BACHMANN-BNPRO-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
25
Rows
25
Columns
253
.1.3.6.1.4.1.31770.10.1.3.1 · 1 row entry · 3 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProClusterTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProClusterTable'
Cluster table with one row per exposed PDU.
bnProClusterEntry row .1.3.6.1.4.1.31770.10.1.3.1.1
One cluster PDU row.
Column Syntax OID
PDU index within the cluster table.
Unsigned32
Constraints:
range: 1-20
.1.3.6.1.4.1.31770.10.1.3.1.1.1
Label of this cluster PDU: its configured name, defaulting to the PDU's
hostname when unset.

This is the writable source of the label that the read-only PduLabel
column of every element table reports for …
SNMPv2-TCDisplayStringr/w
Constraints:
range: 0-64
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.3.1.1.2
Configured cluster mode (role) of this PDU.

This is the persisted mode of the cluster member, not its live
connection health: a PDU configured as link(2) reports link(2)
whether or not it is currently rea…
BnProClusterMode
Type Values:
0unknown
1main
2link
3scanMain
4powerOnly
5bridged
Description:
Configured cluster mode (role) of a PDU.

Values 1-5 are a 1:1 mirror of the camodels cluster.Mode enum, in its
declaration order: the CLI and web frontend carry this setting as the
string 'main' / 'link' / 's…
.1.3.6.1.4.1.31770.10.1.3.1.1.3
.1.3.6.1.4.1.31770.10.1.4.1 · 1 row entry · 27 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProDevicePropertiesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProDevicePropertiesTable'
Table of PDU properties exposed by this SNMP agent. In cluster mode this includes the Main PDU and visible Link PDUs.
bnProDevicePropertiesEntry row .1.3.6.1.4.1.31770.10.1.4.1.1
One PDU entry.
Column Syntax OID
PDU index within the exposed system. Value 1 normally represents the Main PDU.
Unsigned32
Constraints:
range: 1-20
.1.3.6.1.4.1.31770.10.1.4.1.1.1
Human-readable PDU name or hostname.
SNMPv2-TCDisplayString
Constraints:
range: 0-64
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.4.1.1.2
User-configurable friendly name of this PDU.
SNMPv2-TCDisplayStringr/w
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.4.1.1.3
User-configurable location of this PDU.
SNMPv2-TCDisplayStringr/w
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.4.1.1.4
Product model configuration name.
SNMPv2-TCDisplayString
Constraints:
range: 0-64
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.4.1.1.5
Serial number of this PDU.
SNMPv2-TCDisplayString
Constraints:
range: 0-64
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.4.1.1.6
Item number of this PDU.
SNMPv2-TCDisplayString
Constraints:
range: 0-64
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.4.1.1.7
Hardware revision of this PDU, covering control unit (CU), power supply unit (PSU), MCB monitor, and outlet board revisions. Example format: 01.04.05.03.
SNMPv2-TCDisplayString
Constraints:
range: 0-64
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.4.1.1.8
Software version of this PDU.
SNMPv2-TCDisplayString
Constraints:
range: 0-64
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.4.1.1.9
Ethernet 1 MAC address for this PDU.
SNMPv2-TCDisplayString
Constraints:
range: 0-32
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.4.1.1.10
Ethernet 2 MAC address for this PDU.
SNMPv2-TCDisplayString
Constraints:
range: 0-32
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.4.1.1.11
Bridge 0 MAC address for this PDU.
SNMPv2-TCDisplayString
Constraints:
range: 0-32
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.4.1.1.12
Product class of this PDU.
Enumeration
Enumerated Values:
0unknown
1metered
2meteredPlus
3switched
4switchedPlus
.1.3.6.1.4.1.31770.10.1.4.1.1.13
Electrical phase variant of this PDU.
Enumeration
Enumerated Values:
0unknown
1onePhase
3threePhase
.1.3.6.1.4.1.31770.10.1.4.1.1.14
Device rating variant of this PDU.
Enumeration
Enumerated Values:
0unknown
16amp16
32amp32
63amp63
.1.3.6.1.4.1.31770.10.1.4.1.1.15
Indicates whether outlet switching is supported.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.31770.10.1.4.1.1.16
Indicates whether outlet measurement is supported.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.31770.10.1.4.1.1.17
Indicates whether outlet measurement is enabled.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.31770.10.1.4.1.1.18
Indicates whether this PDU supports RCM.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.31770.10.1.4.1.1.19
Indicates whether this PDU supports MCB/fuse monitoring.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.31770.10.1.4.1.1.20
Number of inlets available on this PDU.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.31770.10.1.4.1.1.21
Number of phases available on this PDU.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.31770.10.1.4.1.1.22
Number of outlets available on this PDU.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.31770.10.1.4.1.1.23
Number of MCB/fuse entries available on this PDU.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.31770.10.1.4.1.1.24
Number of RCM entries available on this PDU.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.31770.10.1.4.1.1.25
Number of external sensor entries available on this PDU.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.31770.10.1.4.1.1.26
Number of GPIO entries available on this PDU.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.31770.10.1.4.1.1.27
.1.3.6.1.4.1.31770.10.1.4.2 · 1 row entry · 15 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProDeviceMeasurementsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProDeviceMeasurementsTable'
Per-PDU electrical measurements. This subtable sits under the PDU branch, similar to element measurement tables.
bnProDeviceMeasurementsEntry row .1.3.6.1.4.1.31770.10.1.4.2.1
Column Syntax OID
Label of the PDU this row belongs to: the PDU's configured name, defaulting to its hostname when unset. Identifies the owning PDU without a lookup in the device table; the PDU's numeric index remains the first INDEX sub…
SNMPv2-TCDisplayString
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.4.2.1.1
Total PDU input current.
mABnProCurrentMilliAmpere
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.4.2.1.2
Maximum observed PDU input current.
mABnProCurrentMilliAmpere
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.4.2.1.3
Total active power of this PDU.
WBnProWatt
Description:
Active power in watts (whole numbers). Example: 1200 means 1200 W.
.1.3.6.1.4.1.31770.10.1.4.2.1.4
Maximum observed active power of this PDU.
WBnProWatt
Description:
Active power in watts (whole numbers). Example: 1200 means 1200 W.
.1.3.6.1.4.1.31770.10.1.4.2.1.5
Total apparent power of this PDU.
VABnProVoltAmpere
Description:
Apparent power in volt-amperes (whole numbers). Example: 1500 means 1500 VA.
.1.3.6.1.4.1.31770.10.1.4.2.1.6
Total reactive power of this PDU.
varBnProVar
Description:
Reactive power in volt-amperes reactive (whole numbers). Example: 300 means 300 var.
.1.3.6.1.4.1.31770.10.1.4.2.1.7
PDU power factor. Example: 1000 means 1.000.
BnProPowerFactorMilli
Type Constraints:
range: -1000..1000
Description:
Power factor value with 0.001 base resolution. Example: 980 means 0.980.
.1.3.6.1.4.1.31770.10.1.4.2.1.8
Power factor suffix, for example LA or LE.
SNMPv2-TCDisplayString
Constraints:
range: 0-8
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.4.2.1.9
Accumulated active energy in Wh. For kWh, divide by 1000.
WhBnProWattHour
Based On: SNMPv2-SMICounter64
Description:
Active energy counter in watt-hours stored as integer Wh. A compliant MIB browser
divides by 1000 and appends UNITS to display e.g. 4567 renders as 4.567 kWh.
Wraps at 2^63-1 Wh.
.1.3.6.1.4.1.31770.10.1.4.2.1.10
Second accumulated active energy counter in Wh. For kWh, divide by 1000.
WhBnProWattHour
Based On: SNMPv2-SMICounter64
Description:
Active energy counter in watt-hours stored as integer Wh. A compliant MIB browser
divides by 1000 and appends UNITS to display e.g. 4567 renders as 4.567 kWh.
Wraps at 2^63-1 Wh.
.1.3.6.1.4.1.31770.10.1.4.2.1.11
Accumulated apparent energy in VAh. For kVAh, divide by 1000.
