ATEN-PE2-CFG Table View

Table-centric layout grouping table, row, and column objects.

Tables
38
Rows
38
Columns
162
.1.3.6.1.4.1.21317.1.3.2.3.1.2 · 1 row entry · 10 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk staStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::staStatusTable'
Station status table.
staStatusEntry row .1.3.6.1.4.1.21317.1.3.2.3.1.2.1
Single entry containing station status info.
Indexes
Column Syntax OID
Station ID.
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.21317.1.3.2.3.1.2.1.1
Station FW version.
If the station is not available, it returns 'station N/A'.
RFC1213-MIBDisplayString .1.3.6.1.4.1.21317.1.3.2.3.1.2.1.2
Station model name.
If the station is not available, it returns 'station N/A'
RFC1213-MIBDisplayString .1.3.6.1.4.1.21317.1.3.2.3.1.2.1.3
Outlets of the station are switchable or not.
If the station is not available, it returns value -3000000.
Enumeration
Enumerated Values:
-3000000staNotAvailable
1no
2yes
3mix
.1.3.6.1.4.1.21317.1.3.2.3.1.2.1.4
Outlets of the station are per-port reading or not.
If the station is not available, it returns value -3000000.
Enumeration
Enumerated Values:
-3000000staNotAvailable
1no
2yes
.1.3.6.1.4.1.21317.1.3.2.3.1.2.1.5
Station bank count.
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.1.2.1.6
Station outlet count.
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.1.2.1.7
Station sensor count.
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.1.2.1.8
The station supports auto-ping or not.
If the station is not available, it returns value -3000000.
Enumeration
Enumerated Values:
-3000000staNotAvailable
1no
2yes
.1.3.6.1.4.1.21317.1.3.2.3.1.2.1.9
Station inlet count.
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.1.2.1.10
.1.3.6.1.4.1.21317.1.3.2.3.1.3 · 1 row entry · 1 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk staControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::staControlTable'
Station control table.
staControlEntry row .1.3.6.1.4.1.21317.1.3.2.3.1.3.1
Single entry containing station control info.
Indexes
Column Syntax OID
Reboot the station.
If the station is not available, it returns value -3000000.
Enumerationr/w
Enumerated Values:
-3000000staNotAvailable
1no
2yes
4not-support
.1.3.6.1.4.1.21317.1.3.2.3.1.3.1.1
.1.3.6.1.4.1.21317.1.3.2.3.1.4 · 1 row entry · 3 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk rackConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::rackConfigTable'
Rack config table.
rackConfigEntry row .1.3.6.1.4.1.21317.1.3.2.3.1.4.1
Single entry containing rack config info.
Indexes
Column Syntax OID
Display or set station's rack name.
string length: 1~32
If the station is not available, it returns 'station N/A'.
NOTE: Input string as /empty to set this object to NULL.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.21317.1.3.2.3.1.4.1.1
Display or set station's rack row number.
If the station is not available, it returns value -3000000.
Integer32r/w
Constraints:
range: 1-26
.1.3.6.1.4.1.21317.1.3.2.3.1.4.1.2
Display or set station's rack column number.
If the station is not available, it returns value -3000000.
Integer32r/w
Constraints:
range: 1-26
.1.3.6.1.4.1.21317.1.3.2.3.1.4.1.3
.1.3.6.1.4.1.21317.1.3.2.3.2.1.1 · 1 row entry · 4 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk devStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::devStatusTable'
Device status table.
devStatusEntry row .1.3.6.1.4.1.21317.1.3.2.3.2.1.1.1
Single entry containing device status info.
Indexes
Column Syntax OID
Device input Current value. unit:(0.1mA)
If the station does not support this OID, we show value 0.
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.1.1.1.1
Device input Voltage value. unit:(0.1mV)
If the station does not support this OID, we show value 0.
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.1.1.1.2
Device power Capacity value. unit:(0.1mVA)
If the station does not support this OID, we show value 0.
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.1.1.1.3
Device circuit wired type
Example: 1 for 1 phase, 2 for 3 phase wye, 3 for 3 phase delta
If the station does not support this OID, we show value 0.
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.1.1.1.4
.1.3.6.1.4.1.21317.1.3.2.3.2.1.2 · 1 row entry · 10 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk devConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::devConfigTable'
Device config table.
devConfigEntry row .1.3.6.1.4.1.21317.1.3.2.3.2.1.2.1
Single entry containing device config info.
Indexes
Column Syntax OID
The name of the device.
string length: 1~39
If the station is not available, it returns 'station N/A'.
NOTE: Input string as /empty to set this object to NULL.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.21317.1.3.2.3.2.1.2.1.1
Display or set whether power on schedule or not.
If the station is not available, it returns value -3000000.
Enumerationr/w
Enumerated Values:
-3000000staNotAvailable
1no-delaytime
2delaytime
3not-support
.1.3.6.1.4.1.21317.1.3.2.3.2.1.2.1.2
This function is used to enable or disable all outlet ports to sequential reboot.
If the station is not available, it returns value -3000000.
Enumerationr/w
Enumerated Values:
-3000000staNotAvailable
1no
2yes
3not-support
.1.3.6.1.4.1.21317.1.3.2.3.2.1.2.1.3
Display or set device minimum electric current measurement threshold.
Example: range 0.0~32.0 represents 0~320.
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.1.2.1.4
Display or set device maximum electric current measurement threshold.
Example: range 0.0~32.0 represents 0~320
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station doe…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.1.2.1.5
Display or set device minimum voltage measurement threshold.
Example: range 90.0~260.0 represents 900~2600
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not…
Integer32r/w
Constraints:
range: -3000--3000
range: 900-2600
.1.3.6.1.4.1.21317.1.3.2.3.2.1.2.1.6
Display or set device maximum voltage measurement threshold.
