upsStatusOperational
UPS2-MIB ·
.1.3.6.1.4.1.52.4.1.1.10.6.1.1.1
Object
column
mandatory
Integer32
This object contains 8 bits of information about the current
operational status of the UPS. The bits are encoded as
follows:
BIT 7: 1=replace battery condition
BIT 6: 1=low battery condition
BIT 5: 1=overloaded output condition
BIT 4: 1=on-battery mode of operation
BIT 3: 1=on-line mode of operation
BIT 2: 1=Smart Boost mode of operation (where applicable)
BIT 1: 1=UPS shut down due to low battery, overload,
or `sleep' mode
BIT 0: 1=run time calibration running
Note that bit 0 is the low-order bit.
Context
- MIB
- UPS2-MIB
- OID
.1.3.6.1.4.1.52.4.1.1.10.6.1.1.1- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- upsStatusEntry
- Table
- upsStatusTable
- Siblings
- 2
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsStatusFault mandatory This object contains 8 bits of information about the current
fault conditions of the UPS. The bits are encoded as
follows:
BIT 7: 1=UPS fault - internal temperatu… | column | Integer32 | .1.3.6.1.4.1.52.4.1.1.10.6.1.1.2 |
| upsStatusTemp mandatory The UPS's present internal operating temperature in degrees
Fahrenheit. The value of this object is the actual
temperature * 10 (that is, to determine the actual
temperature, div… | column | Integer32 | .1.3.6.1.4.1.52.4.1.1.10.6.1.1.3 |