tlpAtsOutletPhase
TRIPPLITE-PRODUCTS ·
.1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.17
Object
column
Enumeration
Indicates on which phase or phases the given outlet is associated. For single phase devices, this object will always return phase1(1). For 3-phase devices with outlets wired to a single phase, this object will return phase1(1), phase2(2) or phase3(3). For 3-phase devices with outlets wired to two phases, this object will return phase1-2(4) for phases 1 and 2, phase2-3(5) for phases 2 and 3, and phase3-1(6) for phases 3 and 1. Devices that do not report phase connections will return unknown(0).
Context
- MIB
- TRIPPLITE-PRODUCTS
- OID
.1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.17- Type
- column
- Access
- readonly
- Status
- current
- Parent
- tlpAtsOutletEntry
- Table
- tlpAtsOutletTable
- Siblings
- 16
Syntax
Enumeration
Values & Constraints
Enumerated Values
0 | unknown |
1 | phase1 |
2 | phase2 |
3 | phase3 |
4 | phase1-2 |
5 | phase2-3 |
6 | phase3-1 |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| tlpAtsOutletIndex The table row index for the ats outlet. | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.1 |
| tlpAtsOutletRampAction The ramp action to take on a given outlet when powering on the
device. If this receptacle is not controllable, as denoted by
tlpAtsOutletControllable, then this value will always … | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.10 |
| tlpAtsOutletRampDelay The number of seconds to delay before powering on the given outlet.
If this receptacle is not controllable, as denoted by
tlpAtsOutletControllable, then this value will always ret… | column | seconds SNMPv2-SMIInteger32 | .1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.11 |
| tlpAtsOutletShedAction The shed action to take on a given outlet when powering off the
device. If this receptacle is not controllable, as denoted by
tlpAtsOutletControllable, then this value will always… | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.12 |
| tlpAtsOutletShedDelay The number of seconds to delay before powering off the given outlet.
If this receptacle is not controllable, as denoted by
tlpAtsOutletControllable, then this value will always re… | column | seconds SNMPv2-SMIInteger32 | .1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.13 |
| tlpAtsOutletGroup The tlpAtsOutletGroupIndex group index of the respective group to
which the given outlet is assigned, or zero (0) if the given
outlet is not grouped. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.14 |
| tlpAtsOutletBank Indicates on which bank the given outlet is located. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.15 |
| tlpAtsOutletCircuit Indicates on which circuit the given outlet is wired. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.16 |
| tlpAtsOutletName A user-definable string identifying the name of the outlet. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.2 |
| tlpAtsOutletDescription A user-definable string identifying the device(s) connected to
the given outlet. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.3 |
| tlpAtsOutletState The current state of the outlet. | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.4 |
| tlpAtsOutletControllable Denotes whether this outlet is controllable. | column | SNMPv2-TCTruthValue | .1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.5 |
| tlpAtsOutletCommand Reading this value will always return 0. Setting this value
to turnOff(1) will turn off the outlet. Setting this value
to turnOn(2) will turn on the outlet. Setting this value to
… | column | Enumeration | .1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.6 |
| tlpAtsOutletVoltage The magnitude of the present output voltage for a given outlet.
If the voltage measurement is not supported for an individual
receptacle regardless whether device-wide or just for… | column | 0.1 Volts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.7 |
| tlpAtsOutletCurrent The present output current, in hundredths of amps, of a given outlet.
If the current measurement is not supported for an individual
receptacle regardless whether device-wide or ju… | column | 0.01 Amps SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.8 |
| tlpAtsOutletPower The output power of a given outlet. If the power measurement is
not supported for an individual receptacle regardless whether
device-wide or just for this receptacle, then this va… | column | Watts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.9 |