upsAddlFuncsStatusOperational
UPS2-MIB ·
.1.3.6.1.4.1.52.4.1.1.10.9.1.1.5
Object
column
mandatory
Integer32
This object contains 8 bits of information about the current
operational status of the UPS. The bits are encoded as
follows:
BIT 7: 1=UPS ready to power load upon return of normal line
or upon user command
BIT 6: 1=UPS ready to power load upon user command
BIT 5: 1=UPS in bypass mode as a result of manual bypass
control
BIT 4: 1=UPS is returning from bypass mode
BIT 3: 1=UPS in bypass mode as a result of UPS-Link or
key command
BIT 2: 1=UPS going to bypass mode as a result of UPS-Link
or key command
BIT 1: 1=not defined
BIT 0: 1=wakeup mode - startup test lasting < 2 sec
Note that bit 0 is the low-order bit.