.
cpqRPMTrapUPSTemperatureNormal








.1.3.6.1.4.1.232.154.2.0.20103
ce is reporting temperature is out of range.
          
Recommendations:
          
1. Check to make sure the UPS is in a well ventilated area.
2. Lower the ambient temperature in the area where the UPS is located.
cpqRPMTrapUPSInternalFailure








.1.3.6.1.4.1.232.154.2.0.20111
ce is reporting  a general UPS failure.
          
Recommendations:
          
1. Initiate a UPS self test.
2. If this error persists contact technical support.
cpqRPMTrapUPSInternalFailureCleared








.1.3.6.1.4.1.232.154.2.0.20112
ce is reporting  a general UPS failure.
          
Recommendations:
          
1. Initiate a UPS self test.
2. If this error persists contact technical support.
cpqRPMTrapUPSBatteryFailure








.1.3.6.1.4.1.232.154.2.0.20121
ce is reporting a battery failure.
          
Recommendations:
          
1. Initiate a UPS self test.
2. If this error persists contact technical support.
3. Your battery may need to be replaced.
   The UPS may not be capable of supporting it's load if utility power fails!
cpqRPMTrapUPSBatteryFailureCleared








.1.3.6.1.4.1.232.154.2.0.20122
ce is reporting a battery failure.
          
Recommendations:
          
1. Initiate a UPS self test.
2. If this error persists contact technical support.
3. Your battery may need to be replaced.
   The UPS may not be capable of supporting it's load if utility power fails!
cpqRPMTrapUPSDiagnosticTestFailed







.1.3.6.1.4.1.232.154.2.0.20131
ce is reporting a diagnostic test failed.
          
Recommendations:
          
1. Your battery may need to be replaced.
2. If this error persists contact technical support.
3. The UPS may not be capable of supporting it's load if utility power fails!
cpqRPMTrapUPSDiagnosticTestSucceeded







.1.3.6.1.4.1.232.154.2.0.20132
ce is reporting a diagnostic test failed.
          
Recommendations:
          
1. Your battery may need to be replaced.
2. If this error persists contact technical support.
3. The UPS may not be capable of supporting it's load if utility power fails!
cpqRPMTrapUPSInputUnderOverFreq







.1.3.6.1.4.1.232.154.2.0.20141
Input (Utility) fault: measured input frequency is outside of either the upper or lower frequency limit specification for normal operation.
cpqRPMTrapUPSInputUnderOverFreqCleared







.1.3.6.1.4.1.232.154.2.0.20142
Measured input frequency is normal
cppqRPMtrapUPSStartedOnBattery








.1.3.6.1.4.1.232.154.2.0.20151
ce has been started  while on battery power. AC input power is not present.
          
Recommendations:
          
1. Check to make sure the UPS is plugged into an outlet supplied with utility power.
   If the UPS remains on battery for an extended time it will not be able to sustain the output load.
cppqRPMtrapUPSStartedOnBatteryCleared








.1.3.6.1.4.1.232.154.2.0.20152
ce has been started  while on battery power. AC input power is not present.
          
Recommendations:
          
1. Check to make sure the UPS is plugged into an outlet supplied with utility power.
   If the UPS remains on battery for an extended time it will not be able to sustain the output load!
cpqRPMTrapUPSBypassNotAvailable








.1.3.6.1.4.1.232.154.2.0.20161
ce is reporting bypass not avaliable.
          
Recommendations:
          
1. Initiate a UPS self test.
2. If this error persists contact technical support.
cpqRPMTrapUPSBypassNotAvailableCleared








.1.3.6.1.4.1.232.154.2.0.20162
ce is reporting bypass not avaliable.
          
Recommendations:
          
1. Initiate a UPS self test.
2. If this error persists contact technical support.
cpqRPMTrapUPSUtilityFail







.1.3.6.1.4.1.232.154.2.0.20171
that the utility input power is not within predetermined limits.
This could be, but is not limited to, over voltage, under voltage, over frequency,
under frequency or over current.
cpqRPMTrapUPSUtilityFailCleared







.1.3.6.1.4.1.232.154.2.0.20172
Indicates that the utility input power is within predetermined limits.
cpqRPMTrapUPSUtilityNotPresent







.1.3.6.1.4.1.232.154.2.0.20181
that the utility input is not present.  This differs from
alarm #57 in that the detected voltage is zero in this case.
cpqRPMTrapUPSUtilityNotPresentCleared







.1.3.6.1.4.1.232.154.2.0.20182
Indicates that the utility input is present.
cpqRPMTrapUPSBypassManualTurnedOn







.1.3.6.1.4.1.232.154.2.0.20191
The bypass has been given a manual turn on command.
cpqRPMTrapUPSBypassManualTurnedOff







.1.3.6.1.4.1.232.154.2.0.20192
The bypass has been given a manual turn off command.
cpqRPMTrapUPSSiteWiringFault








.1.3.6.1.4.1.232.154.2.0.20201
ce is reporting  a fault in the input wiring, other than
Phase Rotation: e.g., Ground/Neutral reversed.
          