Example: range 90.0~260.0 represents 900~2600
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not…
Integer32r/w
Constraints:
range: -3000--3000
range: 900-2600
.1.3.6.1.4.1.21317.1.3.2.3.2.1.2.1.7
Display or set device minimum power measurement threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not …
Integer32r/w
Constraints:
range: -3000--3000
range: 0-99999
.1.3.6.1.4.1.21317.1.3.2.3.2.1.2.1.8
Display or set device maximum power measurement threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not …
Integer32r/w
Constraints:
range: -3000--3000
range: 0-99999
.1.3.6.1.4.1.21317.1.3.2.3.2.1.2.1.9
Display or set device maximum power dissipation measurement threshold.
Example: range 0.0 ~ 99999.0 represents 0~999990
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the sta…
Integer32r/w
Constraints:
range: -3000--3000
range: 0-999990
.1.3.6.1.4.1.21317.1.3.2.3.2.1.2.1.10
.1.3.6.1.4.1.21317.1.3.2.3.2.1.3 · 1 row entry · 1 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk devControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::devControlTable'
Device control table.
devControlEntry row .1.3.6.1.4.1.21317.1.3.2.3.2.1.3.1
Single entry containing device control info.
Indexes
Column Syntax OID
This function is used for outlet control of device.
Set off(1) to turn off for outlet control of device.
Set on(2) to turn on for all outlet control of device.
Set reboot(3) to reboot for outlet control of device.
Get t…
Enumerationr/w
Enumerated Values:
-3000000staNotAvailable
1off
2on
3reboot
4nostatus
5not-support
.1.3.6.1.4.1.21317.1.3.2.3.2.1.3.1.1
.1.3.6.1.4.1.21317.1.3.2.3.2.1.4 · 1 row entry · 5 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk devReadingTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::devReadingTable'
Device reading table.
devReadingEntry row .1.3.6.1.4.1.21317.1.3.2.3.2.1.4.1
Single entry containing device reading info.
Indexes
Column Syntax OID
Device electric current value.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.1.4.1.1
Device voltage value.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.1.4.1.2
Device power value.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.1.4.1.3
Device power dissipation value.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.1.4.1.4
Device power factor value.
This value indicates that 100 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.1.4.1.5
.1.3.6.1.4.1.21317.1.3.2.3.2.1.5 · 1 row entry · 4 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk popConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::popConfigTable'
POP config table.
popConfigEntry row .1.3.6.1.4.1.21317.1.3.2.3.2.1.5.1
Single entry containing POP config info.
Indexes
Column Syntax OID
Display or set whether outlet POP mode is enabled or not.
If the station is not available, it returns value -3000000.
Enumerationr/w
Enumerated Values:
-3000000staNotAvailable
1no
2yes
3not-support
.1.3.6.1.4.1.21317.1.3.2.3.2.1.5.1.1
Display or set whether LIFO POP mode is enabled or not.
If the station is not available, it returns value -3000000.
Enumerationr/w
Enumerated Values:
-3000000staNotAvailable
1no
2yes
3not-support
.1.3.6.1.4.1.21317.1.3.2.3.2.1.5.1.2
Display or set whether priority POP mode is enabled or not.
If the station is not available, it returns value -3000000.
Enumerationr/w
Enumerated Values:
-3000000staNotAvailable
1no
2yes
3not-support
.1.3.6.1.4.1.21317.1.3.2.3.2.1.5.1.3
Indicate Outlets' power OFF priorities under Priority POP mode.
Outlet Separator ','
Bank Separator '#'
Assign each priority in each bank by Outlet index or zero (indicate N/A) with separators in ascendant order.
e.g. f…
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.21317.1.3.2.3.2.1.5.1.4
.1.3.6.1.4.1.21317.1.3.2.3.2.1.6 · 1 row entry · 1 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk capConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::capConfigTable'
CAP config table.
capConfigEntry row .1.3.6.1.4.1.21317.1.3.2.3.2.1.6.1
Single entry containing CAP config info.
Indexes
Column Syntax OID
Display or set whether CAP mode is enabled or not.
If the station is not available, it returns value -3000000.
Enumerationr/w
Enumerated Values:
-3000000staNotAvailable
1no
2yes
.1.3.6.1.4.1.21317.1.3.2.3.2.1.6.1.1
.1.3.6.1.4.1.21317.1.3.2.3.2.1.7 · 1 row entry · 1 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk capPriorityConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::capPriorityConfigTable'
CAP priority config table.
capPriorityConfigEntry row .1.3.6.1.4.1.21317.1.3.2.3.2.1.7.1
Single entry containing CAP priority config info.
Indexes
Column Syntax OID
Display or set the CAP Priority of outlet.
Priority 0 means this outlet does not support this OID.
If the station is not available, it returns value -3000000.
Integer32r/w
Constraints:
range: 0-99
.1.3.6.1.4.1.21317.1.3.2.3.2.1.7.1.1
.1.3.6.1.4.1.21317.1.3.2.3.2.2.1 · 1 row entry · 5 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk bankStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::bankStatusTable'
Bank status table.
bankStatusEntry row .1.3.6.1.4.1.21317.1.3.2.3.2.2.1.1
Single entry containing bank status info.
Indexes
Column Syntax OID
Bank ID.
Integer32
Constraints:
range: 1-30
.1.3.6.1.4.1.21317.1.3.2.3.2.2.1.1.1
The Bank Max Current value. unit: (0.1mA).
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.2.1.1.2
The bank attached status.
If the station is not available, it returns value -3000000.
Enumeration
Enumerated Values:
-3000000staNotAvailable
1noattached
2attached
3error
4noexisted
.1.3.6.1.4.1.21317.1.3.2.3.2.2.1.1.3
The breaker status.
If the station is not available, it returns value -3000000.
Enumeration
Enumerated Values:
-3000000staNotAvailable
1off
2on
3not-support
.1.3.6.1.4.1.21317.1.3.2.3.2.2.1.1.4
Display the phase layout of bank.
Example: range 1 ~ 3 represents Line1-LineNeutral ~ Line3-lineNeutral.
