upsConfigInputVoltageHigh
TRIPPUPS1-MIB ·
.1.3.6.1.4.1.850.1.1.10.11
Object
scalar
mandatory
r/w
Integer32
If the value of the input voltage (in Volts) exceeds this value, a utilityVoltageHigh trap will be triggered.
Context
- MIB
- TRIPPUPS1-MIB
- OID
.1.3.6.1.4.1.850.1.1.10.11- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- upsConfig
- Siblings
- 4
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsConfigInputVoltageLow mandatory If the value of the input voltage (in Volts) falls below this value, a
utilityVoltageLow trap will be triggered. | scalar | Integer32 | .1.3.6.1.4.1.850.1.1.10.12 |
| upsConfigOutputPercLoadHigh mandatory If the value of the output percent load exceeds this value, a upsOverload trap
will be triggered. | scalar | Integer32 | .1.3.6.1.4.1.850.1.1.10.13 |
| upsConfigBatteryPercLow mandatory If the value of the battery percent capacity falls below this value, a lowBattery
trap will be triggered. | scalar | Integer32 | .1.3.6.1.4.1.850.1.1.10.14 |
| upsConfigBatteryTemperatureHigh mandatory If the value of the battery temperature exceeds this value, a
batteryTemperatureHigh trap will be triggered. | scalar | Integer32 | .1.3.6.1.4.1.850.1.1.10.15 |