VAhBnProVoltAmpereHour
Based On: SNMPv2-SMICounter64
Description:
Apparent energy counter in volt-ampere-hours stored as integer VAh.
Divide by 1000 for kVAh display. Example: 2500 renders as 2.500 kVAh.
.1.3.6.1.4.1.31770.10.1.4.2.1.12
Accumulated reactive energy in varh. For kvarh, divide by 1000.
varhBnProVarHour
Based On: SNMPv2-SMICounter64
Description:
Reactive energy counter in var-hours stored as integer varh.
Divide by 1000 for kVArh display. Example: 800 renders as 0.800 kVArh.
.1.3.6.1.4.1.31770.10.1.4.2.1.13
Input frequency
HzBnProFrequencyTenthHz
Description:
Frequency value with 0.1 Hz base resolution. Example: 500 means 50.0 Hz.
.1.3.6.1.4.1.31770.10.1.4.2.1.14
Overall status of this PDU.
BnProStatus
Type Values:
0expected
1undefined
2ok
3errorHigh
4errorLow
5warningHigh
6warningLow
7lost
8deactivated
9onAlarmIdentify
10offAlarmIdentify
11onAlarm
12offAlarm
13onWarningIdentify
14offWarningIdentify
15onWarning
16offWarning
17onIdentify
18offIdentify
19on
20off
21onChildAlarm
22offChildAlarm
23onChildWarning
24offChildWarning
25childAlarm
26childWarning
27lostChild
36updateInProgress
37updateError
38onGoingSwitch
39high
40low
41alarm
42warning
43okAlt
44disabled
45fwVersionTooNew
Description:
Common status state; values follow the BlueNetGen2 entity-status model as
emitted by the agent.
.1.3.6.1.4.1.31770.10.1.4.2.1.15
.1.3.6.1.4.1.31770.10.1.5.1 · 1 row entry · 18 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProInletMeasurementsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProInletMeasurementsTable'
Table of PDU inlets. Inlet is a peer branch; phase/outlet relations are expressed by columns in their own tables.
bnProInletEntry row .1.3.6.1.4.1.31770.10.1.5.1.1
Column Syntax OID
Label of the PDU this row belongs to: the PDU's configured name, defaulting to its hostname when unset. Identifies the owning PDU without a lookup in the device table; the PDU's numeric index remains the first INDEX sub…
SNMPv2-TCDisplayString
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.5.1.1.1
Inlet index within one PDU.
Unsigned32
Constraints:
range: 1-4294967295
.1.3.6.1.4.1.31770.10.1.5.1.1.2
Human-readable inlet name.
SNMPv2-TCDisplayString
Constraints:
range: 0-64
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.5.1.1.3
User-configurable friendly name of this inlet.
SNMPv2-TCDisplayStringr/w
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.5.1.1.4
Inlet current.
mABnProCurrentMilliAmpere
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.5.1.1.5
Maximum inlet current.
mABnProCurrentMilliAmpere
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.5.1.1.6
Neutral current.
mABnProCurrentMilliAmpere
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.5.1.1.7
Maximum neutral current.
mABnProCurrentMilliAmpere
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.5.1.1.8
Active inlet power.
WBnProWatt
Description:
Active power in watts (whole numbers). Example: 1200 means 1200 W.
.1.3.6.1.4.1.31770.10.1.5.1.1.9
Maximum active inlet power.
WBnProWatt
Description:
Active power in watts (whole numbers). Example: 1200 means 1200 W.
.1.3.6.1.4.1.31770.10.1.5.1.1.10
Apparent inlet power.
VABnProVoltAmpere
Description:
Apparent power in volt-amperes (whole numbers). Example: 1500 means 1500 VA.
.1.3.6.1.4.1.31770.10.1.5.1.1.11
Reactive inlet power.
varBnProVar
Description:
Reactive power in volt-amperes reactive (whole numbers). Example: 300 means 300 var.
.1.3.6.1.4.1.31770.10.1.5.1.1.12
Active inlet energy in Wh. For kWh, divide by 1000.
WhBnProWattHour
Based On: SNMPv2-SMICounter64
Description:
Active energy counter in watt-hours stored as integer Wh. A compliant MIB browser
divides by 1000 and appends UNITS to display e.g. 4567 renders as 4.567 kWh.
Wraps at 2^63-1 Wh.
.1.3.6.1.4.1.31770.10.1.5.1.1.13
Second active inlet energy counter in Wh. For kWh, divide by 1000.
WhBnProWattHour
Based On: SNMPv2-SMICounter64
Description:
Active energy counter in watt-hours stored as integer Wh. A compliant MIB browser
divides by 1000 and appends UNITS to display e.g. 4567 renders as 4.567 kWh.
Wraps at 2^63-1 Wh.
.1.3.6.1.4.1.31770.10.1.5.1.1.14
Apparent inlet energy in VAh. For kVAh, divide by 1000.
VAhBnProVoltAmpereHour
Based On: SNMPv2-SMICounter64
Description:
Apparent energy counter in volt-ampere-hours stored as integer VAh.
Divide by 1000 for kVAh display. Example: 2500 renders as 2.500 kVAh.
.1.3.6.1.4.1.31770.10.1.5.1.1.15
Reactive inlet energy in varh. For kvarh, divide by 1000.
varhBnProVarHour
Based On: SNMPv2-SMICounter64
Description:
Reactive energy counter in var-hours stored as integer varh.
Divide by 1000 for kVArh display. Example: 800 renders as 0.800 kVArh.
.1.3.6.1.4.1.31770.10.1.5.1.1.16
Input frequency. Example: 500 means 50.0 Hz.
HzBnProFrequencyTenthHz
Description:
Frequency value with 0.1 Hz base resolution. Example: 500 means 50.0 Hz.
.1.3.6.1.4.1.31770.10.1.5.1.1.17
Inlet status.
BnProStatus
Type Values:
0expected
1undefined
2ok
3errorHigh
4errorLow
5warningHigh
6warningLow
7lost
8deactivated
9onAlarmIdentify
10offAlarmIdentify
11onAlarm
12offAlarm
13onWarningIdentify
14offWarningIdentify
15onWarning
16offWarning
17onIdentify
18offIdentify
19on
20off
21onChildAlarm
22offChildAlarm
23onChildWarning
24offChildWarning
25childAlarm
26childWarning
27lostChild
36updateInProgress
37updateError
38onGoingSwitch
39high
40low
41alarm
42warning
43okAlt
44disabled
45fwVersionTooNew
Description:
Common status state; values follow the BlueNetGen2 entity-status model as
emitted by the agent.
.1.3.6.1.4.1.31770.10.1.5.1.1.18
.1.3.6.1.4.1.31770.10.1.5.2 · 1 row entry · 12 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProInletThresholdTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProInletThresholdTable'
Threshold table for inlet measurements. One row represents all supported threshold parameters of one inlet.
bnProInletThresholdEntry row .1.3.6.1.4.1.31770.10.1.5.2.1
Column Syntax OID
Label of the PDU this row belongs to: the PDU's configured name, defaulting to its hostname when unset. Identifies the owning PDU without a lookup in the device table; the PDU's numeric index remains the first INDEX sub…
SNMPv2-TCDisplayString
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.5.2.1.1
Index of the inlet this row belongs to, mirroring the INDEX value so the owning inlet is visible as a readable column.
Unsigned32
Constraints:
range: 1-4294967295
.1.3.6.1.4.1.31770.10.1.5.2.1.2
Low alarm threshold for inlet current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.5.2.1.3
High alarm threshold for inlet current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.5.2.1.4
Low warning threshold for inlet current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.5.2.1.5
High warning threshold for inlet current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.5.2.1.6
Hysteresis for inlet current thresholds.
%BnProHysteresisPerMiller/w
Type Constraints:
range: 0..1000
Description:
Hysteresis expressed as tenths of a percent of the threshold range.
Example: 50 means 5.0 percent hysteresis.