4 ~ 6 represents Line1-Line2, Line2-Line3, Line3-Line1.
If the station does not support this OID, it retur…
Enumeration
Enumerated Values:
-3000000staNotAvailable
-2000000not-support
1l1-n
2l2-n
3l3-n
4l1-l2
5l2-l3
6l3-l1
.1.3.6.1.4.1.21317.1.3.2.3.2.2.1.1.5
.1.3.6.1.4.1.21317.1.3.2.3.2.2.2 · 1 row entry · 8 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk bankConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::bankConfigTable'
Bank config table.
bankConfigEntry row .1.3.6.1.4.1.21317.1.3.2.3.2.2.2.1
Single entry containing bank config info.
Indexes
Column Syntax OID
Display or set the name of the bank.
When this model does not support the OID, we show n/a.
string length: 0~15
If the station is not available, it returns 'station N/A'.
NOTE: Input string as /empty to set this object …
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.21317.1.3.2.3.2.2.2.1.1
Display or set the bank minimum electric current measurement threshold.
Example: range 0.0 ~16.0 represents 0~160
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station d…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.2.2.1.2
Display or set the bank maximum electric current measurement threshold.
Example: range 0.0 ~16.0 represents 0~160
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station d…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.2.2.1.3
Display or set the bank minimum voltage measurement threshold.
Example: range 90.0 ~260.0 represents 900~2600
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does …
Integer32r/w
Constraints:
range: -2000000--2000000
range: -3000--3000
range: 900-2600
.1.3.6.1.4.1.21317.1.3.2.3.2.2.2.1.4
Display or set the bank maximum voltage measurement threshold.
Example: range 90.0 ~260.0 represents 900~2600
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does …
Integer32r/w
Constraints:
range: -2000000--2000000
range: -3000--3000
range: 900-2600
.1.3.6.1.4.1.21317.1.3.2.3.2.2.2.1.5
Display or set the bank minimum power measurement threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not…
Integer32r/w
Constraints:
range: -2000000--2000000
range: -3000--3000
range: 0-99999
.1.3.6.1.4.1.21317.1.3.2.3.2.2.2.1.6
Display or set the bank maximum power measurement threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not…
Integer32r/w
Constraints:
range: -2000000--2000000
range: -3000--3000
range: 0-99999
.1.3.6.1.4.1.21317.1.3.2.3.2.2.2.1.7
Display or set the bank maximum power dissipation measurement threshold.
Example: range 0.0 ~ 99999.0 represents 0~999990
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the st…
Integer32r/w
Constraints:
range: -2000000--2000000
range: -3000--3000
range: 0-999990
.1.3.6.1.4.1.21317.1.3.2.3.2.2.2.1.8
.1.3.6.1.4.1.21317.1.3.2.3.2.2.3 · 1 row entry · 1 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk bankControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::bankControlTable'
Bank control table.
bankControlEntry row .1.3.6.1.4.1.21317.1.3.2.3.2.2.3.1
Single entry containing bank control info.
Indexes
Column Syntax OID
This function is used for outlet control of bank.
Set off(1) to turn off for outlet control of bank.
Set on(2) to turn on for all outlet control of bank.
Set reboot(3) to reboot for outlet control of bank.
Get this obje…
Enumerationr/w
Enumerated Values:
-3000000staNotAvailable
1off
2on
3reboot
4nostatus
5not-support
.1.3.6.1.4.1.21317.1.3.2.3.2.2.3.1.1
.1.3.6.1.4.1.21317.1.3.2.3.2.2.4 · 1 row entry · 5 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk bankReadingTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::bankReadingTable'
Bank reading table.
bankReadingEntry row .1.3.6.1.4.1.21317.1.3.2.3.2.2.4.1
Single entry containing bank reading info.
Indexes
Column Syntax OID
Bank electric current value.
This value indicates that 10,000 times.
If this measurement value is not available, it returns value -1000000.
If the station does not support this OID, it returns value -2000000.
If the sta…
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.2.4.1.1
Bank voltage value.
This value indicates that 10,000 times.
If this measurement value is not available, it returns value -1000000.
If the station does not support this OID, it returns value -2000000.
If the station is n…
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.2.4.1.2
Bank power value.
This value indicates that 10,000 times.
If this measurement value is not available, it returns value -1000000.
If the station does not support this OID, it returns value -2000000.
If the station is not…
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.2.4.1.3
Bank power dissipation value.
This value indicates that 10,000 times.
If this measurement value is not available, it returns value -1000000.
If the station does not support this OID, it returns value -2000000.
If the st…
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.2.4.1.4
Bank power Factor value.
This value indicates that 100 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.2.4.1.5
.1.3.6.1.4.1.21317.1.3.2.3.2.3.1 · 1 row entry · 5 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk outletStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::outletStatusTable'
Outlet status table.
outletStatusEntry row .1.3.6.1.4.1.21317.1.3.2.3.2.3.1.1
Single entry containing outlet status info.
Indexes
Column Syntax OID
Outlet ID.
Integer32
Constraints:
range: 1-42
.1.3.6.1.4.1.21317.1.3.2.3.2.3.1.1.1
Outlet Max Current value. unit: (0.1mA).
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.3.1.1.2
Outlet switchable.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000.
Enumeration
Enumerated Values:
-3000000staNotAvailable
-2000000not-support
1no
2yes
.1.3.6.1.4.1.21317.1.3.2.3.2.3.1.1.3
Outlet latest auto-ping result.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000.
Enumeration
Enumerated Values:
-3000000staNotAvailable
-2000000not-support
1na
2online
3not-reachable
.1.3.6.1.4.1.21317.1.3.2.3.2.3.1.1.4
Display the phase layout of outlet.
Example: range 1 ~ 3 represents Line1-LineNeutral ~ Line3-lineNeutral.
4 ~ 6 represents Line1-Line2, Line2-Line3, Line3-Line1.
