upsBatteryStatus
TRIPPUPS1-MIB ·
.1.3.6.1.4.1.850.1.1.2.1
Object
scalar
mandatory
Enumeration
The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the batteries are fully charged. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigMinutesRemaining. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost.
Context
- MIB
- TRIPPUPS1-MIB
- OID
.1.3.6.1.4.1.850.1.1.2.1- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- upsBattery
- Siblings
- 5
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | unknown |
2 | batteryNormal |
3 | batteryLow |
4 | batteryDepleted |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsSecondsOnBattery mandatory If the unit is on battery power, the elapsed time
since the UPS last switched to battery power, or the
time since the network management subsystem was last
restarted, whichever is… | scalar | Integer32 | .1.3.6.1.4.1.850.1.1.2.2 |
| upsEstimatedMinutesRemaining mandatory An estimate of the time to battery charge depletion
under the present load conditions if the utility power
were to be lost and remain off. UNITS - minutes | scalar | Integer32 | .1.3.6.1.4.1.850.1.1.2.3 |
| upsBatteryChargeRemaining mandatory The estimate of the battery charge remaining expressed
as a percent of full charge. | scalar | Integer32 | .1.3.6.1.4.1.850.1.1.2.4 |
| upsBatteryVoltage mandatory The magnitude of the present battery voltage. UNITS 0.1 Volt DC. | scalar | Integer32 | .1.3.6.1.4.1.850.1.1.2.5 |
| upsBatteryTemperature mandatory The ambient temperature at or near the UPS Battery.
UNITS degrees Centigrade | scalar | Integer32 | .1.3.6.1.4.1.850.1.1.2.7 |