BESTPOWER-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
5
Rows
5
Columns
18

upsConfigTestScheduleTable

table mandatory
.1.3.6.1.4.1.2947.1.5.4 · 1 row entry · 3 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk upsConfigTestScheduleTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BESTPOWER-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BESTPOWER-MIB::upsConfigTestScheduleTable'
The table to schedule ups battery tests.
upsConfigTestScheduleEntry row .1.3.6.1.4.1.2947.1.5.4.1
The entries for each day.
Column Syntax OID
The index of scheduled events.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2947.1.5.4.1.1
The weekday on which the UPS should shut down.
Enumerationr/w
Enumerated Values:
1sunday
2monday
3tuesday
4wednesday
5thursday
6friday
7saturday
8none
.1.3.6.1.4.1.2947.1.5.4.1.2
The time that the process of shutting down the UPS will be initiated
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.2947.1.5.4.1.3
.1.3.6.1.4.1.2947.1.5.5 · 1 row entry · 5 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk upsConfigShutdownScheduleTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BESTPOWER-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BESTPOWER-MIB::upsConfigShutdownScheduleTable'
The table to schedule shutting down the ups.
upsConfigShutdownScheduleEntry row .1.3.6.1.4.1.2947.1.5.5.1
The entries for each day.
Column Syntax OID
The index of scheduled events.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2947.1.5.5.1.1
The weekday on which the UPS should shut down.
Enumerationr/w
Enumerated Values:
1sunday
2monday
3tuesday
4wednesday
5thursday
6friday
7saturday
8none
.1.3.6.1.4.1.2947.1.5.5.1.2
The time that the process of shutting down the UPS will be initiated
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.2947.1.5.5.1.3
The weekday on which the UPS should restart
Enumerationr/w
Enumerated Values:
1sunday
2monday
3tuesday
4wednesday
5thursday
6friday
7saturday
8none
.1.3.6.1.4.1.2947.1.5.5.1.4
The time the UPS will restart in hh:mm:ss format.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.2947.1.5.5.1.5
.1.3.6.1.4.1.2947.1.5.9.1 · 1 row entry · 5 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk upsConfigTrapsReceiversTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BESTPOWER-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BESTPOWER-MIB::upsConfigTrapsReceiversTable'
A list of managers to send traps to.
upsConfigTrapsReceiversEntry row .1.3.6.1.4.1.2947.1.5.9.1.1
The managers to send traps to.
Indexes
Column Syntax OID
trapsIndexmandatory
The index to a trap receiver entry.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2947.1.5.9.1.1.1
The IP address of the manager to send a trap to.
RFC1155-SMIIpAddressr/w
Type Constraints:
range: 4
.1.3.6.1.4.1.2947.1.5.9.1.1.2
The community name to use in the trap when
sent to the manager.
OctetStringr/w
Constraints:
range: 0-19
.1.3.6.1.4.1.2947.1.5.9.1.1.3
severityLevelmandatory
The severity threshold of traps to send to the manager.
Traps are labeled by severity as informational(1), warning(2),
severe(3). Only traps of equal or greater severity than
this value are sent to the manager.
Enumerationr/w
Enumerated Values:
1information
2warning
3severe
.1.3.6.1.4.1.2947.1.5.9.1.1.4
An entry will become active if yes, otherwise it will be
disabled.
Enumerationr/w
Enumerated Values:
1yes
2no
.1.3.6.1.4.1.2947.1.5.9.1.1.5
.1.3.6.1.4.1.2947.1.5.10.1 · 1 row entry · 2 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk upsRegisteredShutdownClientsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BESTPOWER-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BESTPOWER-MIB::upsRegisteredShutdownClientsTable'
A list of registered shutdown client table entries.
The table contains zero, one, or many rows at any moment,
depending upon the number of Netwatch clients registered
with BestLink
upsRegisteredShutdownClientsEntry row .1.3.6.1.4.1.2947.1.5.10.1.1
An entry containing information applicable to a
particular registered shutdown client.
Column Syntax OID
An index of alarm entries in the RegisteredShutdownClientsTable.
PositiveInteger .1.3.6.1.4.1.2947.1.5.10.1.1.1
The IP Address of the registered shutdown client
RFC1155-SMIIpAddress
Type Constraints:
range: 4
.1.3.6.1.4.1.2947.1.5.10.1.1.2

upsAlarmTable

table mandatory
.1.3.6.1.4.1.2947.1.8.3 · 1 row entry · 3 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk upsAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BESTPOWER-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BESTPOWER-MIB::upsAlarmTable'
A list of alarm table entries.  The table contains
zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect.  The table
is initially empty at agent startup.  The agent
creates a row in the table each time a condition is
detected and deletes that row when that condition no
longer pertains.  The agent creates the first row with
upsAlarmIndex equal to 1, and increments the value of
upsAlarmIndex each time a new row is created.
upsAlarmEntry row .1.3.6.1.4.1.2947.1.8.3.1
An entry containing information applicable to a
particular alarm.
Indexes
Column Syntax OID
upsAlarmIndexmandatory
An index of alarm entries in the alarm log.
PositiveInteger .1.3.6.1.4.1.2947.1.8.3.1.1
upsAlarmNamemandatory
A unique identifier for an alarm condition. This
value must remain constant.
Enumeration
Enumerated Values:
1onBattery
2lowRuntime
3nearLowBattery
4lowBattery
5highBattery
6checkBattery
7replaceBattery
8checkInverter
9batteriesDisconnected
10outputOverload
11lowAcOut
12circuitBreakerWarning
13circuitBreakerShdn
14bypassOn
15autoBypass
16siteWiringFault
17checkFan
18highAmbTemp
19highHSTemp
20highXFMRTemp
21highPFMTemp
22probeMissing
23checkPowerSupply
24tapRegulator
25relayFailure
26checkFuse
27checkMOV
28memoryError
29callService
30upsFailed
31userTest
32testInProgress
33diagnosticTestFailed
34ePO
35upsOff
36communicationsLost
.1.3.6.1.4.1.2947.1.8.3.1.2
upsAlarmTimemandatory
The time that the alarm occurred in hh:mm:ss format.
RFC1213-MIBDisplayString .1.3.6.1.4.1.2947.1.8.3.1.3