upsRunTimeCalibration
UPS2-MIB ·
.1.3.6.1.4.1.52.4.1.1.10.3.1.1.5
Object
column
mandatory
r/w
Enumeration
This object may be written to initiate or terminate the test used to calibrate the returned run time value. This test will only run if battery capacity is 100%. Results of this test can be retrieved by upsEstimatedRunTimeRemaining. Valid values for writing are 1 (initiate test) and 2 (terminate test). In addition, this object may be read to determine whether the test is currently running. Valid values for reading are 3 (test is in progress) and 4 (test is not in progress).
Context
- MIB
- UPS2-MIB
- OID
.1.3.6.1.4.1.52.4.1.1.10.3.1.1.5- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- upsBatteryEntry
- Table
- upsBatteryTable
- Siblings
- 8
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | performTest |
2 | abortTest |
3 | testInProgress |
4 | testNotInProgress |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsBatteryCapacity mandatory The UPS's remaining battery capacity expressed as a percent
of the fully charged condition. The value of this object is
the actual percentage * 10 (that is, to determine the actu… | column | Integer32 | .1.3.6.1.4.1.52.4.1.1.10.3.1.1.1 |
| upsBatteryVoltage mandatory The UPS's present battery voltage. The value of this object
is the actual voltage * 100 (that is, to determine the actual
voltage, divide the value of this object by 100). | column | Integer32 | .1.3.6.1.4.1.52.4.1.1.10.3.1.1.2 |
| upsBatteryTest mandatory This object may be written to initiate testing of the UPS's
battery packs. Reading this object will always return a 0. | column | Enumeration | .1.3.6.1.4.1.52.4.1.1.10.3.1.1.3 |
| upsBatteryTestResult mandatory The result of the last battery test performed. | column | Enumeration | .1.3.6.1.4.1.52.4.1.1.10.3.1.1.4 |
| upsEstimatedRunTimeRemaining mandatory The UPS's estimated remaining run time in minutes. The UPS
may be queried when operating in the on-line, bypass, or
on-battery modes of operation. The run time estimate is
based… | column | Integer32 | .1.3.6.1.4.1.52.4.1.1.10.3.1.1.6 |
| upsTransferCause mandatory The reason for the most recent transfer to on-battery
operation. | column | Enumeration | .1.3.6.1.4.1.52.4.1.1.10.3.1.1.7 |
| upsBatteryTestTime mandatory The frequency of execution of the UPS's automatic battery
test. The test may be run immediately upon startup, upon
startup and every 7 days thereafter, upon startup and every
14 … | column | Enumeration | .1.3.6.1.4.1.52.4.1.1.10.3.1.1.8 |
| upsLowBatteryWarning mandatory The interval between activation of the UPS's low battery
alarm warnings and shutdown of the UPS. | column | Enumeration | .1.3.6.1.4.1.52.4.1.1.10.3.1.1.9 |