upsConfigAudibleStatus
UPS-MIB ·
.1.3.6.1.2.1.33.1.9.8
Object
scalar
r/w
Enumeration
The requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect.
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | disabled |
2 | enabled |
3 | muted |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsConfigInputVoltage The magnitude of the nominal input voltage. On those
systems which support read-write access to this
object, if there is an attempt to set this variable to
a value that is not su… | scalar | RMS Volts NonNegativeInteger | .1.3.6.1.2.1.33.1.9.1 |
| upsConfigHighVoltageTransferPoint The maximum line voltage allowed before the UPS
system transfers to battery backup. | scalar | RMS Volts NonNegativeInteger | .1.3.6.1.2.1.33.1.9.10 |
| upsConfigInputFreq The nominal input frequency. On those systems which
support read-write access to this object, if there is
an attempt to set this variable to a value that is not
supported, the re… | scalar | 0.1 Hertz NonNegativeInteger | .1.3.6.1.2.1.33.1.9.2 |
| upsConfigOutputVoltage The magnitude of the nominal output voltage. On
those systems which support read-write access to this
object, if there is an attempt to set this variable to
a value that is not s… | scalar | RMS Volts NonNegativeInteger | .1.3.6.1.2.1.33.1.9.3 |
| upsConfigOutputFreq The nominal output frequency. On those systems which
support read-write access to this object, if there is
an attempt to set this variable to a value that is not
supported, the r… | scalar | 0.1 Hertz NonNegativeInteger | .1.3.6.1.2.1.33.1.9.4 |
| upsConfigOutputVA The magnitude of the nominal Volt-Amp rating. | scalar | Volt-Amps NonNegativeInteger | .1.3.6.1.2.1.33.1.9.5 |
| upsConfigOutputPower The magnitude of the nominal true power rating. | scalar | Watts NonNegativeInteger | .1.3.6.1.2.1.33.1.9.6 |
| upsConfigLowBattTime The value of upsEstimatedMinutesRemaining at which a
lowBattery condition is declared. For agents which
support only discrete (discontinuous) values, then the
agent shall round u… | scalar | minutes NonNegativeInteger | .1.3.6.1.2.1.33.1.9.7 |
| upsConfigLowVoltageTransferPoint The minimum input line voltage allowed before the UPS
system transfers to battery backup. | scalar | RMS Volts NonNegativeInteger | .1.3.6.1.2.1.33.1.9.9 |