upsStartupAfterDelay
TRIPPUPS1-MIB ·
.1.3.6.1.4.1.850.1.1.9.3
Object
scalar
mandatory
r/w
Integer32
Setting this object will start the output after the indicated number of seconds, includeing starting the UPS, if necessary. Setting this object to 0 will cause the start to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootDuration countdown in progress. When read, upsStartupAfterDelay will return the number of seconds until start, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall depend upon the value of upsAutoRestart at that time. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted. UNITS seconds
Context
- MIB
- TRIPPUPS1-MIB
- OID
.1.3.6.1.4.1.850.1.1.9.3- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- upsControl
- Siblings
- 4
Syntax
Integer32
Values & Constraints
Object Constraints
range: -1-32767
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsShutdownType mandatory Setting this object will start the output after the
indicated number of seconds. Setting this object to 0
will cause the UPS to start the output immediately.
If the output is alr… | scalar | Enumeration | .1.3.6.1.4.1.850.1.1.9.1 |
| upsShutdownAfterDelay mandatory Setting this object will shutdown (i.e., turn off)
either the UPS output or the UPS system (as determined
by the value of upsShhutdownType at the time of
shutdown) after the indic… | scalar | Integer32 | .1.3.6.1.4.1.850.1.1.9.2 |
| upsRebootDuration mandatory Setting this object will immediately shutdown (i.e.,
turn off) either the UPS output or the UPS system (as
determined by the value of the upsShutdownType at the time
of shutdown) … | scalar | Integer32 | .1.3.6.1.4.1.850.1.1.9.4 |
| upsAutoRestart mandatory Setting this object to 'on' will cause the UPS system
to restart after a shutdown if/when utility power is present. | scalar | Enumeration | .1.3.6.1.4.1.850.1.1.9.5 |