.1.3.6.1.4.1.31770.10.1.5.2.1.7
Low alarm threshold for inlet neutral current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.5.2.1.8
High alarm threshold for inlet neutral current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.5.2.1.9
Low warning threshold for inlet neutral current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.5.2.1.10
High warning threshold for inlet neutral current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.5.2.1.11
Hysteresis for inlet neutral current thresholds.
%BnProHysteresisPerMiller/w
Type Constraints:
range: 0..1000
Description:
Hysteresis expressed as tenths of a percent of the threshold range.
Example: 50 means 5.0 percent hysteresis.
.1.3.6.1.4.1.31770.10.1.5.2.1.12
.1.3.6.1.4.1.31770.10.1.5.3 · 1 row entry · 5 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProInletResetTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProInletResetTable'
Reset control table for inlet measurements.
bnProInletResetEntry row .1.3.6.1.4.1.31770.10.1.5.3.1
Column Syntax OID
Label of the PDU this row belongs to: the PDU's configured name, defaulting to its hostname when unset. Identifies the owning PDU without a lookup in the device table; the PDU's numeric index remains the first INDEX sub…
SNMPv2-TCDisplayString
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.5.3.1.1
Index of the inlet this row belongs to, mirroring the INDEX value so the owning inlet is visible as a readable column.
Unsigned32
Constraints:
range: 1-4294967295
.1.3.6.1.4.1.31770.10.1.5.3.1.2
Write reset(1) to clear the maximum inlet current value.
Enumerationr/w
Enumerated Values:
1reset
.1.3.6.1.4.1.31770.10.1.5.3.1.3
Write reset(1) to clear the maximum active inlet power value.
Enumerationr/w
Enumerated Values:
1reset
.1.3.6.1.4.1.31770.10.1.5.3.1.4
Write reset(1) to clear the second active inlet energy counter.
Enumerationr/w
Enumerated Values:
1reset
.1.3.6.1.4.1.31770.10.1.5.3.1.5
.1.3.6.1.4.1.31770.10.1.6.1 · 1 row entry · 18 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProPhaseMeasurementsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProPhaseMeasurementsTable'
Table of electrical phases. Phase is a peer branch, not nested below inlet.
bnProPhaseEntry row .1.3.6.1.4.1.31770.10.1.6.1.1
Column Syntax OID
Label of the PDU this row belongs to: the PDU's configured name, defaulting to its hostname when unset. Identifies the owning PDU without a lookup in the device table; the PDU's numeric index remains the first INDEX sub…
SNMPv2-TCDisplayString
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.6.1.1.1
Phase index within one PDU.
Integer32
Constraints:
range: 1-4294967295
.1.3.6.1.4.1.31770.10.1.6.1.1.2
Human-readable phase name.
SNMPv2-TCDisplayString
Constraints:
range: 0-64
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.6.1.1.3
User-configurable friendly name of this phase.
SNMPv2-TCDisplayStringr/w
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.6.1.1.4
Phase current.
mABnProCurrentMilliAmpere
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.6.1.1.5
Maximum phase current.
mABnProCurrentMilliAmpere
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.6.1.1.6
Phase voltage.
VBnProVoltageVolt
Description:
Voltage value in volts.
.1.3.6.1.4.1.31770.10.1.6.1.1.7
Phase power factor. Example: 1000 means 1.000.
BnProPowerFactorMilli
Type Constraints:
range: -1000..1000
Description:
Power factor value with 0.001 base resolution. Example: 980 means 0.980.
.1.3.6.1.4.1.31770.10.1.6.1.1.8
Power factor suffix, for example LA or LE.
SNMPv2-TCDisplayString
Constraints:
range: 0-8
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.6.1.1.9
Active phase power.
WBnProWatt
Description:
Active power in watts (whole numbers). Example: 1200 means 1200 W.
.1.3.6.1.4.1.31770.10.1.6.1.1.10
Maximum active phase power.
WBnProWatt
Description:
Active power in watts (whole numbers). Example: 1200 means 1200 W.
.1.3.6.1.4.1.31770.10.1.6.1.1.11
Apparent phase power.
VABnProVoltAmpere
Description:
Apparent power in volt-amperes (whole numbers). Example: 1500 means 1500 VA.
.1.3.6.1.4.1.31770.10.1.6.1.1.12
Reactive phase power.
varBnProVar
Description:
Reactive power in volt-amperes reactive (whole numbers). Example: 300 means 300 var.
.1.3.6.1.4.1.31770.10.1.6.1.1.13
Active phase energy in Wh. For kWh, divide by 1000.
WhBnProWattHour
Based On: SNMPv2-SMICounter64
Description:
Active energy counter in watt-hours stored as integer Wh. A compliant MIB browser
divides by 1000 and appends UNITS to display e.g. 4567 renders as 4.567 kWh.
Wraps at 2^63-1 Wh.
.1.3.6.1.4.1.31770.10.1.6.1.1.14
Second active phase energy counter in Wh. For kWh, divide by 1000.
WhBnProWattHour
Based On: SNMPv2-SMICounter64
Description:
Active energy counter in watt-hours stored as integer Wh. A compliant MIB browser
divides by 1000 and appends UNITS to display e.g. 4567 renders as 4.567 kWh.
Wraps at 2^63-1 Wh.
.1.3.6.1.4.1.31770.10.1.6.1.1.15
Apparent phase energy in VAh. For kVAh, divide by 1000.
VAhBnProVoltAmpereHour
Based On: SNMPv2-SMICounter64
Description:
Apparent energy counter in volt-ampere-hours stored as integer VAh.
Divide by 1000 for kVAh display. Example: 2500 renders as 2.500 kVAh.
.1.3.6.1.4.1.31770.10.1.6.1.1.16
Reactive phase energy in varh. For kvarh, divide by 1000.
varhBnProVarHour
Based On: SNMPv2-SMICounter64
Description:
Reactive energy counter in var-hours stored as integer varh.
Divide by 1000 for kVArh display. Example: 800 renders as 0.800 kVArh.
.1.3.6.1.4.1.31770.10.1.6.1.1.17
Phase status.
BnProStatus
Type Values:
0expected
1undefined
2ok
3errorHigh
4errorLow
5warningHigh
6warningLow
7lost
8deactivated
9onAlarmIdentify
10offAlarmIdentify
11onAlarm
12offAlarm
13onWarningIdentify
14offWarningIdentify
15onWarning
16offWarning
17onIdentify
18offIdentify
19on
20off
21onChildAlarm
22offChildAlarm
23onChildWarning
24offChildWarning
25childAlarm
26childWarning
27lostChild
36updateInProgress
37updateError
38onGoingSwitch
39high
40low
41alarm
42warning
43okAlt
44disabled
45fwVersionTooNew
Description:
Common status state; values follow the BlueNetGen2 entity-status model as
emitted by the agent.
.1.3.6.1.4.1.31770.10.1.6.1.1.18
.1.3.6.1.4.1.31770.10.1.6.2 · 1 row entry · 17 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProPhaseThresholdTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProPhaseThresholdTable'
Threshold table for phase measurements. One row represents all supported threshold parameters of one phase.
bnProPhaseThresholdEntry row .1.3.6.1.4.1.31770.10.1.6.2.1
Column Syntax OID
Label of the PDU this row belongs to: the PDU's configured name, defaulting to its hostname when unset. Identifies the owning PDU without a lookup in the device table; the PDU's numeric index remains the first INDEX sub…
SNMPv2-TCDisplayString
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.6.2.1.1
Index of the phase this row belongs to, mirroring the INDEX value so the owning phase is visible as a readable column.
Unsigned32
Constraints:
range: 1-4294967295
.1.3.6.1.4.1.31770.10.1.6.2.1.2
Low alarm threshold for phase current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.6.2.1.3
High alarm threshold for phase current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.6.2.1.4
Low warning threshold for phase current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.6.2.1.5
High warning threshold for phase current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.6.2.1.6
Hysteresis for phase current thresholds.
%BnProHysteresisPerMiller/w
Type Constraints:
range: 0..1000
Description:
Hysteresis expressed as tenths of a percent of the threshold range.
