upsStatusFault
UPS2-MIB ·
.1.3.6.1.4.1.52.4.1.1.10.6.1.1.2
Object
column
mandatory
Integer32
This object contains 8 bits of information about the current
fault conditions of the UPS. The bits are encoded as
follows:
BIT 7: 1=UPS fault - internal temperature has exceeded
nominal limits
BIT 6: 1=UPS fault - bypass relay (where applicable) malfunction
BIT 5: 1=UPS fault - battery charger failure
BIT 4: 1=UPS in shut down mode via `S' command
BIT 3: 1=UPS in `sleep' mode via `@ddd' command
BIT 2: 1=UPS fault - main relay malfunction
BIT 1: 1=UPS unable to transfer to on-battery operation
due to overload
BIT 0: 1=UPS's output unpowered due to low battery shut down
Note that bit 0 is the low-order bit.
Context
- MIB
- UPS2-MIB
- OID
.1.3.6.1.4.1.52.4.1.1.10.6.1.1.2- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- upsStatusEntry
- Table
- upsStatusTable
- Siblings
- 2
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsStatusOperational mandatory This object contains 8 bits of information about the current
operational status of the UPS. The bits are encoded as
follows:
BIT 7: 1=replace battery condition
BI… | column | Integer32 | .1.3.6.1.4.1.52.4.1.1.10.6.1.1.1 |
| upsStatusTemp mandatory The UPS's present internal operating temperature in degrees
Fahrenheit. The value of this object is the actual
temperature * 10 (that is, to determine the actual
temperature, div… | column | Integer32 | .1.3.6.1.4.1.52.4.1.1.10.6.1.1.3 |