upsAddlFuncsStatusOperational
UPS2-MIB ·
.1.3.6.1.4.1.52.4.1.1.10.9.1.1.5
Object
column
mandatory
Integer32
This object contains 8 bits of information about the current
operational status of the UPS. The bits are encoded as
follows:
BIT 7: 1=UPS ready to power load upon return of normal line
or upon user command
BIT 6: 1=UPS ready to power load upon user command
BIT 5: 1=UPS in bypass mode as a result of manual bypass
control
BIT 4: 1=UPS is returning from bypass mode
BIT 3: 1=UPS in bypass mode as a result of UPS-Link or
key command
BIT 2: 1=UPS going to bypass mode as a result of UPS-Link
or key command
BIT 1: 1=not defined
BIT 0: 1=wakeup mode - startup test lasting < 2 sec
Note that bit 0 is the low-order bit.
Context
- MIB
- UPS2-MIB
- OID
.1.3.6.1.4.1.52.4.1.1.10.9.1.1.5- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- upsAddlFuncsEntry
- Table
- upsAddlFuncsTable
- Siblings
- 8
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsAddlFuncsNumBatteryPacks mandatory The number of battery pack units connected to the UPS. | column | Integer32 | .1.3.6.1.4.1.52.4.1.1.10.9.1.1.1 |
| upsAddlFuncsNumBadBatteryPacks mandatory The number of bad (faulty) battery pack units connected
to the UPS. | column | Integer32 | .1.3.6.1.4.1.52.4.1.1.10.9.1.1.2 |
| upsAddlFuncsOutputCurrent mandatory The true rms load current drawn from the UPS. The value
of this object is the actual amperage * 100 (that is, to
determine the actual amperage, divide the value of this
object by… | column | Integer32 | .1.3.6.1.4.1.52.4.1.1.10.9.1.1.3 |
| upsAddlFuncsOutputApparentPower mandatory The UPS's output load represented as a percentage of full rated
load in Volt-Amps. The value of this object is the actual
percentage * 10 (that is, to determine the actual perc… | column | Integer32 | .1.3.6.1.4.1.52.4.1.1.10.9.1.1.4 |
| upsAddlFuncsStatusFault mandatory This object contains 8 bits of information about the current
fault conditions of the UPS. The bits are encoded as
follows:
BIT 7: reserved for future use
BIT 6: … | column | Integer32 | .1.3.6.1.4.1.52.4.1.1.10.9.1.1.6 |
| upsAddlFuncsConfigPassword mandatory The password that controls access to the UPS's LCD display.
A maximum of 4 characters may be entered. | column | OctetString | .1.3.6.1.4.1.52.4.1.1.10.9.1.1.7 |
| upsAddlFuncsConfigDisable mandatory This object may be written to immediately shut down the
UPS, requiring a manual reset. Reading this object will
always return a 0. | column | Enumeration | .1.3.6.1.4.1.52.4.1.1.10.9.1.1.8 |
| upsAddlFuncsConfigBypass mandatory This object may be written to cause the UPS to transfer
to or from the bypass mode. Reading this object will
always return a 0. | column | Enumeration | .1.3.6.1.4.1.52.4.1.1.10.9.1.1.9 |