If the station does not support this OID, it retur…
Enumeration
Enumerated Values:
-3000000staNotAvailable
-2000000not-support
1l1-n
2l2-n
3l3-n
4l1-l2
5l2-l3
6l3-l1
.1.3.6.1.4.1.21317.1.3.2.3.2.3.1.1.5
.1.3.6.1.4.1.21317.1.3.2.3.2.3.2 · 1 row entry · 21 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk outletConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::outletConfigTable'
Outlet config table.
outletConfigEntry row .1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1
Single entry containing outlet config info.
Indexes
Column Syntax OID
Display or set the name of the outlet.
If the station does not support this OID, we show n/a.
string length: 0~48
If the station is not available, it returns 'station N/A'.
NOTE: Input string as /empty to set this ob…
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.1
Display or set the confirmation of the outlet.
If the station is not available, it returns value -3000000.
Enumerationr/w
Enumerated Values:
-3000000staNotAvailable
1no
2yes
3noauth
4not-support
.1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.2
Display or set the ON delay time of the outlet.
When this model does not support the OID, we show value -1.
If the station is not available, it returns value -3000000.
Integer32r/w
Constraints:
range: -1-999
.1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.3
Display or set the OFF delay time of the outlet.
When this model does not support the OID, we show value -1.
If the station is not available, it returns value -3000000.
Integer32r/w
Constraints:
range: -1-999
.1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.4
Display or set the shutdown method of the outlet.
If the station is not available, it returns value -3000000.
Enumerationr/w
Enumerated Values:
-3000000staNotAvailable
1kill-the-power
2wake-on-lan
3after-ac-back
4not-support
.1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.5
Display or set the MAC address of shutdown method.
The value is hex format with length 12.
If the station does not support this OID, it return '00-00-00-00-00-00'.
If the station is not available, it returns '00-00-00-0…
SNMPv2-TCMacAddressr/w
Type Constraints:
range: 6
Description:
Represents an 802 MAC address represented in the
`canonical' order defined by IEEE 802.1a, i.e., as if it
were transmitted least significant bit first, even though
802.5 (in contrast to other 802.x protocols) requires M…
.1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.6
Display or set whether the local access of the outlet is locked by remote or not.
If the station is not available, it returns value -3000000.
Enumerationr/w
Enumerated Values:
-3000000staNotAvailable
1unlocked
2locked
3not-support
.1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.7
Display or set the outlet minimum electric current measurement threshold.
Example: range 0.0 ~16.0 represents 0~160
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.8
Display or set the outlet maximum electric current measurement threshold.
Example: range 0.0 ~16.0 represents 0~160
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.9
Display or set the outlet minimum voltage measurement threshold.
Example: range 90.0 ~260.0 represents 900~2600
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station doe…
Integer32r/w
Constraints:
range: -2000000--2000000
range: -3000--3000
range: 900-2600
.1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.10
Display or set the outlet maximum voltage measurement threshold.
Example: range 90.0 ~260.0 represents 900~2600
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station doe…
Integer32r/w
Constraints:
range: -2000000--2000000
range: -3000--3000
range: 900-2600
.1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.11
Display or set the outlet minimum power measurement threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does n…
Integer32r/w
Constraints:
range: -2000000--2000000
range: -3000--3000
range: 0-99999
.1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.12
Display or set the outlet maximum power measurement threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does n…
Integer32r/w
Constraints:
range: -2000000--2000000
range: -3000--3000
range: 0-99999
.1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.13
Display or set the outlet maximum power dissipation measurement threshold.
Example: range 0.0 ~ 99999.0 represents 0~999990
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the …
Integer32r/w
Constraints:
range: -2000000--2000000
range: -3000--3000
range: 0-999990
.1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.14
Display or set the outlet auto-ping continuously-failed time to reset outlet.
Example: range 0 ~ 5
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available…
Integer32r/w
Constraints:
range: -2000000--2000000
range: -3000--3000
range: 0-10
.1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.15
Display or set the outlet auto-ping pinging interval in seconds.
Example: range 10 ~ 600
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it retur…
Integer32r/w
Constraints:
range: -2000000--2000000
range: -3000--3000
range: 0-60
.1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.16
Display or set the outlet auto-ping max retry times.
Example: range 0 ~ 5
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -30000…
Integer32r/w
Constraints:
range: -2000000--2000000
range: -3000--3000
range: 0-10
.1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.17
Display or set the outlet auto-ping first-ping-delay in seconds after outlet switches on.
Example: range 10 ~ 600
Empty value: -3000.
If the station does not support this OID, it returns value -2000000.
If the station i…
Integer32r/w
Constraints:
range: -2000000--2000000
range: -3000--3000
range: 0-60
.1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.18
Outlet auto-ping destination IP address.
If the station does not support this OID, it returns value '0.0.0.0'.
If the station is not available, it returns '0.0.0.0'.
RFC1155-SMIIpAddressr/w
Type Constraints:
range: 4
.1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.19
Display or set the outlet auto-ping enable state.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000.
Enumerationr/w
Enumerated Values:
-3000000staNotAvailable
-2000000not-support
1disable
2enable
.1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.20
Display or set the outlet auto-ping reboot enable state.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000.
Enumerationr/w
Enumerated Values:
-3000000staNotAvailable
-2000000not-support
1disable
2enable
.1.3.6.1.4.1.21317.1.3.2.3.2.3.2.1.21
.1.3.6.1.4.1.21317.1.3.2.3.2.3.3 · 1 row entry · 1 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk outletControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::outletControlTable'
Outlet control table.
outletControlEntry row .1.3.6.1.4.1.21317.1.3.2.3.2.3.3.1
Single entry containing outlet control info.
Indexes
Column Syntax OID
This function is used for the outlet control.
Set off(1) to turn off the outlet.
Set on(2) to turn on the outlet.
Set reboot(3) to reboot the outlet.
pending(3), fault(5), noauth(6), not-suport(7), pop(8) can't be set.
