tlpUpsOutletCommand
TRIPPLITE-PRODUCTS ·
.1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.6
Object
column
r/w
Enumeration
Reading this value will always return 0. Setting this value to turnOff(1) will turn off the outlet. Setting this value to turnOn(2) will turn on the outlet. Setting this value to cycle(3) will turn the outlet off, then turn it back on.
Context
- MIB
- TRIPPLITE-PRODUCTS
- OID
.1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.6- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- tlpUpsOutletEntry
- Table
- tlpUpsOutletTable
- Siblings
- 13
Syntax
Enumeration
Values & Constraints
Enumerated Values
0 | idle |
1 | turnOff |
2 | turnOn |
3 | cycle |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| tlpUpsOutletIndex The table row index for the ups outlet. | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.1 |
| tlpUpsOutletRampAction The ramp action to take on a given outlet when powering on the
device. If this receptacle is not controllable, as denoted by
tlpUpsOutletControllable, then this value will always … | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.10 |
| tlpUpsOutletRampDelay The number of seconds to delay before powering on the given outlet.
If this receptacle is not controllable, as denoted by
tlpUpsOutletControllable, then this value will always ret… | column | seconds SNMPv2-SMIInteger32 | .1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.11 |
| tlpUpsOutletShedAction The shed action to take on a given outlet when powering off the
device. If this receptacle is not controllable, as denoted by
tlpUpsOutletControllable, then this value will always… | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.12 |
| tlpUpsOutletShedDelay The number of seconds to delay before powering off the given outlet.
If this receptacle is not controllable, as denoted by
tlpUpsOutletControllable, then this value will always re… | column | seconds SNMPv2-SMIInteger32 | .1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.13 |
| tlpUpsOutletGroup The tlpUpsOutletGroupIndex group index of the respective group to
which the given outlet is assigned, or zero (0) if the given
outlet is not grouped. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.14 |
| tlpUpsOutletName A user-definable string identifying the name of the outlet. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.2 |
| tlpUpsOutletDescription A user-definable string identifying the device(s) connected to
the given outlet. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.3 |
| tlpUpsOutletState The current state of the outlet. | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.4 |
| tlpUpsOutletControllable Denotes whether this outlet is controllable. | column | SNMPv2-TCTruthValue | .1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.5 |
| tlpUpsOutletVoltage The magnitude of the present output voltage for a given outlet.
If the voltage measurement is not supported for an individual
receptacle regardless whether device-wide or just for… | column | 0.1 Volts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.7 |
| tlpUpsOutletCurrent The present output current, in hundredths of amps, of a given outlet.
If the current measurement is not supported for an individual
receptacle regardless whether device-wide or ju… | column | 0.01 Amps SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.8 |
| tlpUpsOutletPower The output power of a given outlet. If the power measurement is
not supported for an individual receptacle regardless whether
device-wide or just for this receptacle, then this va… | column | Watts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.9 |