upsConfigInputVoltage
UPS-MIB ·
.1.3.6.1.2.1.33.1.9.1
Object
scalar
r/w
RMS Volts NonNegativeInteger
The magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
Syntax
RMS Volts NonNegativeInteger
- Source
- NonNegativeInteger
- Base type
Integer32
Values & Constraints
Type Constraints
range: 0..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsConfigHighVoltageTransferPoint The maximum line voltage allowed before the UPS
system transfers to battery backup. | scalar | RMS Volts NonNegativeInteger | .1.3.6.1.2.1.33.1.9.10 |
| upsConfigInputFreq The nominal input frequency. On those systems which
support read-write access to this object, if there is
an attempt to set this variable to a value that is not
supported, the re… | scalar | 0.1 Hertz NonNegativeInteger | .1.3.6.1.2.1.33.1.9.2 |
| upsConfigOutputVoltage The magnitude of the nominal output voltage. On
those systems which support read-write access to this
object, if there is an attempt to set this variable to
a value that is not s… | scalar | RMS Volts NonNegativeInteger | .1.3.6.1.2.1.33.1.9.3 |
| upsConfigOutputFreq The nominal output frequency. On those systems which
support read-write access to this object, if there is
an attempt to set this variable to a value that is not
supported, the r… | scalar | 0.1 Hertz NonNegativeInteger | .1.3.6.1.2.1.33.1.9.4 |
| upsConfigOutputVA The magnitude of the nominal Volt-Amp rating. | scalar | Volt-Amps NonNegativeInteger | .1.3.6.1.2.1.33.1.9.5 |
| upsConfigOutputPower The magnitude of the nominal true power rating. | scalar | Watts NonNegativeInteger | .1.3.6.1.2.1.33.1.9.6 |
| upsConfigLowBattTime The value of upsEstimatedMinutesRemaining at which a
lowBattery condition is declared. For agents which
support only discrete (discontinuous) values, then the
agent shall round u… | scalar | minutes NonNegativeInteger | .1.3.6.1.2.1.33.1.9.7 |
| upsConfigAudibleStatus The requested state of the audible alarm. When in
the disabled state, the audible alarm should never
sound. The enabled state is self-describing. Setting
this object to muted(3… | scalar | Enumeration | .1.3.6.1.2.1.33.1.9.8 |
| upsConfigLowVoltageTransferPoint The minimum input line voltage allowed before the UPS
system transfers to battery backup. | scalar | RMS Volts NonNegativeInteger | .1.3.6.1.2.1.33.1.9.9 |