upsAddlFuncsStatusFault

UPS2-MIB · .1.3.6.1.4.1.52.4.1.1.10.9.1.1.6

Object

column mandatory Integer32
This object contains 8 bits of information about the current
fault conditions of the UPS.  The bits are encoded as
follows:
              
BIT 7:  reserved for future use
BIT 6:  reserved for future use
BIT 5:  reserved for future use
BIT 4:  1=UPS fault - DC imbalance, UPS in bypass
BIT 3:  1=UPS fault - output voltage select failure, UPS
          in bypass
BIT 2:  1=UPS fault - bypass supply failure
BIT 1:  1=UPS fault - Isolation Unit fan failure
BIT 0:  1=UPS fault - Electronics Unit fan failure, UPS
          in bypass
              
Note that bit 0 is the low-order bit.

Context

MIB
UPS2-MIB
OID
.1.3.6.1.4.1.52.4.1.1.10.9.1.1.6
Type
column
Access
readonly
Status
mandatory
Parent
upsAddlFuncsEntry
Table
upsAddlFuncsTable
Siblings
8

Syntax

Integer32
Source
COPS-PR-SPPIInteger32
Base type
Integer32

Values & Constraints

Type Constraints
range: -2147483648..2147483647

Related Objects

Sibling Objects