Enumerationr/w
Enumerated Values:
-3000000staNotAvailable
1off
2on
3pending
4reboot
5fault
6noauth
7not-support
8pop
.1.3.6.1.4.1.21317.1.3.2.3.2.3.3.1.1
.1.3.6.1.4.1.21317.1.3.2.3.2.3.4 · 1 row entry · 5 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk outletReadingTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::outletReadingTable'
Outlet reading table.
outletReadingEntry row .1.3.6.1.4.1.21317.1.3.2.3.2.3.4.1
Single entry containing outlet reading info.
Indexes
Column Syntax OID
Outlet electric current value.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.3.4.1.1
Outlet voltage value.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.3.4.1.2
Outlet power value.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.3.4.1.3
Outlet power dissipation value.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.3.4.1.4
Outlet Power Factor value.
This value indicates that 100 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.3.4.1.5
.1.3.6.1.4.1.21317.1.3.2.3.2.3.5 · 1 row entry · 2 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk outletAutoPingIpTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::outletAutoPingIpTable'
Outlet auto-ping table.
outletAutoPingIpEntry row .1.3.6.1.4.1.21317.1.3.2.3.2.3.5.1
Single entry containing outlet auto-ping ip info.
Indexes
Column Syntax OID
Represents the type of the corresponding instance
of outletConfigAutoPingRemoteIP object.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000.
Enumeration
Enumerated Values:
1ipv4
2ipv6
.1.3.6.1.4.1.21317.1.3.2.3.2.3.5.1.1
Outlet auto-ping destination IP address.
If the station does not support this OID, it returns value '0.0.0.0'.
If the station is not available, it returns '0.0.0.0'.
INET-ADDRESS-MIBInetAddressr/w
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21317.1.3.2.3.2.3.5.1.2
.1.3.6.1.4.1.21317.1.3.2.3.2.4.1 · 1 row entry · 2 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk lineStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::lineStatusTable'
Line status table.
lineStatusEntry row .1.3.6.1.4.1.21317.1.3.2.3.2.4.1.1
Single entry containing line status info.
Indexes
Column Syntax OID
Line ID.
Integer32
Constraints:
range: 1-3
.1.3.6.1.4.1.21317.1.3.2.3.2.4.1.1.1
The Max Line Current value. unit: (0.1mA)
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.4.1.1.2
.1.3.6.1.4.1.21317.1.3.2.3.2.4.2 · 1 row entry · 6 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk lineConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::lineConfigTable'
Line config table.
lineConfigEntry row .1.3.6.1.4.1.21317.1.3.2.3.2.4.2.1
Single entry containing line config info.
Indexes
Column Syntax OID
Display or set the line Minimum current measurement threshold.
Example: range 0.0 ~16.0 represents 0~160
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not s…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.4.2.1.1
Display or set the line Maximum electric current measurement threshold.
Example: range 0.0 ~16.0 represents 0~160
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station d…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.4.2.1.2
Display or set the line minimum voltage measurement threshold.
Example: range 90.0 ~380.0 represents 900~3800
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does …
Integer32r/w
Constraints:
range: -2000000--2000000
range: -3000--3000
range: 900-3800
.1.3.6.1.4.1.21317.1.3.2.3.2.4.2.1.3
Display or set the line maximum voltage measurement threshold.
Example: range 90.0 ~380.0 represents 900~3800
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does …
Integer32r/w
Constraints:
range: -2000000--2000000
range: -3000--3000
range: 900-3800
.1.3.6.1.4.1.21317.1.3.2.3.2.4.2.1.4
Display or set the line minimum power measurement threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not…
Integer32r/w
Constraints:
range: -2000000--2000000
range: -3000--3000
range: 0-99999
.1.3.6.1.4.1.21317.1.3.2.3.2.4.2.1.5
Display or set the line maximum power measurement threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not…
Integer32r/w
Constraints:
range: -2000000--2000000
range: -3000--3000
range: 0-99999
.1.3.6.1.4.1.21317.1.3.2.3.2.4.2.1.6
.1.3.6.1.4.1.21317.1.3.2.3.2.4.3 · 1 row entry · 3 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk lineReadingTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::lineReadingTable'
Line reading table.
lineReadingEntry row .1.3.6.1.4.1.21317.1.3.2.3.2.4.3.1
Single entry containing line reading info.
Indexes
Column Syntax OID
Line current value.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.4.3.1.1
Line voltage value.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.4.3.1.2
Line power value.
This value indicates that 10,000 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.4.3.1.3
.1.3.6.1.4.1.21317.1.3.2.3.2.4.4 · 1 row entry · 1 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk neutralStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::neutralStatusTable'
Line reading table.
neutralStatusEntry row .1.3.6.1.4.1.21317.1.3.2.3.2.4.4.1
Single entry containing line reading info.
Indexes
Column Syntax OID
Neutral leakage current status.
If the station is not available, it returns value -3000000.
Enumeration
Enumerated Values:
-3000000staNotAvailable
1no-detection
2detection
3not-support
.1.3.6.1.4.1.21317.1.3.2.3.2.4.4.1.1
.1.3.6.1.4.1.21317.1.3.2.3.2.5.1 · 1 row entry · 2 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk inletStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::inletStatusTable'
Inlet status table.
inletStatusEntry row .1.3.6.1.4.1.21317.1.3.2.3.2.5.1.1
Single entry containing inlet status info.
Indexes
Column Syntax OID
Line ID.
Integer32
Constraints:
range: 1-3
.1.3.6.1.4.1.21317.1.3.2.3.2.5.1.1.1
The Inlet Max Current value. unit: (0.1mA).
If device is phase wye, then means L1 or L2 or L3 current.
If device is phase delta, then means L1L2 or L2L3 or L3L1 current.
If the station does not support this OID, it retu…
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.5.1.1.2
.1.3.6.1.4.1.21317.1.3.2.3.2.5.2 · 1 row entry · 7 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk inletConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::inletConfigTable'
Inlet config table.
inletConfigEntry row .1.3.6.1.4.1.21317.1.3.2.3.2.5.2.1
Single entry containing inlet config info.