Example: 50 means 5.0 percent hysteresis.
.1.3.6.1.4.1.31770.10.1.6.2.1.7
Low alarm threshold for phase voltage.
VBnProVoltageVoltr/w
Description:
Voltage value in volts.
.1.3.6.1.4.1.31770.10.1.6.2.1.8
High alarm threshold for phase voltage.
VBnProVoltageVoltr/w
Description:
Voltage value in volts.
.1.3.6.1.4.1.31770.10.1.6.2.1.9
Low warning threshold for phase voltage.
VBnProVoltageVoltr/w
Description:
Voltage value in volts.
.1.3.6.1.4.1.31770.10.1.6.2.1.10
High warning threshold for phase voltage.
VBnProVoltageVoltr/w
Description:
Voltage value in volts.
.1.3.6.1.4.1.31770.10.1.6.2.1.11
Hysteresis for phase voltage thresholds.
%BnProHysteresisPerMiller/w
Type Constraints:
range: 0..1000
Description:
Hysteresis expressed as tenths of a percent of the threshold range.
Example: 50 means 5.0 percent hysteresis.
.1.3.6.1.4.1.31770.10.1.6.2.1.12
Low alarm threshold for phase power factor.
BnProPowerFactorMillir/w
Type Constraints:
range: -1000..1000
Description:
Power factor value with 0.001 base resolution. Example: 980 means 0.980.
.1.3.6.1.4.1.31770.10.1.6.2.1.13
High alarm threshold for phase power factor.
BnProPowerFactorMillir/w
Type Constraints:
range: -1000..1000
Description:
Power factor value with 0.001 base resolution. Example: 980 means 0.980.
.1.3.6.1.4.1.31770.10.1.6.2.1.14
Low warning threshold for phase power factor.
BnProPowerFactorMillir/w
Type Constraints:
range: -1000..1000
Description:
Power factor value with 0.001 base resolution. Example: 980 means 0.980.
.1.3.6.1.4.1.31770.10.1.6.2.1.15
High warning threshold for phase power factor.
BnProPowerFactorMillir/w
Type Constraints:
range: -1000..1000
Description:
Power factor value with 0.001 base resolution. Example: 980 means 0.980.
.1.3.6.1.4.1.31770.10.1.6.2.1.16
Hysteresis for phase power factor thresholds.
%BnProHysteresisPerMiller/w
Type Constraints:
range: 0..1000
Description:
Hysteresis expressed as tenths of a percent of the threshold range.
Example: 50 means 5.0 percent hysteresis.
.1.3.6.1.4.1.31770.10.1.6.2.1.17
.1.3.6.1.4.1.31770.10.1.6.3 · 1 row entry · 5 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProPhaseResetTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProPhaseResetTable'
Reset control table for phase measurements.
bnProPhaseResetEntry row .1.3.6.1.4.1.31770.10.1.6.3.1
Column Syntax OID
Label of the PDU this row belongs to: the PDU's configured name, defaulting to its hostname when unset. Identifies the owning PDU without a lookup in the device table; the PDU's numeric index remains the first INDEX sub…
SNMPv2-TCDisplayString
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.6.3.1.1
Index of the phase this row belongs to, mirroring the INDEX value so the owning phase is visible as a readable column.
Unsigned32
Constraints:
range: 1-4294967295
.1.3.6.1.4.1.31770.10.1.6.3.1.2
Write reset(1) to clear the maximum phase current value.
Enumerationr/w
Enumerated Values:
1reset
.1.3.6.1.4.1.31770.10.1.6.3.1.3
Write reset(1) to clear the maximum active phase power value.
Enumerationr/w
Enumerated Values:
1reset
.1.3.6.1.4.1.31770.10.1.6.3.1.4
Write reset(1) to clear the second active phase energy counter.
Enumerationr/w
Enumerated Values:
1reset
.1.3.6.1.4.1.31770.10.1.6.3.1.5
.1.3.6.1.4.1.31770.10.1.7.1 · 1 row entry · 8 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProMcbMeasurementsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProMcbMeasurementsTable'
Table of MCB/fuse monitoring entries.
bnProMcbEntry row .1.3.6.1.4.1.31770.10.1.7.1.1
Column Syntax OID
Label of the PDU this row belongs to: the PDU's configured name, defaulting to its hostname when unset. Identifies the owning PDU without a lookup in the device table; the PDU's numeric index remains the first INDEX sub…
SNMPv2-TCDisplayString
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.7.1.1.1
MCB/fuse index within one PDU.
Unsigned32
Constraints:
range: 1-4294967295
.1.3.6.1.4.1.31770.10.1.7.1.1.2
Human-readable MCB/fuse name.
SNMPv2-TCDisplayString
Constraints:
range: 0-64
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.7.1.1.3
User-configurable friendly name of this MCB/fuse.
SNMPv2-TCDisplayStringr/w
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.7.1.1.4
MCB/fuse current.
mABnProCurrentMilliAmpere
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.7.1.1.5
Maximum MCB/fuse current.
mABnProCurrentMilliAmpere
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.7.1.1.6
Write reset(1) to clear the maximum MCB/fuse current value.
Enumerationr/w
Enumerated Values:
1reset
.1.3.6.1.4.1.31770.10.1.7.1.1.7
MCB/fuse alarm state.
BnProStatus
Type Values:
0expected
1undefined
2ok
3errorHigh
4errorLow
5warningHigh
6warningLow
7lost
8deactivated
9onAlarmIdentify
10offAlarmIdentify
11onAlarm
12offAlarm
13onWarningIdentify
14offWarningIdentify
15onWarning
16offWarning
17onIdentify
18offIdentify
19on
20off
21onChildAlarm
22offChildAlarm
23onChildWarning
24offChildWarning
25childAlarm
26childWarning
27lostChild
36updateInProgress
37updateError
38onGoingSwitch
39high
40low
41alarm
42warning
43okAlt
44disabled
45fwVersionTooNew
Description:
Common status state; values follow the BlueNetGen2 entity-status model as
emitted by the agent.
.1.3.6.1.4.1.31770.10.1.7.1.1.8
.1.3.6.1.4.1.31770.10.1.7.2 · 1 row entry · 7 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProMcbThresholdTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProMcbThresholdTable'
Threshold table for MCB measurements. One row represents all supported threshold parameters of one MCB.
bnProMcbThresholdEntry row .1.3.6.1.4.1.31770.10.1.7.2.1
Column Syntax OID
Label of the PDU this row belongs to: the PDU's configured name, defaulting to its hostname when unset. Identifies the owning PDU without a lookup in the device table; the PDU's numeric index remains the first INDEX sub…
SNMPv2-TCDisplayString
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.7.2.1.1
Index of the MCB this row belongs to, mirroring the INDEX value so the owning MCB is visible as a readable column.
Unsigned32
Constraints:
range: 1-4294967295
.1.3.6.1.4.1.31770.10.1.7.2.1.2
Low alarm threshold for MCB current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.7.2.1.3
High alarm threshold for MCB current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.7.2.1.4
Low warning threshold for MCB current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.7.2.1.5
High warning threshold for MCB current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.7.2.1.6
Hysteresis applied to the MCB current alarm and warning thresholds.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.7.2.1.7
.1.3.6.1.4.1.31770.10.1.8.1 · 1 row entry · 20 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProOutletMeasurementsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProOutletMeasurementsTable'
Table of outlets. Outlet is a peer branch, not nested below phase.
bnProOutletEntry row .1.3.6.1.4.1.31770.10.1.8.1.1
Column Syntax OID
Label of the PDU this row belongs to: the PDU's configured name, defaulting to its hostname when unset. Identifies the owning PDU without a lookup in the device table; the PDU's numeric index remains the first INDEX sub…
SNMPv2-TCDisplayString
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.8.1.1.1
Outlet index within one PDU.
Unsigned32
Constraints:
range: 1-4294967295
.1.3.6.1.4.1.31770.10.1.8.1.1.2
Human-readable outlet name.