Recommendations:
          
1. Contact an electrician.
cpqRPMTrapUPSSiteWiringNormal








.1.3.6.1.4.1.232.154.2.0.20202
ce is reporting  a fault in the input wiring, other than
Phase Rotation: e.g., Ground/Neutral reversed.
          
Recommendations:
          
1. Contact an electrician.
cpqRPMtrapUPSTemperatureOutOfRange








.1.3.6.1.4.1.232.154.2.0.21007
ce is reporting  temperature is out of range.
          
Recommendations:
          
1. Check to make sure the UPS is in a well ventilated area.
2. Lower the ambient temperature in the area where the UPS is located.
cpqRPMtrapUPSTemperatureOutOfRangeCleared








.1.3.6.1.4.1.232.154.2.0.21008
ce is reporting temperature is out of range.
          
Recommendations:
          
1. Check to make sure the UPS is in a well ventilated area.
2. Lower the ambient temperature in the area where the UPS is located.
cpqRPMTrapUPSShutdownPending








.1.3.6.1.4.1.232.154.2.0.21011
ce is reporting shutdown pending condition.
          
Recommendations:
          
1. Immediately restore power to the UPS.
   The UPS will not continue to supply power to devices following the shutdown!
cpqRPMTrapUPSShutdownPendingCleared








.1.3.6.1.4.1.232.154.2.0.21012
ce is reporting shutdown pending condition.
          
Recommendations:
          
1. Immediately restore power to the UPS.
   The UPS will not continue to supply power to devices following the shutdown!
cpqRPMTrapUPSShutdownImminent








.1.3.6.1.4.1.232.154.2.0.21013
ce is reporting a shutdown imminent condition.
          
Recommendations:
          
1. Immediately restore power to the UPS.
   The UPS will not continue to supply power to devices following the shutdown!
cpqRPMTrapUPSShutdownImminentCleared








.1.3.6.1.4.1.232.154.2.0.21014
ce is reporting a shutdown imminent condition.
          
Recommendations:
          
1. Immediately restore power to the UPS.
   The UPS will not continue to supply power to devices following the shutdown!
cpqRPMtrapUPSOutputoutofRange








.1.3.6.1.4.1.232.154.2.0.21019
ce is reporting output voltage is out of Range.
          
Recommendations:
          
1. Initiate a UPS self test.
2. If this error persists contact technical support.
cpqRPMTrapUPSOutputVoltageNormal








.1.3.6.1.4.1.232.154.2.0.21020
ce is reporting output voltage is out of Range.
          
Recommendations:
          
1. Initiate a UPS self test.
2. If this error persists contact technical support.
cpqRPMtrapUPSInputOutofRange








.1.3.6.1.4.1.232.154.2.0.21021
ce is reporting input voltage is out of range.
          
Recommendations:
          
1. Check to make sure the UPS is plugged into an outlet supplied with utility power.
2. If the UPS remains on battery for an extended period of time it will not be able to sustain the load.
cpqRPMtrapUPSInputOutofRangeCleared








.1.3.6.1.4.1.232.154.2.0.21022
ce is reporting input voltage is out of range.
          
Recommendations:
          
1. Check to make sure the UPS is plugged into an outlet supplied with utility power.
2. If the UPS remains on battery for an extended period of time it will not be able to sustain the load.
cpqRPMTrapUPSLossOfRedundancy








.1.3.6.1.4.1.232.154.2.0.21023
ce is reporting a loss of redundancy due to one of the following.
1. One or more of the Electronics Modules has failed
2. One or more of the electronics modules has been manually removed.
3. The amount of load on the UPS has increased to the point that the UPS
   is no longer able to support an N+1 configuration.
          
