tlpCoolingSetPointDegF
TRIPPLITE-PRODUCTS ·
.1.3.6.1.4.1.850.1.1.3.5.5.2.1.1
Object
The set point temperature the unit will control the temperature in tenths degrees Fahrenheit. If not supported, this value will always return ERROR_NO_SUCH_NAME.
Context
- MIB
- TRIPPLITE-PRODUCTS
- OID
.1.3.6.1.4.1.850.1.1.3.5.5.2.1.1- Type
- column
- Access
- readwrite
- Status
- current
- Units
- 0.1 degrees Fahrenheit
- Parent
- tlpCoolingConfigTemperatureFahrenheitEntry
- Table
- tlpCoolingConfigTemperatureFahrenheitTable
- Siblings
- 6
Syntax
0.1 degrees Fahrenheit SNMPv2-SMIInteger32
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| tlpCoolingSupplyAirHighLimitDegF Maximum allowed supply air temperature in tenths degrees Fahrenheit before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME. | column | 0.1 degrees Fahrenheit SNMPv2-SMIInteger32 | .1.3.6.1.4.1.850.1.1.3.5.5.2.1.2 |
| tlpCoolingSupplyAirLowLimitDegF Minimum allowed supply air temperature in tenths degrees Fahrenheit before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME. | column | 0.1 degrees Fahrenheit SNMPv2-SMIInteger32 | .1.3.6.1.4.1.850.1.1.3.5.5.2.1.3 |
| tlpCoolingMaxDeviationLimitDegF Maximum allowed air temperature deviation from set temperature before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME. | column | 0.1 degrees Fahrenheit SNMPv2-SMIInteger32 | .1.3.6.1.4.1.850.1.1.3.5.5.2.1.4 |
| tlpCoolingReturnAirHighLimitDegF Maximum allowed supply air temperature in tenths degrees Fahrenheit before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME. | column | 0.1 degrees Fahrenheit SNMPv2-SMIInteger32 | .1.3.6.1.4.1.850.1.1.3.5.5.2.1.5 |
| tlpCoolingReturnAirLowLimitDegF Minimum allowed supply air temperature in tenths degrees Fahrenheit before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME. | column | 0.1 degrees Fahrenheit SNMPv2-SMIInteger32 | .1.3.6.1.4.1.850.1.1.3.5.5.2.1.6 |
| tlpCoolingRemoteSetPointDegF The remote set point temperature the unit will control the temperature in tenths degrees Fahrenheit.
If not supported, this value will always return ERROR_NO_SUCH_NAME. | column | 0.1 degrees Fahrenheit SNMPv2-SMIInteger32 | .1.3.6.1.4.1.850.1.1.3.5.5.2.1.7 |