Indexes
Column Syntax OID
Display or set the inlet Minimum current measurement threshold.
Example: range 0.0 ~16.0 represents 0~160
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not …
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.5.2.1.1
Display or set the inlet Maximum electric current measurement threshold.
Example: range 0.0 ~16.0 represents 0~160
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station …
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.5.2.1.2
Display or set the inlet minimum voltage measurement threshold.
Example: range 90.0 ~380.0 represents 900~3800
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does…
Integer32r/w
Constraints:
range: -2000000--2000000
range: -3000--3000
range: 900-3800
.1.3.6.1.4.1.21317.1.3.2.3.2.5.2.1.3
Display or set the inlet maximum voltage measurement threshold.
Example: range 90.0 ~380.0 represents 900~3800
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does…
Integer32r/w
Constraints:
range: -2000000--2000000
range: -3000--3000
range: 900-3800
.1.3.6.1.4.1.21317.1.3.2.3.2.5.2.1.4
Display or set the inlet minimum power measurement threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does no…
Integer32r/w
Constraints:
range: -2000000--2000000
range: -3000--3000
range: 0-99999
.1.3.6.1.4.1.21317.1.3.2.3.2.5.2.1.5
Display or set the inlet maximum power measurement threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does no…
Integer32r/w
Constraints:
range: -2000000--2000000
range: -3000--3000
range: 0-99999
.1.3.6.1.4.1.21317.1.3.2.3.2.5.2.1.6
Display or set the inlet maximum power dissipation measurement threshold.
Example: range 0.0 ~ 99999.0 represents 0~999990
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the s…
Integer32r/w
Constraints:
range: -2000000--2000000
range: -3000--3000
range: 0-999990
.1.3.6.1.4.1.21317.1.3.2.3.2.5.2.1.7
.1.3.6.1.4.1.21317.1.3.2.3.2.5.3 · 1 row entry · 4 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk inletReadingTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::inletReadingTable'
Inlet reading table.
inletReadingEntry row .1.3.6.1.4.1.21317.1.3.2.3.2.5.3.1
Single entry containing inlet reading info.
Indexes
Column Syntax OID
Inlet current value.
If device is phase wye, then means L1 or L2 or L3 current.
If device is phase delta, then means L1L2 or L2L3 or L3L1 current.
This value indicates that 10,000 times.
If the station does not support …
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.5.3.1.1
Inlet voltage value.
If device is phase wye, then means L1 or L2 or L3 voltage.
If device is phase delta, then means L1L2 or L2L3 or L3L1 voltage.
This value indicates that 10,000 times.
If the station does not support …
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.5.3.1.2
Inlet power value.
If device is phase wye, then means L1 or L2 or L3 power.
If device is phase delta, then means L1L2 or L2L3 or L3L1 power.
This value indicates that 10,000 times.
If the station does not support this O…
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.5.3.1.3
Inlet power value.
If device is phase wye, then means L1 or L2 or L3 power dissipation.
If device is phase delta, then means L1L2 or L2L3 or L3L1 power dissipation.
This value indicates that 10,000 times.
If the station…
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.2.5.3.1.4
.1.3.6.1.4.1.21317.1.3.2.3.3.1.3 · 1 row entry · 8 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk sensorConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::sensorConfigTable'
Sensor config table.
Use port/addr as indexes to access sensor configurations.
sensorConfigEntry row .1.3.6.1.4.1.21317.1.3.2.3.3.1.3.1
Single entry containing sensor config info.
Column Syntax OID
Sensor Port Number.
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.21317.1.3.2.3.3.1.3.1.1
Sensor Address.
Integer32
Constraints:
range: 1-31
.1.3.6.1.4.1.21317.1.3.2.3.3.1.3.1.2
Display or set sensor minimum temperature measurement threshold.
Example: range -20.0 ~ 60.0 represents -200~600
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station doe…
Integer32r/w
Constraints:
range: -3000--3000
range: -200-600
.1.3.6.1.4.1.21317.1.3.2.3.3.1.3.1.3
Display or set sensor maximum temperature measurement threshold.
Example: range -20.0 ~ 60.0 represents -200~600
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station doe…
Integer32r/w
Constraints:
range: -3000--3000
range: -200-600
.1.3.6.1.4.1.21317.1.3.2.3.3.1.3.1.4
Display or set sensor minimum humidity measurement threshold.
Example: range 10.0 ~ 95.0 represents 100~950
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not…
Integer32r/w
Constraints:
range: -3000--3000
range: 100-950
.1.3.6.1.4.1.21317.1.3.2.3.3.1.3.1.5
Display or set sensor maximum humidity measurement threshold.
Example: range 10.0 ~ 95.0 represents 100~950
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station does not…
Integer32r/w
Constraints:
range: -3000--3000
range: 100-950
.1.3.6.1.4.1.21317.1.3.2.3.3.1.3.1.6
Display or set sensor minimum pressure measurement threshold.
Example: range -250.0 ~ 250.0 represents -2500 ~ 2500
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station …
Integer32r/w
Constraints:
range: -3000--3000
range: -2500-2500
.1.3.6.1.4.1.21317.1.3.2.3.3.1.3.1.7
Display or set sensor maximum pressure measurement threshold.
Example: range -250.0 ~ 250.0 represents -2500 ~ 2500
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the station …
Integer32r/w
Constraints:
range: -3000--3000
range: -2500-2500
.1.3.6.1.4.1.21317.1.3.2.3.3.1.3.1.8
.1.3.6.1.4.1.21317.1.3.2.3.3.1.4 · 1 row entry · 3 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk sensorReadingTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::sensorReadingTable'
Sensor reading table.
Use port/addr as indexes to access sensor readings.
sensorReadingEntry row .1.3.6.1.4.1.21317.1.3.2.3.3.1.4.1
Single entry containing sensor reading info.
