tlpUpsInputEntry
TRIPPLITE-PRODUCTS ·
.1.3.6.1.4.1.850.1.1.3.1.3.2.1.1
Object
row
An entry containing information applicable to all input lines per each ups managed by this agent.
Context
- MIB
- TRIPPLITE-PRODUCTS
- OID
.1.3.6.1.4.1.850.1.1.3.1.3.2.1.1- Type
- row
- Status
- current
- Parent
- tlpUpsInputTable
- Table
- tlpUpsInputTable
- Children
- 10
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| tlpUpsInputLineBads A count of the number of times the input entered an out-of-tolerance
condition as defined by the manufacturer. This count is incremented
by one each time the input transitions fr… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.1 |
| tlpUpsInputWattHours The number of watt hours of energy utilized in the past 24 hours. Use
tlpUpsControlResetWattHours to reset the watt hours calculation algorithm. | column | WH SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.10 |
| tlpUpsInputNominalVoltage The nominal value of the input line voltage. This value may not
be supported on all models. If not supported, this value will return
ERROR_NO_SUCH_NAME. | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.2 |
| tlpUpsInputNominalFrequency The nominal value of the input line frequency. This value may not
be supported on all models. If not supported, this value will return
ERROR_NO_SUCH_NAME. | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.3 |
| tlpUpsInputLowTransferVoltage The minimum line voltage allowed before the ups system transfers to
battery backup. | column | 0.1 Volts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.4 |
| tlpUpsInputLowTransferVoltageLowerBound The lower boundary value of tlpUpsInputLowTransferVoltage as dictated
by the hardware of the unit. | column | 0.1 Volts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.5 |
| tlpUpsInputLowTransferVoltageUpperBound The upper boundary value of tlpUpsInputLowTransferVoltage as dictated
by the hardware of the unit. | column | 0.1 Volts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.6 |
| tlpUpsInputHighTransferVoltage The maximum line voltage allowed before the ups system transfers to
battery backup. | column | 0.1 Volts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.7 |
| tlpUpsInputHighTransferVoltageLowerBound The lower boundary value of tlpUpsInputHighTransferVoltage as dictated
by the hardware of the unit. | column | 0.1 Volts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.8 |
| tlpUpsInputHighTransferVoltageUpperBound The upper boundary value of tlpUpsInputHighTransferVoltage as dictated
by the hardware of the unit. | column | 0.1 Volts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.9 |
Indexes
| Object | Type | Syntax | OID |
|---|---|---|---|
| tlpDeviceIndex The table row index for the device. | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.1.2.1.1 |