Argus-Power-System-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
4
Rows
4
Columns
17
upsInputTable
table.1.3.6.1.4.1.7309.6.1.3.2
·
1 row entry
·
3 columns
Uses the alpha variant from
Command help
/opt/observium/mibs/alpha.
Walk upsInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Argus-Power-System-MIB' -M '/opt/observium/mibs/alpha:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Argus-Power-System-MIB::upsInputTable'
A list of input table entries. The number of entries is given by the value of upsInputNumLines.
An entry containing information applicable to a
particular input line.
particular input line.
Indexes
| Column | Syntax | OID |
|---|---|---|
| upsInputLineIndexThe input line identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.7309.6.1.3.2.1.1 |
| upsInputFrequencyThe present input frequency. | HertzInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.7309.6.1.3.2.1.2 |
| upsInputVoltageThe magnitude of the present input voltage. | 0.1 RMS VoltsInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.7309.6.1.3.2.1.3 |
upsOutputTable
table.1.3.6.1.4.1.7309.6.1.4.4
·
1 row entry
·
7 columns
Uses the alpha variant from
Command help
/opt/observium/mibs/alpha.
Walk upsOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Argus-Power-System-MIB' -M '/opt/observium/mibs/alpha:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Argus-Power-System-MIB::upsOutputTable'
A list of output table entries. The number of entries is given by the value of upsOutputNumLines.
An entry containing information applicable to a
particular output line.
particular output line.
Indexes
| Column | Syntax | OID |
|---|---|---|
| upsOutputLineIndexThe output line identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.7309.6.1.4.4.1.1 |
| upsOutputVoltageThe present output voltage. | 0.1 RMS VoltsInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.7309.6.1.4.4.1.2 |
| upsOutputCurrentThe present output current. | 0.1 RMS AmpInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.7309.6.1.4.4.1.3 |
| upsOutputPowerVAThe present output VA. | VAInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.7309.6.1.4.4.1.4 |
| upsOutputPowerWattThe present output true power. | WattsInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.7309.6.1.4.4.1.5 |
| upsPowerFactorThe present power factor. | percentInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.7309.6.1.4.4.1.6 |
| upsOutputPercentLoadThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA. | percentInteger32 Constraints: range: 0-200 | .1.3.6.1.4.1.7309.6.1.4.4.1.7 |
upsAlarmTable
table.1.3.6.1.4.1.7309.6.1.5.2
·
1 row entry
·
3 columns
Uses the alpha variant from
Command help
/opt/observium/mibs/alpha.
Walk upsAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Argus-Power-System-MIB' -M '/opt/observium/mibs/alpha:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Argus-Power-System-MIB::upsAlarmTable'
A list of alarm table entries.
An entry containing information applicable to a
particular alarm.
particular alarm.
Indexes
| Column | Syntax | OID |
|---|---|---|
| upsAlarmIdA unique identifier for an alarm condition. This value must remain constant. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.7309.6.1.5.2.1.1 |
| upsAlarmDescrA unique description of the alarm. | OctetString Constraints: range: 0-255 | .1.3.6.1.4.1.7309.6.1.5.2.1.2 |
| upsAlarmStatus1 - ON or 0 - OFF. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.7309.6.1.5.2.1.3 |
upsExtraTable
table.1.3.6.1.4.1.7309.6.1.8.2
·
1 row entry
·
4 columns
Uses the alpha variant from
Command help
/opt/observium/mibs/alpha.
Walk upsExtraTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Argus-Power-System-MIB' -M '/opt/observium/mibs/alpha:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Argus-Power-System-MIB::upsExtraTable'
A table of CXC upstem controller extra variables
An entry into the CXC upstem controller extra variable table
Indexes
| Column | Syntax | OID |
|---|---|---|
| upsExtraIndexThe index of the extra variable in the CXC upstem controller table | Integer32 Constraints: range: 0-65535 | .1.3.6.1.4.1.7309.6.1.8.2.1.1 |
| upsExtraNameThe description of the extra variable as reported by the CXC upstem controller | OctetString Constraints: range: 0-30 | .1.3.6.1.4.1.7309.6.1.8.2.1.2 |
| upsExtraIntegerValueThe integer value of the extra variable as reported by the CXC upstem controller | Integer32 Constraints: range: -1000000000-1000000000 | .1.3.6.1.4.1.7309.6.1.8.2.1.3 |
| upsExtraStringValueThe string value of the extra variable as reported by the CXC upstem controller | OctetString Constraints: range: 0-255 | .1.3.6.1.4.1.7309.6.1.8.2.1.4 |