Column Syntax OID
Sensor's Temperature value.
This value indicates that 1,000 times.
If this measurement value is not available, it returns value -1000000.
If the station does not support this OID, it returns value -2000000.
If the stati…
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.3.1.4.1.1
Sensor's Humidity value.
This value indicates that 1,000 times.
If this measurement value is not available, it returns value -1000000.
If the station does not support this OID, it returns value -2000000.
If the station …
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.3.1.4.1.2
Sensor's Pressure value.
This value indicates that 1,000 times.
If this measurement value is not available, it returns value -1000000.
If the station does not support this OID, it returns value -2000000.
If the station …
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.3.3.1.4.1.3
.1.3.6.1.4.1.21317.1.3.2.3.3.2.1 · 1 row entry · 2 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk dryContactStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::dryContactStatusTable'
Dry contact status table.
dryContactStatusEntry row .1.3.6.1.4.1.21317.1.3.2.3.3.2.1.1
Single entry containing dry contact status info.
Column Syntax OID
Dry contact ID.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.21317.1.3.2.3.3.2.1.1.1
Display dry contact status.
close(0) represents door close.
open(1) represents door open.
not-attached(2) represents door sensor don't attach to device.
If the station is not available, it returns value -3000000.
Enumeration
Enumerated Values:
-3000000staNotAvailable
0close
1open
2not-attached
10not-support
.1.3.6.1.4.1.21317.1.3.2.3.3.2.1.1.2
.1.3.6.1.4.1.21317.1.3.2.3.3.2.2 · 1 row entry · 1 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk dryContactConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::dryContactConfigTable'
Dry contact config table.
dryContactConfigEntry row .1.3.6.1.4.1.21317.1.3.2.3.3.2.2.1
Single entry containing dry contact config info.
Column Syntax OID
Display or set dry contact type.
If the station is not available, it returns value -3000000.
Enumerationr/w
Enumerated Values:
-3000000staNotAvailable
0notinstalled
1photo
2inductiveproximity
3reed
4waterleakage
5smoke
10not-support
.1.3.6.1.4.1.21317.1.3.2.3.3.2.2.1.1
.1.3.6.1.4.1.21317.1.3.2.3.4.1 · 1 row entry · 1 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk netStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::netStatusTable'
Net status table.
netStatusEntry row .1.3.6.1.4.1.21317.1.3.2.3.4.1.1
Single entry containing net status info.
Indexes
Column Syntax OID
Station MAC address.
The value is hex format with length 12.
If the station does not support this OID, it return '00-00-00-00-00-00'.
If the station is not available, it returns '00-00-00-00-00-00'.
SNMPv2-TCMacAddress
Type Constraints:
range: 6
Description:
Represents an 802 MAC address represented in the
`canonical' order defined by IEEE 802.1a, i.e., as if it
were transmitted least significant bit first, even though
802.5 (in contrast to other 802.x protocols) requires M…
.1.3.6.1.4.1.21317.1.3.2.3.4.1.1.1
.1.3.6.1.4.1.21317.1.3.2.3.4.2 · 1 row entry · 3 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk httpConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::httpConfigTable'
HTTP config table.
httpConfigEntry row .1.3.6.1.4.1.21317.1.3.2.3.4.2.1
Single entry containing HTTP config info.
Indexes
Column Syntax OID
Display or set the HTTP port of the station.
If the station is not available, it returns value -3000000.
Integer32r/w
Constraints:
range: 1-65535
.1.3.6.1.4.1.21317.1.3.2.3.4.2.1.1
Display or set the HTTPs port of the station.
If the station is not available, it returns value -3000000.
Integer32r/w
Constraints:
range: 1-65535
.1.3.6.1.4.1.21317.1.3.2.3.4.2.1.2
Display or set whether to use HTTPS only or HTTP/HTTPS for the web page.
If the station is not available, it returns value -3000000.
Enumerationr/w
Enumerated Values:
-3000000staNotAvailable
1no
2yes
.1.3.6.1.4.1.21317.1.3.2.3.4.2.1.3
.1.3.6.1.4.1.21317.1.3.2.3.4.3 · 1 row entry · 8 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk netConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::netConfigTable'
Net config table.
netConfigEntry row .1.3.6.1.4.1.21317.1.3.2.3.4.3.1
Single entry containing net config info.
Column Syntax OID
Network Port Number.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.21317.1.3.2.3.4.3.1.1
Display or set IPv4 address automatically or not
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.21317.1.3.2.3.4.3.1.2
Display or set fixed IPv4 address
RFC1155-SMIIpAddressr/w
Type Constraints:
range: 4
.1.3.6.1.4.1.21317.1.3.2.3.4.3.1.3
Display or set subnet mask address
RFC1155-SMIIpAddressr/w
Type Constraints:
range: 4
.1.3.6.1.4.1.21317.1.3.2.3.4.3.1.4
Display or set gateway address
RFC1155-SMIIpAddressr/w
Type Constraints:
range: 4
.1.3.6.1.4.1.21317.1.3.2.3.4.3.1.5
Display or set DNS address automatically or not
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.21317.1.3.2.3.4.3.1.6
Display or set prefer DNS address
RFC1155-SMIIpAddressr/w
Type Constraints:
range: 4
.1.3.6.1.4.1.21317.1.3.2.3.4.3.1.7
Display or set alternate DNS address
RFC1155-SMIIpAddressr/w
Type Constraints:
range: 4
.1.3.6.1.4.1.21317.1.3.2.3.4.3.1.8
.1.3.6.1.4.1.21317.1.3.2.3.5.1.1 · 1 row entry · 2 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk trapConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::trapConfigTable'
Trap config table.
trapConfigEntry row .1.3.6.1.4.1.21317.1.3.2.3.5.1.1.1
Single entry containing trap config info.
Indexes
Column Syntax OID
Display or set whether this trap entry is enabled or not.
You should set the username/auth-password/priv-password first, when choosing snmpv3.
You should set the community string first, when choosing snmpv1/v2c.
