upsShutdownType
UPS-MIB ·
.1.3.6.1.2.1.33.1.8.1
Object
scalar
r/w
Enumeration
This object determines the nature of the action to be
taken at the time when the countdown of the
upsShutdownAfterDelay and upsRebootWithDuration
objects reaches zero.
Setting this object to output(1) indicates that
shutdown requests should cause only the output of the
UPS to turn off. Setting this object to system(2)
indicates that shutdown requests will cause the entire
UPS system to turn off.
Context
- MIB
- UPS-MIB
- OID
.1.3.6.1.2.1.33.1.8.1- Type
- scalar
- Access
- readwrite
- Status
- current
- Parent
- upsControl
- Siblings
- 4
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | output |
2 | system |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsShutdownAfterDelay Setting this object will shutdown (i.e., turn off)
either the UPS output or the UPS system (as determined
by the value of upsShutdownType at the time of
shutdown) after the indica… | scalar | seconds Integer32 | .1.3.6.1.2.1.33.1.8.2 |
| upsStartupAfterDelay Setting this object will start the output after the
indicated number of seconds, including starting the
UPS, if necessary. Setting this object to 0 will
cause the startup to occu… | scalar | seconds Integer32 | .1.3.6.1.2.1.33.1.8.3 |
| upsRebootWithDuration Setting this object will immediately shutdown (i.e.,
turn off) either the UPS output or the UPS system (as
determined by the value of upsShutdownType at the time
of shutdown) for … | scalar | seconds Integer32 | .1.3.6.1.2.1.33.1.8.4 |
| upsAutoRestart Setting this object to 'on' will cause the UPS system
to restart after a shutdown if the shutdown occurred
during a power loss as a result of either a
upsShutdownAfterDelay or an … | scalar | Enumeration | .1.3.6.1.2.1.33.1.8.5 |