wtWebioAn1AlarmClearMailSubject
Webio-ANx-MIB ·
.1.3.6.1.4.1.5040.1.2.3.3.1.5.3.1.16
Object
column
mandatory
r/w
OctetString
Subject line for alarm clear mail.
Context
- MIB
- Webio-ANx-MIB
- OID
.1.3.6.1.4.1.5040.1.2.3.3.1.5.3.1.16- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- wtWebioAn1AlarmEntry
- Table
- wtWebioAn1AlarmTable
- Siblings
- 18
Syntax
OctetString
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| wtWebioAn1AlarmTrigger mandatory Binary coded trigger condition:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Sensor 1
Bit 1: Timer
Bit 2: ColdStart
Bit 3: WarmStart | column | OctetString | .1.3.6.1.4.1.5040.1.2.3.3.1.5.3.1.1 |
| wtWebioAn1AlarmTrapText mandatory This text is sent in the trap body. | column | OctetString | .1.3.6.1.4.1.5040.1.2.3.3.1.5.3.1.10 |
| wtWebioAn1AlarmMailOptions mandatory Binary coded options:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Attach Thermo.csv Enable
Bit 1-7: unused | column | OctetString | .1.3.6.1.4.1.5040.1.2.3.3.1.5.3.1.11 |
| wtWebioAn1AlarmTcpIpAddr mandatory Name or IP address of the TCP server which accepts the trap. | column | OctetString | .1.3.6.1.4.1.5040.1.2.3.3.1.5.3.1.12 |
| wtWebioAn1AlarmTcpPort mandatory Port number of the TCP server which accepts the trap. | column | Integer32 | .1.3.6.1.4.1.5040.1.2.3.3.1.5.3.1.13 |
| wtWebioAn1AlarmTcpText mandatory This text is sent in the TCP trap body. | column | OctetString | .1.3.6.1.4.1.5040.1.2.3.3.1.5.3.1.14 |
| wtWebioAn1AlarmHysteresis mandatory Temperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.)
, in degrees with maximum 2 decimal places. | column | OctetString | .1.3.6.1.4.1.5040.1.2.3.3.1.5.3.1.15 |
| wtWebioAn1AlarmClearMailText mandatory Alarm clear mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time. | column | OctetString | .1.3.6.1.4.1.5040.1.2.3.3.1.5.3.1.17 |
| wtWebioAn1AlarmClearTrapText mandatory This text is sent in the trap body. | column | OctetString | .1.3.6.1.4.1.5040.1.2.3.3.1.5.3.1.18 |
| wtWebioAn1AlarmClearTcpText mandatory This text is sent in the TCP trap body. | column | OctetString | .1.3.6.1.4.1.5040.1.2.3.3.1.5.3.1.19 |
| wtWebioAn1AlarmMin mandatory Minimum temperature in degrees with maximum 2 decimal places. | column | OctetString | .1.3.6.1.4.1.5040.1.2.3.3.1.5.3.1.2 |
| wtWebioAn1AlarmMax mandatory Maximum temperature in degrees with maximum 2 decimal places. | column | OctetString | .1.3.6.1.4.1.5040.1.2.3.3.1.5.3.1.3 |
| wtWebioAn1AlarmInterval mandatory Send interval for alarm messages. | column | OctetString | .1.3.6.1.4.1.5040.1.2.3.3.1.5.3.1.4 |
| wtWebioAn1AlarmEnable mandatory Binary coded alarm enable:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Mail Enable
Bit 1: SNMP Trap enable
Bit 2: TCP Client enable | column | OctetString | .1.3.6.1.4.1.5040.1.2.3.3.1.5.3.1.5 |
| wtWebioAn1AlarmEMailAddr mandatory E-Mail address for sending the alarm mail to. | column | OctetString | .1.3.6.1.4.1.5040.1.2.3.3.1.5.3.1.6 |
| wtWebioAn1AlarmMailSubject mandatory Subject line for alarm mail. | column | OctetString | .1.3.6.1.4.1.5040.1.2.3.3.1.5.3.1.7 |
| wtWebioAn1AlarmMailText mandatory Alarm mail text: <T1> provides the current temperature.
<Z> provides the current time. | column | OctetString | .1.3.6.1.4.1.5040.1.2.3.3.1.5.3.1.8 |
| wtWebioAn1AlarmManagerIP mandatory Name or IP address of the SNMP Manager which accepts the trap. | column | OctetString | .1.3.6.1.4.1.5040.1.2.3.3.1.5.3.1.9 |