SNMPv2-TCDisplayString
Constraints:
range: 0-64
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.8.1.1.3
User-configurable friendly name of this outlet.
SNMPv2-TCDisplayStringr/w
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.8.1.1.4
Outlet mode.
BnProOutletMode
Type Values:
0unknown
1off
2on
3unsupported
Description:
Outlet runtime mode.
.1.3.6.1.4.1.31770.10.1.8.1.1.5
Outlet current.
mABnProCurrentMilliAmpere
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.8.1.1.6
Maximum outlet current.
mABnProCurrentMilliAmpere
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.8.1.1.7
Outlet voltage.
VBnProVoltageVolt
Description:
Voltage value in volts.
.1.3.6.1.4.1.31770.10.1.8.1.1.8
Outlet power factor. Example: 1000 means 1.000.
BnProPowerFactorMilli
Type Constraints:
range: -1000..1000
Description:
Power factor value with 0.001 base resolution. Example: 980 means 0.980.
.1.3.6.1.4.1.31770.10.1.8.1.1.9
Power factor suffix, for example LA or LE.
SNMPv2-TCDisplayString
Constraints:
range: 0-8
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.8.1.1.10
Active outlet power.
WBnProWatt
Description:
Active power in watts (whole numbers). Example: 1200 means 1200 W.
.1.3.6.1.4.1.31770.10.1.8.1.1.11
Maximum active outlet power.
WBnProWatt
Description:
Active power in watts (whole numbers). Example: 1200 means 1200 W.
.1.3.6.1.4.1.31770.10.1.8.1.1.12
Apparent outlet power.
VABnProVoltAmpere
Description:
Apparent power in volt-amperes (whole numbers). Example: 1500 means 1500 VA.
.1.3.6.1.4.1.31770.10.1.8.1.1.13
Reactive outlet power.
varBnProVar
Description:
Reactive power in volt-amperes reactive (whole numbers). Example: 300 means 300 var.
.1.3.6.1.4.1.31770.10.1.8.1.1.14
Active outlet energy in Wh. For kWh, divide by 1000.
WhBnProWattHour
Based On: SNMPv2-SMICounter64
Description:
Active energy counter in watt-hours stored as integer Wh. A compliant MIB browser
divides by 1000 and appends UNITS to display e.g. 4567 renders as 4.567 kWh.
Wraps at 2^63-1 Wh.
.1.3.6.1.4.1.31770.10.1.8.1.1.15
Second active outlet energy counter in Wh. For kWh, divide by 1000.
WhBnProWattHour
Based On: SNMPv2-SMICounter64
Description:
Active energy counter in watt-hours stored as integer Wh. A compliant MIB browser
divides by 1000 and appends UNITS to display e.g. 4567 renders as 4.567 kWh.
Wraps at 2^63-1 Wh.
.1.3.6.1.4.1.31770.10.1.8.1.1.16
Apparent outlet energy in VAh. For kVAh, divide by 1000.
VAhBnProVoltAmpereHour
Based On: SNMPv2-SMICounter64
Description:
Apparent energy counter in volt-ampere-hours stored as integer VAh.
Divide by 1000 for kVAh display. Example: 2500 renders as 2.500 kVAh.
.1.3.6.1.4.1.31770.10.1.8.1.1.17
Reactive outlet energy in varh. For kvarh, divide by 1000.
varhBnProVarHour
Based On: SNMPv2-SMICounter64
Description:
Reactive energy counter in var-hours stored as integer varh.
Divide by 1000 for kVArh display. Example: 800 renders as 0.800 kVArh.
.1.3.6.1.4.1.31770.10.1.8.1.1.18
Outlet status.
BnProStatus
Type Values:
0expected
1undefined
2ok
3errorHigh
4errorLow
5warningHigh
6warningLow
7lost
8deactivated
9onAlarmIdentify
10offAlarmIdentify
11onAlarm
12offAlarm
13onWarningIdentify
14offWarningIdentify
15onWarning
16offWarning
17onIdentify
18offIdentify
19on
20off
21onChildAlarm
22offChildAlarm
23onChildWarning
24offChildWarning
25childAlarm
26childWarning
27lostChild
36updateInProgress
37updateError
38onGoingSwitch
39high
40low
41alarm
42warning
43okAlt
44disabled
45fwVersionTooNew
Description:
Common status state; values follow the BlueNetGen2 entity-status model as
emitted by the agent.
.1.3.6.1.4.1.31770.10.1.8.1.1.19
Indicates whether identify control (off/on) is supported for this outlet.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.31770.10.1.8.1.1.20
.1.3.6.1.4.1.31770.10.1.8.2 · 1 row entry · 12 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProOutletThresholdTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProOutletThresholdTable'
Threshold table for outlet measurements. One row represents all supported threshold parameters of one outlet.
bnProOutletThresholdEntry row .1.3.6.1.4.1.31770.10.1.8.2.1
Column Syntax OID
Label of the PDU this row belongs to: the PDU's configured name, defaulting to its hostname when unset. Identifies the owning PDU without a lookup in the device table; the PDU's numeric index remains the first INDEX sub…
SNMPv2-TCDisplayString
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.8.2.1.1
Index of the outlet this row belongs to, mirroring the INDEX value so the owning outlet is visible as a readable column.
Unsigned32
Constraints:
range: 1-4294967295
.1.3.6.1.4.1.31770.10.1.8.2.1.2
Low alarm threshold for outlet current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.8.2.1.3
High alarm threshold for outlet current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.8.2.1.4
Low warning threshold for outlet current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.8.2.1.5
High warning threshold for outlet current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.8.2.1.6
Hysteresis for outlet current thresholds.
%BnProHysteresisPerMiller/w
Type Constraints:
range: 0..1000
Description:
Hysteresis expressed as tenths of a percent of the threshold range.
Example: 50 means 5.0 percent hysteresis.
.1.3.6.1.4.1.31770.10.1.8.2.1.7
Low alarm threshold for outlet power factor.
BnProPowerFactorMillir/w
Type Constraints:
range: -1000..1000
Description:
Power factor value with 0.001 base resolution. Example: 980 means 0.980.
.1.3.6.1.4.1.31770.10.1.8.2.1.8
High alarm threshold for outlet power factor.
BnProPowerFactorMillir/w
Type Constraints:
range: -1000..1000
Description:
Power factor value with 0.001 base resolution. Example: 980 means 0.980.
.1.3.6.1.4.1.31770.10.1.8.2.1.9
Low warning threshold for outlet power factor.
BnProPowerFactorMillir/w
Type Constraints:
range: -1000..1000
Description:
Power factor value with 0.001 base resolution. Example: 980 means 0.980.
.1.3.6.1.4.1.31770.10.1.8.2.1.10
High warning threshold for outlet power factor.
BnProPowerFactorMillir/w
Type Constraints:
range: -1000..1000
Description:
Power factor value with 0.001 base resolution. Example: 980 means 0.980.
.1.3.6.1.4.1.31770.10.1.8.2.1.11
Hysteresis for outlet power factor thresholds.
%BnProHysteresisPerMiller/w
Type Constraints:
range: 0..1000
Description:
Hysteresis expressed as tenths of a percent of the threshold range.
Example: 50 means 5.0 percent hysteresis.
.1.3.6.1.4.1.31770.10.1.8.2.1.12
.1.3.6.1.4.1.31770.10.1.8.3 · 1 row entry · 5 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProOutletControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProOutletControlTable'
Control table for outlet switching commands. One row represents the writable control command settings of one outlet.
bnProOutletControlEntry row .1.3.6.1.4.1.31770.10.1.8.3.1
Column Syntax OID
Label of the PDU this row belongs to: the PDU's configured name, defaulting to its hostname when unset. Identifies the owning PDU without a lookup in the device table; the PDU's numeric index remains the first INDEX sub…
SNMPv2-TCDisplayString
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.8.3.1.1
Index of the outlet this row belongs to, mirroring the INDEX value so the owning outlet is visible as a readable column.
