pduOutletSwitchControl

VERTIV-QUETZAL-MIB · .1.3.6.1.4.1.21239.6.1.99.7.1.10

Object

column deprecated r/w Enumeration
Used for manual control of the outlet. The default is none(0). When
set, it keeps this value until the operation is complete. Then the
value goes back to none(0). Outlet must be in manual mode to set,
otherwise it causes an inconsistentValue error. Can be set to one of
the following:
1 = Cancel pending action
2 = Turn outlet on without delay
3 = After delay, turn outlet on
4 = Turn outlet off without delay
5 = After delay, turn outlet off
6 = Reboot outlet without delay
7 = After delay, reboot outlet

Context

MIB
VERTIV-QUETZAL-MIB
OID
.1.3.6.1.4.1.21239.6.1.99.7.1.10
Type
column
Access
readwrite
Status
deprecated
Parent
pduOutletSwitchEntry
Table
pduOutletSwitchTable
Siblings
9

Syntax

Enumeration

Values & Constraints

Enumerated Values
0none
1cancelActions
2onNoDelay
3onDelay
4offNoDelay
5offDelay
6rebootNoDelay
7rebootDelay

Related Objects

Sibling Objects