Recommendations:
          
1. Check the UPS to see if one of the modules has failed.
2. Make sure that all modules are securely plugged in.
3. Reduce the load to return the N+1 configuration.
4. If the amount of load is now going to exceed and N+1 configuration
   permanently, change the configuration on the front panel of the UPS
   to Capacity instead of Parallel N+1.
cpqRPMTrapUPSLossOfRedundancyCleared








.1.3.6.1.4.1.232.154.2.0.21024
ce is reporting a loss of redundancy due to one of the following.
1. One or more of the Electronics Modules has failed
2. One or more of the electronics modules has been manually removed.
3. The amount of load on the UPS has increased to the point that the UPS is no longer
   able to support an N+1 configuration.
          
Recommendations:
          
1. Check the UPS to see if one of the modules has failed.
2. Make sure that all modules are securely plugged in.
3. Reduce the load to return the N+1 configuration.
4. If the amount of load is now going to exceed and N+1 configuration permanently,
   change the configuration on the front panel of the UPS to Capacity instead of Parallel N+1.
cpqRPMTrapUPSOnBuck







.1.3.6.1.4.1.232.154.2.0.21029
ce is reporting an On Buck condition due to the following.
          
1. Utility power has increased above recommended utility input levels.
          
Recommendation:
          
1. Contact an electrician.
cpqRPMTrapUPSOnBoost







.1.3.6.1.4.1.232.154.2.0.21031
ce is reporting an On Boost condition due to the following.
          
1. Utility power has dropped below recommended utility input levels.
          
Recommendation:
          
1. Contact an electrician.
cpqRPMTrapUPSManualLoadDumped








.1.3.6.1.4.1.232.154.2.0.21033
The UPS has been powered off with user interaction.
cpqRPMTrapUPSManualLoadDumpedCleared








.1.3.6.1.4.1.232.154.2.0.21034
The UPS has been powered off with user interaction.
cpqRPMTrapUPSFanFailure








.1.3.6.1.4.1.232.154.2.0.21035
ce is reporting a fan failure has occurred.
          
Recommendations:
          
1. If this error persists contact technical support.
cpqRPMTrapUPSFanFailureCleared








.1.3.6.1.4.1.232.154.2.0.21036
ce is reporting a fan failure has occurred.
          
Recommendations:
          
1. If this error persists contact technical support.
cpqRPMTrapUPSEPOInitiated








.1.3.6.1.4.1.232.154.2.0.21037
ce is reporting an Emergency Power Off (EPO) command has been
received to shutdown the UPS immediately with out delay. This command
may come from a local control panel or from a remote source.
          
Recommendations:
          
1. Turn the UPS on to reapply power to attached equipment.
cpqRPMTrapUPSCheckBreaker








.1.3.6.1.4.1.232.154.2.0.21041
ce is reporting an output Breaker or Relay has failed or may be
stuck open or closed with this alarm.
          
Recommendations:
          
1. Check all breakers on the UPS.
2. If this error persists contact technical support.
cpqRPMTrapUPSCheckBreakerCleared








.1.3.6.1.4.1.232.154.2.0.21042
ce is reporting an output Breaker or Relay has failed or may be
stuck open or closed with this alarm.
          
Recommendations:
          
1. Check all breakers on the UPS.
2. If this error persists contact technical support.
cpqRPMTrapUPSCabinetDoorOpen








.1.3.6.1.4.1.232.154.2.0.21045
ce is reporting a cover panel has been removed while utility power is present.
          
Recommendations:
          
1. Reinstall all panels.
2. If this error persists contact technical support.
cpqRPMTrapUPSCabinetDoorOpenCleared








.1.3.6.1.4.1.232.154.2.0.21046
ce is reporting a cover panel has been removed while utility power is present.
          
Recommendations:
          
1. Reinstall all panels.
2. If this error persists contact technical support.
cpqRPMtrapUPSBypassOnAuto








.1.3.6.1.4.1.232.154.2.0.21047
ce is operating in auto bypass mode.
          
Recommendations:
          
1. In bypass mode, the UPS cannot support devices if there is a power failure.
2. Once maintenance has been performed return the UPS to normal mode.
cpqRPMtrapUPSBypassOnAutoCleared








.1.3.6.1.4.1.232.154.2.0.21048
ce is operating in auto bypass mode.
          
Recommendations:
          
1. In bypass mode, the UPS cannot support devices if there is a power failure.
2. Once maintenance has been performed return the UPS to normal mode.
cpqRPMTrapUPSBatteriesDisconnected








.1.3.6.1.4.1.232.154.2.0.21053
ce is reporting  batteries are not connected to the UPS.
          