Unsigned32
Constraints:
range: 1-4294967295
.1.3.6.1.4.1.31770.10.1.8.3.1.2
Requested control action for the outlet. Use powerCycle together with bnProOutletPowerCycleTime. If bnProOutletMode is unsupported, control actions are not supported for this outlet.
BnProOutletControlActionr/w
Type Values:
0unknown
1off
2on
3powerCycle
Description:
Requested outlet or outlet-group control action.
.1.3.6.1.4.1.31770.10.1.8.3.1.3
Power-cycle duration for the outlet in seconds. Value 0 means immediate off/on without extra delay. Used only when bnProOutletControlAction is powerCycle and bnProOutletMode is not unsupported.
secondsBnProSecondsr/w
Description:
Duration in whole seconds. Example: 10 means 10 seconds.
.1.3.6.1.4.1.31770.10.1.8.3.1.4
Requested identify command for the outlet. Valid only when bnProOutletIdentifySupported is true. Use on to enable the identification indication and off to disable it.
BnProOutletIdentifyCommandr/w
Type Values:
1off
2on
Description:
Requested identify command for an outlet or outlet group.
.1.3.6.1.4.1.31770.10.1.8.3.1.5
.1.3.6.1.4.1.31770.10.1.8.4 · 1 row entry · 5 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProOutletResetTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProOutletResetTable'
Reset control table for outlet measurements.
bnProOutletResetEntry row .1.3.6.1.4.1.31770.10.1.8.4.1
Column Syntax OID
Label of the PDU this row belongs to: the PDU's configured name, defaulting to its hostname when unset. Identifies the owning PDU without a lookup in the device table; the PDU's numeric index remains the first INDEX sub…
SNMPv2-TCDisplayString
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.8.4.1.1
Index of the outlet this row belongs to, mirroring the INDEX value so the owning outlet is visible as a readable column.
Unsigned32
Constraints:
range: 1-4294967295
.1.3.6.1.4.1.31770.10.1.8.4.1.2
Write reset(1) to clear the maximum outlet current value.
Enumerationr/w
Enumerated Values:
1reset
.1.3.6.1.4.1.31770.10.1.8.4.1.3
Write reset(1) to clear the maximum active outlet power value.
Enumerationr/w
Enumerated Values:
1reset
.1.3.6.1.4.1.31770.10.1.8.4.1.4
Write reset(1) to clear the second active outlet energy counter.
Enumerationr/w
Enumerated Values:
1reset
.1.3.6.1.4.1.31770.10.1.8.4.1.5
.1.3.6.1.4.1.31770.10.1.9.1 · 1 row entry · 9 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProRcmMeasurementsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProRcmMeasurementsTable'
Table of residual current monitoring entries. RCM is a peer branch.
bnProRcmEntry row .1.3.6.1.4.1.31770.10.1.9.1.1
Column Syntax OID
Label of the PDU this row belongs to: the PDU's configured name, defaulting to its hostname when unset. Identifies the owning PDU without a lookup in the device table; the PDU's numeric index remains the first INDEX sub…
SNMPv2-TCDisplayString
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.9.1.1.1
RCM index within one PDU.
Unsigned32
Constraints:
range: 1-4294967295
.1.3.6.1.4.1.31770.10.1.9.1.1.2
Human-readable RCM name.
SNMPv2-TCDisplayString
Constraints:
range: 0-64
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.9.1.1.3
User-configurable friendly name of this RCM entry.
SNMPv2-TCDisplayStringr/w
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.9.1.1.4
AC residual current.
mABnProCurrentMilliAmpere
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.9.1.1.5
Maximum AC residual current.
mABnProCurrentMilliAmpere
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.9.1.1.6
DC residual current.
mABnProCurrentMilliAmpere
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.9.1.1.7
Maximum DC residual current.
mABnProCurrentMilliAmpere
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.9.1.1.8
RCM status.
BnProStatus
Type Values:
0expected
1undefined
2ok
3errorHigh
4errorLow
5warningHigh
6warningLow
7lost
8deactivated
9onAlarmIdentify
10offAlarmIdentify
11onAlarm
12offAlarm
13onWarningIdentify
14offWarningIdentify
15onWarning
16offWarning
17onIdentify
18offIdentify
19on
20off
21onChildAlarm
22offChildAlarm
23onChildWarning
24offChildWarning
25childAlarm
26childWarning
27lostChild
36updateInProgress
37updateError
38onGoingSwitch
39high
40low
41alarm
42warning
43okAlt
44disabled
45fwVersionTooNew
Description:
Common status state; values follow the BlueNetGen2 entity-status model as
emitted by the agent.
.1.3.6.1.4.1.31770.10.1.9.1.1.9
.1.3.6.1.4.1.31770.10.1.9.2 · 1 row entry · 12 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProRcmThresholdTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProRcmThresholdTable'
Threshold table for residual current monitoring. One row represents all supported threshold parameters of one RCM.
bnProRcmThresholdEntry row .1.3.6.1.4.1.31770.10.1.9.2.1
Column Syntax OID
Label of the PDU this row belongs to: the PDU's configured name, defaulting to its hostname when unset. Identifies the owning PDU without a lookup in the device table; the PDU's numeric index remains the first INDEX sub…
SNMPv2-TCDisplayString
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.9.2.1.1
Index of the RCM this row belongs to, mirroring the INDEX value so the owning RCM is visible as a readable column.
Unsigned32
Constraints:
range: 1-4294967295
.1.3.6.1.4.1.31770.10.1.9.2.1.2
Low alarm threshold for RCM AC residual current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.9.2.1.3
High alarm threshold for RCM AC residual current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.9.2.1.4
Low warning threshold for RCM AC residual current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.9.2.1.5
High warning threshold for RCM AC residual current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.9.2.1.6
Hysteresis for RCM AC residual current thresholds.
%BnProHysteresisPerMiller/w
Type Constraints:
range: 0..1000
Description:
Hysteresis expressed as tenths of a percent of the threshold range.
Example: 50 means 5.0 percent hysteresis.
.1.3.6.1.4.1.31770.10.1.9.2.1.7
Low alarm threshold for RCM DC residual current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.9.2.1.8
High alarm threshold for RCM DC residual current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.9.2.1.9
Low warning threshold for RCM DC residual current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.9.2.1.10
High warning threshold for RCM DC residual current.
mABnProCurrentMilliAmperer/w
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.9.2.1.11
Hysteresis for RCM DC residual current thresholds.
%BnProHysteresisPerMiller/w
Type Constraints:
range: 0..1000
Description:
Hysteresis expressed as tenths of a percent of the threshold range.
Example: 50 means 5.0 percent hysteresis.
.1.3.6.1.4.1.31770.10.1.9.2.1.12
.1.3.6.1.4.1.31770.10.1.9.3 · 1 row entry · 8 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProRcmSelfTestTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProRcmSelfTestTable'
Per-RCM self-test control and last-result table.
bnProRcmSelfTestEntry row .1.3.6.1.4.1.31770.10.1.9.3.1
Self-test entry for a single RCM.
Column Syntax OID
Label of the PDU this row belongs to: the PDU's configured name, defaulting to its hostname when unset. Identifies the owning PDU without a lookup in the device table; the PDU's numeric index remains the first INDEX sub…
SNMPv2-TCDisplayString
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.9.3.1.1
Index of the RCM this row belongs to, mirroring the INDEX value so the owning RCM is visible as a readable column.
Unsigned32
Constraints:
range: 1-4294967295
.1.3.6.1.4.1.31770.10.1.9.3.1.2
Write to trigger an RCM self-test. The value selects which notifications
the self-test emits.
BnProRcmSelfTestCommandr/w
Type Values:
0selfTestWithoutAnyNotification
1selfTestWithAlarmNotifyOnly
2selfTestWithSelfTestNotifyOnly
3selfTestWithAlarmAndSelfTestNotify
4selfTestCommand
Description:
RCM self-test command, optionally selecting which notifications the
self-test emits. Writing triggers a self-test for the addressed RCM.