If the …
Enumerationr/w
Enumerated Values:
-3000000staNotAvailable
1no
2yes
.1.3.6.1.4.1.21317.1.3.2.3.5.1.1.1.1
Display or set SNMP trap version for sending trap.
You should set the username/auth-password/priv-password first, when choosing snmpv3.
You should set the community string first, when choosing snmpv1/v2c.
If the station…
Enumerationr/w
Enumerated Values:
-3000000staNotAvailable
1v1
2v2c
3v3
.1.3.6.1.4.1.21317.1.3.2.3.5.1.1.1.2
.1.3.6.1.4.1.21317.1.3.2.3.5.1.2 · 1 row entry · 7 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk trapReceiverConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::trapReceiverConfigTable'
SNMP agent trap setup table. If users want to use trap, 
they must set enable trap, IP and community first.
trapReceiverConfigEntry row .1.3.6.1.4.1.21317.1.3.2.3.5.1.2.1
Single entry containing trap receiver config info.
Column Syntax OID
Index of trap receiver.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.21317.1.3.2.3.5.1.2.1.1
Trap receiver IP address.
If the station does not support this OID, it returns value '0.0.0.0'.
If the station is not available, it returns '0.0.0.0'.
RFC1155-SMIIpAddressr/w
Type Constraints:
range: 4
.1.3.6.1.4.1.21317.1.3.2.3.5.1.2.1.2
NMS trap port to be used by agent to send trap.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000.
Integer32r/w
Constraints:
range: 1-65535
.1.3.6.1.4.1.21317.1.3.2.3.5.1.2.1.3
If use SNMPv1/v2c to receive trap should set this community string.
MAX string length: 20
If the station does not support this OID, it returns value 'not-support'.
If the station is not available, it returns 'station N/…
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.21317.1.3.2.3.5.1.2.1.4
If use SNMPv3 to receive trap should set this username string.
MAX string length: 20.
If the station does not support this OID, it returns value 'not-support'.
If the station is not available, it returns 'station N/A'.
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.21317.1.3.2.3.5.1.2.1.5
If use SNMPv3 to receive trap should set this auth password string.
MAX string length: 20
If the station does not support this OID, it returns value 'not-support'.
If the station is not available, it returns 'station N/…
OctetStringr/w
Constraints:
range: 8-20
.1.3.6.1.4.1.21317.1.3.2.3.5.1.2.1.6
If use SNMPv3 to receive trap should set this privacy password string.
MAX string length: 20
If the station does not support this OID, it returns value 'not-support'.
If the station is not available, it returns 'station…
OctetStringr/w
Constraints:
range: 8-20
.1.3.6.1.4.1.21317.1.3.2.3.5.1.2.1.7
.1.3.6.1.4.1.21317.1.3.2.3.5.1.3 · 1 row entry · 3 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk trapReceiverIpTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::trapReceiverIpTable'
Trap Receiver Ip table.
trapReceiverIpEntry row .1.3.6.1.4.1.21317.1.3.2.3.5.1.3.1
Single entry containing trap receiver ip info.
Column Syntax OID
Index of trap receiver.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.21317.1.3.2.3.5.1.3.1.1
Represents the type of the corresponding instance
of trapReceiverIp object.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns value -3000000.
Enumeration
Enumerated Values:
1ipv4
2ipv6
.1.3.6.1.4.1.21317.1.3.2.3.5.1.3.1.2
Outlet auto-ping destination IP address.
If the station does not support this OID, it returns value '0.0.0.0'.
If the station is not available, it returns '0.0.0.0'.
INET-ADDRESS-MIBInetAddressr/w
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21317.1.3.2.3.5.1.3.1.3
.1.3.6.1.4.1.21317.1.3.2.3.50.1 · 1 row entry · 1 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk trapNotifConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::trapNotifConfigTable'
Trap notification config table.
trapNotifConfigEntry row .1.3.6.1.4.1.21317.1.3.2.3.50.1.1
Single entry containing trap notification config info.
Indexes
Column Syntax OID
Display or set whether this trap entry is enabled or not.
You should set the username/auth-password/priv-password first, when choosing snmpv3.
You should set the community string first, when choosing snmpv1/v2c.
If the …
Enumerationr/w
Enumerated Values:
-3000000staNotAvailable
1no
2yes
.1.3.6.1.4.1.21317.1.3.2.3.50.1.1.1
.1.3.6.1.4.1.21317.1.3.2.3.50.2 · 1 row entry · 5 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk trapNotifAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE2-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE2-CFG::trapNotifAlarmTable'
Trap notification alarm table.
trapNotifAlarmEntry row .1.3.6.1.4.1.21317.1.3.2.3.50.2.1
Single entry containing trap notification alarm info.
Indexes
Column Syntax OID
Station breaker alarm status.
If the station is not available, it returns value -3000000.
Enumeration
Enumerated Values:
-3000000staNotAvailable
0normal
1alarm
.1.3.6.1.4.1.21317.1.3.2.3.50.2.1.1
Station current alarm status.
If the station is not available, it returns value -3000000.
Enumeration
Enumerated Values:
-3000000staNotAvailable
0normal
1alarm
.1.3.6.1.4.1.21317.1.3.2.3.50.2.1.2
Station voltage alarm status.
If the station is not available, it returns value -3000000.
Enumeration
Enumerated Values:
-3000000staNotAvailable
0normal
1alarm
.1.3.6.1.4.1.21317.1.3.2.3.50.2.1.3
Station power alarm status.
If the station is not available, it returns value -3000000.
Enumeration
Enumerated Values:
-3000000staNotAvailable
0normal
1alarm
.1.3.6.1.4.1.21317.1.3.2.3.50.2.1.4
Station sensor alarm status.
If the station is not available, it returns value -3000000.
Enumeration
Enumerated Values:
-3000000staNotAvailable
0normal
1alarm
.1.3.6.1.4.1.21317.1.3.2.3.50.2.1.5