upsShutdownAfterDelay
UPS-MIB ·
.1.3.6.1.2.1.33.1.8.2
Object
scalar
r/w
seconds Integer32
Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of seconds, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.
Context
- MIB
- UPS-MIB
- OID
.1.3.6.1.2.1.33.1.8.2- Type
- scalar
- Access
- readwrite
- Status
- current
- Units
- seconds
- Parent
- upsControl
- Siblings
- 4
Syntax
seconds Integer32
Values & Constraints
Object Constraints
range: -1-2147483648
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsShutdownType This object determines the nature of the action to be
taken at the time when the countdown of the
upsShutdownAfterDelay and upsRebootWithDuration
objects reaches zero.
… | scalar | Enumeration | .1.3.6.1.2.1.33.1.8.1 |
| upsStartupAfterDelay Setting this object will start the output after the
indicated number of seconds, including starting the
UPS, if necessary. Setting this object to 0 will
cause the startup to occu… | scalar | seconds Integer32 | .1.3.6.1.2.1.33.1.8.3 |
| upsRebootWithDuration Setting this object will immediately shutdown (i.e.,
turn off) either the UPS output or the UPS system (as
determined by the value of upsShutdownType at the time
of shutdown) for … | scalar | seconds Integer32 | .1.3.6.1.2.1.33.1.8.4 |
| upsAutoRestart Setting this object to 'on' will cause the UPS system
to restart after a shutdown if the shutdown occurred
during a power loss as a result of either a
upsShutdownAfterDelay or an … | scalar | Enumeration | .1.3.6.1.2.1.33.1.8.5 |