.1.3.6.1.4.1.31770.10.1.9.3.1.3
Overall result of the most recent RCM self-test.
BnProRcmSelfTestResult
Type Values:
0notRun
1notReachable
2success
3failure
4partialSuccess
5cancelled
255notApplicable
Description:
Result of the most recent RCM self-test.
.1.3.6.1.4.1.31770.10.1.9.3.1.4
AC-path result of the most recent RCM self-test.
BnProRcmSelfTestResult
Type Values:
0notRun
1notReachable
2success
3failure
4partialSuccess
5cancelled
255notApplicable
Description:
Result of the most recent RCM self-test.
.1.3.6.1.4.1.31770.10.1.9.3.1.5
DC-path result of the most recent RCM self-test.
BnProRcmSelfTestResult
Type Values:
0notRun
1notReachable
2success
3failure
4partialSuccess
5cancelled
255notApplicable
Description:
Result of the most recent RCM self-test.
.1.3.6.1.4.1.31770.10.1.9.3.1.6
Timestamp of the most recent RCM self-test.
SNMPv2-TCDateAndTime
Type Constraints:
range: 8
range: 11
Description:
A date-time specification.

field octets contents range
----- ------ -------- -----
1 1-2 year* 0..65536
2 3 month …
.1.3.6.1.4.1.31770.10.1.9.3.1.7
Human-readable result of the most recent RCM self-test.
SNMPv2-TCDisplayString
Constraints:
range: 0-255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.9.3.1.8
.1.3.6.1.4.1.31770.10.1.10.1 · 1 row entry · 5 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProSpdTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProSpdTable'
Table of surge protection device entries.
bnProSpdEntry row .1.3.6.1.4.1.31770.10.1.10.1.1
Column Syntax OID
Label of the PDU this row belongs to: the PDU's configured name, defaulting to its hostname when unset. Identifies the owning PDU without a lookup in the device table; the PDU's numeric index remains the first INDEX sub…
SNMPv2-TCDisplayString
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.10.1.1.1
SPD index within one PDU.
Unsigned32
Constraints:
range: 1-4294967295
.1.3.6.1.4.1.31770.10.1.10.1.1.2
Human-readable SPD name.
SNMPv2-TCDisplayString
Constraints:
range: 0-64
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.10.1.1.3
User-configurable friendly name of this SPD entry.
SNMPv2-TCDisplayStringr/w
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.10.1.1.4
SPD status.
BnProStatus
Type Values:
0expected
1undefined
2ok
3errorHigh
4errorLow
5warningHigh
6warningLow
7lost
8deactivated
9onAlarmIdentify
10offAlarmIdentify
11onAlarm
12offAlarm
13onWarningIdentify
14offWarningIdentify
15onWarning
16offWarning
17onIdentify
18offIdentify
19on
20off
21onChildAlarm
22offChildAlarm
23onChildWarning
24offChildWarning
25childAlarm
26childWarning
27lostChild
36updateInProgress
37updateError
38onGoingSwitch
39high
40low
41alarm
42warning
43okAlt
44disabled
45fwVersionTooNew
Description:
Common status state; values follow the BlueNetGen2 entity-status model as
emitted by the agent.
.1.3.6.1.4.1.31770.10.1.10.1.1.5
.1.3.6.1.4.1.31770.10.1.11.1 · 1 row entry · 7 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProExternalSensorMeasurementsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProExternalSensorMeasurementsTable'
Table of external sensors such as temperature and humidity sensors.
bnProExternalSensorEntry row .1.3.6.1.4.1.31770.10.1.11.1.1
Column Syntax OID
Label of the PDU this row belongs to: the PDU's configured name, defaulting to its hostname when unset. Identifies the owning PDU without a lookup in the device table; the PDU's numeric index remains the first INDEX sub…
SNMPv2-TCDisplayString
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.11.1.1.1
External sensor index within one PDU.
Unsigned32
Constraints:
range: 1-4294967295
.1.3.6.1.4.1.31770.10.1.11.1.1.2
Human-readable external sensor name.
SNMPv2-TCDisplayString
Constraints:
range: 0-64
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.11.1.1.3
User-configurable friendly name of this external sensor.
SNMPv2-TCDisplayStringr/w
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.11.1.1.4
Temperature value. Example: 235 means 23.5 degrees Celsius.
°CBnProTemperatureTenthCelsius
Description:
Temperature value with 0.1 degree Celsius base resolution. Example: 235 means 23.5 degrees Celsius.
.1.3.6.1.4.1.31770.10.1.11.1.1.5
Relative humidity. Example: 455 means 45.5 percent.
%BnProPercentTenth
Description:
Percent value with 0.1 percent base resolution. Example: 455 means 45.5 percent.
.1.3.6.1.4.1.31770.10.1.11.1.1.6
External sensor status.
BnProStatus
Type Values:
0expected
1undefined
2ok
3errorHigh
4errorLow
5warningHigh
6warningLow
7lost
8deactivated
9onAlarmIdentify
10offAlarmIdentify
11onAlarm
12offAlarm
13onWarningIdentify
14offWarningIdentify
15onWarning
16offWarning
17onIdentify
18offIdentify
19on
20off
21onChildAlarm
22offChildAlarm
23onChildWarning
24offChildWarning
25childAlarm
26childWarning
27lostChild
36updateInProgress
37updateError
38onGoingSwitch
39high
40low
41alarm
42warning
43okAlt
44disabled
45fwVersionTooNew
Description:
Common status state; values follow the BlueNetGen2 entity-status model as
emitted by the agent.
.1.3.6.1.4.1.31770.10.1.11.1.1.7
.1.3.6.1.4.1.31770.10.1.11.2 · 1 row entry · 3 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProExternalSensorThresholdTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProExternalSensorThresholdTable'
Threshold table for external sensor temperature offset. One row represents the temperature offset setting of one external sensor.
bnProExternalSensorThresholdEntry row .1.3.6.1.4.1.31770.10.1.11.2.1
Column Syntax OID
Label of the PDU this row belongs to: the PDU's configured name, defaulting to its hostname when unset. Identifies the owning PDU without a lookup in the device table; the PDU's numeric index remains the first INDEX sub…
SNMPv2-TCDisplayString
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.11.2.1.1
Index of the external sensor this row belongs to, mirroring the INDEX value so the owning external sensor is visible as a readable column.
Unsigned32
Constraints:
range: 1-4294967295
.1.3.6.1.4.1.31770.10.1.11.2.1.2
Temperature offset applied to the external sensor reading.
0.1 degree CelsiusBnProTemperatureTenthCelsiusr/w
Description:
Temperature value with 0.1 degree Celsius base resolution. Example: 235 means 23.5 degrees Celsius.
.1.3.6.1.4.1.31770.10.1.11.2.1.3
.1.3.6.1.4.1.31770.10.1.12.1 · 1 row entry · 7 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProGpioTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProGpioTable'
Table of GPIO entries.
bnProGpioEntry row .1.3.6.1.4.1.31770.10.1.12.1.1
Column Syntax OID
Label of the PDU this row belongs to: the PDU's configured name, defaulting to its hostname when unset. Identifies the owning PDU without a lookup in the device table; the PDU's numeric index remains the first INDEX sub…
SNMPv2-TCDisplayString
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.12.1.1.1
GPIO index within one PDU.
Unsigned32
Constraints:
range: 1-4294967295
.1.3.6.1.4.1.31770.10.1.12.1.1.2
Human-readable GPIO name.
SNMPv2-TCDisplayString
Constraints:
range: 0-64
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.12.1.1.3
User-configurable friendly name of this GPIO.
SNMPv2-TCDisplayStringr/w
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.12.1.1.4
GPIO mode.
BnProGpioMode
Type Values:
0unknown
1input
2output
3inout
Description:
GPIO direction and capability mode.
.1.3.6.1.4.1.31770.10.1.12.1.1.5
GPIO output switch command. Valid for output-capable GPIOs.
BnProGpioSwitchStater/w
Type Values:
0unknown
1off
2on
Description:
GPIO output switch command state.