Recomendations:
          
1. Connect the UPS Batteries.
   The UPS will not be capable of supporting it's load if the utility power fails!
cpqRPMTrapUPSBatteriesDisconnectedCleared








.1.3.6.1.4.1.232.154.2.0.21054
ce is reporting  batteries are not connected to the UPS.
          
Recomendations:
          
1. Connect the UPS Batteries.
   The UPS will not be capable of supporting it's load if the utility power fails!
cpqRPMTrapUPSBatteryLow








.1.3.6.1.4.1.232.154.2.0.21055
ce is reporting low battery.
          
Recommendations:
          
1. Check to make sure the UPS is plugged into an outlet supplied with utility power.
2. When utility power is restored, charge the battery to it's full capacity.
   If the battery level continues to decrease, the UPS will not be able to sustain the output load!
cpqRPMTrapUPSBatteryLowCleared








.1.3.6.1.4.1.232.154.2.0.21056
ce is reporting low battery.
          
Recommendations:
          
1. Check to make sure the UPS is plugged into an outlet supplied with utility power.
2. When utility power is restored, charge the battery to it's full capacity.
   If the battery level continues to decrease, the UPS will not be able to sustain the output load!
cpqRPMTrapUPSBatteryDischarged








.1.3.6.1.4.1.232.154.2.0.21057
ce is reporting batteries are completely discharged.
          
Recommendations:
          
1. Connect the UPS to utility power to charge the batteries.
   The UPS will not be able to support it's load if the utility power fails!
cpqRPMTrapUPSBatteryDischargedCleared








.1.3.6.1.4.1.232.154.2.0.21058
ce is reporting batteries are completely discharged.
          
Recommendations:
          
1. Connect the UPS to utility power to charge the batteries.
   The UPS will not be able to support it's load if the utility power fails!
cpqRPMtrapUPSBypassONManual








.1.3.6.1.4.1.232.154.2.0.21059
ce is operating in manual bypass mode.
          
Recommendations:
          
1. In bypass mode, the UPS cannot support devices if there is a power failure.
2. Once maintenance has been performed return the UPS to normal mode.
cpqRPMtrapUPSBypassOffManual








.1.3.6.1.4.1.232.154.2.0.21060
ce is operating in manual bypass mode.
          
Recommendations:
          
1. In bypass mode, the UPS cannot support devices if there is a power failure.
2. Once maintenance has been performed return the UPS to normal mode.
cpqRPMTrapUPSOnBattery








.1.3.6.1.4.1.232.154.2.0.21063
ce is reporting on battery condition.
          
Recommendations:
          
1. Check to make sure the UPS is plugged into an outlet supplied with utility power.
   If the UPS remains on battery for an extended time it will not be able to sustain the output load!
cpqRPMTrapUPSOnUtilityPower








.1.3.6.1.4.1.232.154.2.0.21064
ce is reporting on battery condition.
          
Recommendations:
          
1. Check to make sure the UPS is plugged into an outlet supplied with utility power.
   If the UPS remains on battery for an extended time it will not be able to sustain the output load!
cpqRPMTrapUPSDCStartOccurred







.1.3.6.1.4.1.232.154.2.0.29998
The UPS has been started on battery when AC input power is not present.  This alarm is used to record the date and time of this event.
cpqRPMTrapUPSDCStartOccurredCleared







.1.3.6.1.4.1.232.154.2.0.29999
The UPS has been started on utility while AC input power is present.
cpqRPMTrapLookupFailed








.1.3.6.1.4.1.232.154.2.0.3
CRPM failed to find an IP address for the device hostname.
cpqRPMTrapConnectionFailed








.1.3.6.1.4.1.232.154.2.0.4
CRPM failed to connect to a device.
cpqRPMTrapDeviceSettingsChanged








.1.3.6.1.4.1.232.154.2.0.5
Device settings have been changed by a user.
cpqRPMTestTrap







.1.3.6.1.4.1.232.154.2.0.50001
This trap is sent to test SNMP setup.
cpqPMTrapCritical





.1.3.6.1.4.1.232.154.3.0.1
A critical alarm has occurred. Action: Check the Trap Details for more information.
cpqPMTrapWarning





.1.3.6.1.4.1.232.154.3.0.2
A warning alarm has occurred. Action: Check the Trap Details for more information.
cpqPMTrapInformation





.1.3.6.1.4.1.232.154.3.0.3
An information alarm has occurred. Action: Check the Trap Details for more information.
cpqPMTrapCleared





.1.3.6.1.4.1.232.154.3.0.4
An alarm has cleared. Action: Check the Trap Details for more information.