.1.3.6.1.4.1.31770.10.1.12.1.1.6
GPIO runtime status.
BnProGpioStatus
Type Values:
0unknown
1off
2on
3low
4high
Description:
GPIO runtime state.
.1.3.6.1.4.1.31770.10.1.12.1.1.7
.1.3.6.1.4.1.31770.10.1.13.1 · 1 row entry · 15 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProOutletGroupMeasurementsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProOutletGroupMeasurementsTable'
Table of outlet-group status and measurements.
bnProOutletGroupEntry row .1.3.6.1.4.1.31770.10.1.13.1.1
Column Syntax OID
Label of the PDU this row belongs to: the PDU's configured name, defaulting to its hostname when unset. Identifies the owning PDU without a lookup in the device table; the PDU's numeric index remains the first INDEX sub…
SNMPv2-TCDisplayString
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.13.1.1.1
Outlet group index within one PDU.
Unsigned32
Constraints:
range: 1-4294967295
.1.3.6.1.4.1.31770.10.1.13.1.1.2
Human-readable outlet group name.
SNMPv2-TCDisplayString
Constraints:
range: 0-64
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.13.1.1.3
User-configurable friendly name of this outlet group.
SNMPv2-TCDisplayStringr/w
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.13.1.1.4
Requested or configured control state for the outlet group.
BnProOutletGroupControlState
Type Values:
0unknown
1off
2on
3restart
4unsupported
Description:
Requested or configured control state for an outlet group.
.1.3.6.1.4.1.31770.10.1.13.1.1.5
Effective aggregated runtime state of the outlet group. Returns unsupported if outlet-group switching is not supported.
BnProOutletGroupEffectiveState
Type Values:
0unknown
1off
2on
3mixed
4unsupported
Description:
Effective aggregated runtime state of an outlet group.
.1.3.6.1.4.1.31770.10.1.13.1.1.6
Number of outlets in this outlet group.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.31770.10.1.13.1.1.7
Outlet-group current.
mABnProCurrentMilliAmpere
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.13.1.1.8
Maximum outlet-group current.
mABnProCurrentMilliAmpere
Description:
Current value in milliampere. Example: 850 means 850 mA.
.1.3.6.1.4.1.31770.10.1.13.1.1.9
Outlet-group active power.
WBnProWatt
Description:
Active power in watts (whole numbers). Example: 1200 means 1200 W.
.1.3.6.1.4.1.31770.10.1.13.1.1.10
Maximum outlet-group active power.
WBnProWatt
Description:
Active power in watts (whole numbers). Example: 1200 means 1200 W.
.1.3.6.1.4.1.31770.10.1.13.1.1.11
Outlet-group power factor. Example: 1000 means 1.000.
BnProPowerFactorMilli
Type Constraints:
range: -1000..1000
Description:
Power factor value with 0.001 base resolution. Example: 980 means 0.980.
.1.3.6.1.4.1.31770.10.1.13.1.1.12
Outlet-group active energy in Wh. For kWh, divide by 1000.
WhBnProWattHour
Based On: SNMPv2-SMICounter64
Description:
Active energy counter in watt-hours stored as integer Wh. A compliant MIB browser
divides by 1000 and appends UNITS to display e.g. 4567 renders as 4.567 kWh.
Wraps at 2^63-1 Wh.
.1.3.6.1.4.1.31770.10.1.13.1.1.13
Outlet-group second active energy counter in Wh. For kWh, divide by 1000.
WhBnProWattHour
Based On: SNMPv2-SMICounter64
Description:
Active energy counter in watt-hours stored as integer Wh. A compliant MIB browser
divides by 1000 and appends UNITS to display e.g. 4567 renders as 4.567 kWh.
Wraps at 2^63-1 Wh.
.1.3.6.1.4.1.31770.10.1.13.1.1.14
Outlet group status.
BnProStatus
Type Values:
0expected
1undefined
2ok
3errorHigh
4errorLow
5warningHigh
6warningLow
7lost
8deactivated
9onAlarmIdentify
10offAlarmIdentify
11onAlarm
12offAlarm
13onWarningIdentify
14offWarningIdentify
15onWarning
16offWarning
17onIdentify
18offIdentify
19on
20off
21onChildAlarm
22offChildAlarm
23onChildWarning
24offChildWarning
25childAlarm
26childWarning
27lostChild
36updateInProgress
37updateError
38onGoingSwitch
39high
40low
41alarm
42warning
43okAlt
44disabled
45fwVersionTooNew
Description:
Common status state; values follow the BlueNetGen2 entity-status model as
emitted by the agent.
.1.3.6.1.4.1.31770.10.1.13.1.1.15
.1.3.6.1.4.1.31770.10.1.13.2 · 1 row entry · 5 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProOutletGroupControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProOutletGroupControlTable'
Control table for outlet-group switching commands. One row represents the writable control command settings of one outlet group.
bnProOutletGroupControlEntry row .1.3.6.1.4.1.31770.10.1.13.2.1
Column Syntax OID
Label of the PDU this row belongs to: the PDU's configured name, defaulting to its hostname when unset. Identifies the owning PDU without a lookup in the device table; the PDU's numeric index remains the first INDEX sub…
SNMPv2-TCDisplayString
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.13.2.1.1
Index of the outlet group this row belongs to, mirroring the INDEX value so the owning outlet group is visible as a readable column.
Unsigned32
Constraints:
range: 1-4294967295
.1.3.6.1.4.1.31770.10.1.13.2.1.2
Requested control action for the outlet group. Use powerCycle together with bnProOutletGroupPowerCycleTime.
BnProOutletControlActionr/w
Type Values:
0unknown
1off
2on
3powerCycle
Description:
Requested outlet or outlet-group control action.
.1.3.6.1.4.1.31770.10.1.13.2.1.3
Power-cycle duration for the outlet group in seconds. Value 0 means immediate off/on without extra delay. Used only when bnProOutletGroupControlAction is powerCycle and switching is supported.
secondsBnProSecondsr/w
Description:
Duration in whole seconds. Example: 10 means 10 seconds.
.1.3.6.1.4.1.31770.10.1.13.2.1.4
Requested identify command for the outlet group. Use on to enable the identification indication and off to disable it.
BnProOutletIdentifyCommandr/w
Type Values:
1off
2on
Description:
Requested identify command for an outlet or outlet group.
.1.3.6.1.4.1.31770.10.1.13.2.1.5
.1.3.6.1.4.1.31770.10.1.13.3 · 1 row entry · 5 columns
Uses the bachmann variant from /opt/observium/mibs/bachmann.
Command help
Walk bnProOutletGroupResetTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACHMANN-BNPRO-MIB' -M '/opt/observium/mibs/bachmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACHMANN-BNPRO-MIB::bnProOutletGroupResetTable'
Reset control table for outlet-group measurements.
bnProOutletGroupResetEntry row .1.3.6.1.4.1.31770.10.1.13.3.1
Column Syntax OID
Label of the PDU this row belongs to: the PDU's configured name, defaulting to its hostname when unset. Identifies the owning PDU without a lookup in the device table; the PDU's numeric index remains the first INDEX sub…
SNMPv2-TCDisplayString
Constraints:
range: 0-128
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31770.10.1.13.3.1.1
Index of the outlet group this row belongs to, mirroring the INDEX value so the owning outlet group is visible as a readable column.
Unsigned32
Constraints:
range: 1-4294967295
.1.3.6.1.4.1.31770.10.1.13.3.1.2
Write reset(1) to clear the maximum outlet-group current value.
Enumerationr/w
Enumerated Values:
1reset
.1.3.6.1.4.1.31770.10.1.13.3.1.3
Write reset(1) to clear the maximum outlet-group active power value.
Enumerationr/w
Enumerated Values:
1reset
.1.3.6.1.4.1.31770.10.1.13.3.1.4
Write reset(1) to clear the second outlet-group active energy counter.
Enumerationr/w
Enumerated Values:
1reset
.1.3.6.1.4.1.31770.10.1.13.3.1.5